Further, the site is not located within the flood hazard overlay mapping and therefore this flood hazard overlay
code an is not applicable to this development.



Issue 14 – Roofwater Capture and Reuse
  Justification for the tank sizing has been provided based on an assumption that reuse is only required for
  communal landscaping. The Sustainable Building Design Code seeks to maximise water efficiency and
  requires non-potable reuse, which includes fixtures both external and internal to the dwelling.

Response

For QDC 4.2 (residential buildings), the requirement will only apply to new Class 1 and 10 buildings (i.e. houses
and their garages) and not multi-unit residential buildings (Class 2).

As per our previous response correspondence and meeting with Council engineers (Morgan Gaffney & Mark
Lewis), we have now revised our proposal to consider re-use for the following external purposes.
    -    Communal Landscaping
    -    Pool top up
    -    Communal WC’s


The following extract provides the criteria has been adopted and calculations of re-use quantities.




SCG Consulting Engineers                            Page 2 of 5                                  SCG Ref: 33132(L2)
Log in to download the original file

SCG 33132(L2).pdf · 1.2 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.