 Noosa Fair Redevelopment – Lanyana Way, Noosa Heads

© 2013 - TTM Consulting Pty Ltd                                                              Reference No: 13GCA0108 R02_2.docx


Table 2: Background Creep Noise Limits at Noise Sensitive Properties

                                                             Measured Ambient                Time-Varying
Receiver*                    Time Period                         Noise Levels            Noise Emission Criteria
                                                                     LA90,T                       LAeq,T
                          Day (7am – 6pm)                             46                            51

                       Evening (6pm – 10pm)                           40                            45
 1 and 3
                         Night (10pm – 7am)                           37                            42

                    Early Morning (6am – 7am)*                        43                            48

                          Day (7am – 6pm)                             46                            51

                       Evening (6pm – 10pm)                           39                            44
     2
                         Night (10pm – 7am)                           33                            38

                    Early Morning (6am – 7am)*                        42                            47

*Receiver 1 comprises of dwellings located in Coral Tree Avenue. Receiver 2 is dwellings located in Wyandra
Street, and Receiver 3 is the proposed on-site residential building.


4.1.2      Sleep Disturbance
Sleep disturbance criterion levels are taken from the EPA Ecoaccess Guideline: Planning for Noise
Control (PNC). As a rule in planning for short-term or transient noise events, the indoor sound
pressure level should not exceed approximately 45 dB(A) Lmax more than 10-15 times per night.
The corresponding external noise level from the PNC, assuming partially closed windows, is 52
dB(A) Lmax, measured in the free field (4m from the façade of a building).


4.1.3      Mechanical Plant
Assessment of mechanical plant is pursuant to the noise requirements of EPP 2008 Background
Creep (steady-state) and potentially the EPA Ecoaccess Guideline: Planning for Noise Control.

The Ecoaccess Guideline: Planning for Noise Control recommends that a criterion is set based
upon background noise planning levels for the applicable receiver land use. Table 1 and Table 2 of
the guideline have been referred to in establishing the Ecoaccess criteria.

The design levels for both criteria are presented in Table 3 over page. To achieve a reasonable
balance between satisfying noise limits and the cost of achieving the noise limits, we recommend
that the EPP2008 Background Creep is a suitable criterion.




www.ttmgroup.com.au
                                  T: 07 5514 8000 F: 07 5514 8144 E: [email protected]            Page 9
Log in to download the original file

Environmental_Acoustic Report.pdf · 4.4 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.