GOLDER ASSOCIATES Work Order : EBd608438 Page Number : SofS

Client x
06683025 ALS Quote Reference: EN/002/0S Issue Date 2 12 Jul 2006 ALS Enutrorenantai

Project

Method Reference Summary

The analytical procedures used by ALS Environmental are based on established intemationally-recognized procedures such as those published by the US EPA, APHA, AS and NEPM. In house procedure are employed in the
absence of documented standards or by client request. The following report provides brief descriptions of the analytical procedures employed for results reported herein. Reference methods from which ALSE methods are
based are provided in parenthesis.

 

Matrix Type: WATER Method Reference Summary

Preparation Methods.
EN25 : Digestion for Total Recoverable Metals - USEPA SW846-3005 Method 3005 is a Nitric/Hydrochloric acid digestion procedure used to prepare surface and ground water samples for
analysis by \CPAES or ICPMS. This method is compliant with NEPM (1999) Schedule B(3) (Appdx. 2)

Analytical Methods.
EA041 : Colour (True) - APHA 20th ed., 2120 B. This method is compliant with NEPM (1999) Schedule B(3) (Appdx. 2)

ED037-P : Alkalinity by PC Titrator - APHA 20th ed.., 2320 B This procedure determines alkalinity by both manual! measurement and automated measurement (e.g. PC Titrate) using pH 4.5 for
indicating the total alkalinity end-point. This method is compliant with NEPM (1999) Schedule B(3) (Appdx. 2)

EDO4OF : Major Anions - Filtered - APHA 20th ed., 3120 Sulphur and Silcon content is determined by ICP/AES and reported as Sulphate after conversion by gravimetric factor.
EDO045-P : Chloride by PC Titrator - APHA 20th ed., 4500 C!-B. Automated Silver Nitrate titration.

EDO93F : Major Cations - Fittered - APHA 20th ed., 3120; USEPA SW 846 - 6010 The ICPAES technique ionises filtered sample atoms emitting a characteristic spectrum. This spectrum is then
compared against matrix matched standards for quantification. This method is compliant with NEPM (1999) Schedule B(3) (Appdx. 2)

EGOOSF : Dissolved Metals by ICP-AES - APHA 20th ed., 3120; USEPA SW 846-6010 The ICPAES technique ionises the 0.45um filtered samples, emitting a characteristic spectrum which is
compared against matrix matched standards. This method is compliant with NEPM (1999) Schedule B(3) (Appdx. 2)

EGO005T : Total Recoverable Metals by ICP-AES - APHA 20th ed., 3120; USEPA SW 846 - 6010 Samples are digested by USEPA 3005 prior to analysis. The ICPAES technique ionises the
sample atoms emitting a characteristic spectrum. This spectrum is then compared against matrix matched standards for quantification. This method is compliant with NEPM (1999) Schedule 8(3)
(Appdx. 2)

EG020A-F ; Dissolved Metals by ICP-MS - Sulte A - (APHA 20th ed., 3125; USEPA SW846 - 6020, ALS QWI-EN/EG020): The ICPMS technique utilizes a highly efficient argon plasma to ionize
selected elements. lons are then passed into a high vacuum mass spectrometer, which separates the analytes based on their distinct mass to charge ratios prior to their measurement by a
discrete dynode ion detector.

Report version KICINA 208 ‘A Campbell Broinats unvtod Carnpenty

Used in these records

About this file

File size
7.5 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Application part 2 [As Published].pdf · 7.5 MB (large file)