PUMP CONNECTED TO
PAVEMENT LANDSCAPED CONTROL PANEL FOR MAINS
FINISHED SURFACE OVERRIDE WHEN TANK EMPTY RAINWATER TANK HEAVY DUTY GRATE WITH
CHILD PROOF LOCK
RL. 49.48
BACKFILL WITH APPROVED EXCAVATED 1. LABELS TO BE FIXED ADJACENT TO ALL OUTDOOR WATERING
MATERIAL OR APPROVED ORDINARY FILL TAPS STATING THAT THE WATER IS NOT TO BE CONSUMED.
COMPACTED IN MAX. 150mm LAYERS TO 2. PROVIDE EMERGENCY MAINS TAP ADJACENT TO WATER METER
THE DENSITY OF THE ADJACENT SOIL AND CONNECTED TO THE MAINS SUPPLY. HIGH LEVEL ALARM
3. R.W.T. SUPPLY MUST NOT BE CONNECTED TO DRINKING AND
WELL TAMPED INITIAL ZONES SHALL BE BATHING WATER TAP OUTLETS.
Ø65 PN9 UPVC Ø65 x Ø50 TAPER
10mm CRUSHED ROCK WELL TAMPED & 4. FIRST FLUSH DEVICES TO BE FITTED TO ALL DOWNPIPES PIT VOL =3 4m
SWJ RISING MAIN Ø50 x 50 TEE
AT OPTIMUM MOISTURE CONTENT CONNECTED TO R.W.T.
500
5. ALL DOWNPIPES TO BE ENTIRELY P.V.C. ALL PIPES TO BE
BEDDING HAUNCH & OVERLAY ZONES BACKUP SEALED UP TO UNDERSIDE OF ROOF GUTTERS.
0.450
Y
SHALL BE 10mm CRUSHED ROCK WELL MAINS WATER 6. ENSURE ALL CONNECTIONS WITHIN CHARGED SYSTEMS ARE Ø50 90 DEGREE BEND
TAMPED & AT OPTIMUM MOISTURE AIR GAP SOLVENT WELDED.
Ø
PUMP 2 CUT-IN
CONTENT 7. TANK TO BE CONNECTED TO SYDNEY WATER APPROVED
FIRST FLUSH CONTROL PANEL TO ENSURE MAINS WATER SUPPLY IS
PROVIDED WHEN TANK EMPTIES.
X
DEVICE Ø50 UPVC PN9 SWJ PIPE
PIPE Ø W Xmin Y 8. ALL PLUMBING WORKS TO BE CARRIED OUT BY A LICENSED
500
W RAINWATER PLUMBER IN ACCORDANCE WITH SYDNEY WATER GUIDELINES
100 - 150 300 75 75 STORAGE ZONE AND 'NSW CODE OF PRACTICE: PLUMBING AND DRAINAGE' Ø50 STOP VALVE
NOTES:
2m
TANK WATER
Ø50 NON-RETURN VALVE
1. BACKFILL CRUSHED ROCK WETMIX. PLACED & COMPACTED IN SUPPLY VIA CUT - IN
MAX. 150mm LAYERS TO 95% MODIFIED MAX. DRY DENSITY. PUMP
2. REFER TO PIPE LAYING SPECIFICATIONS FOR DETAILS WATER SUPPLY
AS PER BASIX
500
PUMP
TYPICAL PIPE LAYING DETAILS REQUIREMENTS ANAEROBIC ZONE
NTS
CUT - OUT
TANK WATER TANK STAND TO OVERFLOW LINE 2 x GROUNDFOS AP12.50.111
SUPPLY VIA PUMP MANUFACTURERS PUMPS INSTALLED TO
DETAILS CHARGED INLET PIPE MANUFACTURERS SPECIFICATIONS
RAINWATER TANK DIAGRAM 900SQ 600 DEEP SUMP 50 HIGH CONCRETE PEDESTAL
N.T.S.
PUMP-PUT PIT DETAIL
N.T.S.
DOWNPIPE AS
SPECIFIED
ADAPTOR TO
TOP OF GUTTER TO BE 50mm SUIT DOWNPIPE
HIGHER THAN OVERFLOW
METAL ROOF
MEDIUM DUTY
0.250
3° FALL 300x200 BOX
FINISHED GROUND LEVEL
GRATE GUTTER SAFETY
OVERFLOW
PUMP NOTES
400x85
1.000 RAINWATER 45° ELBOW 1. THE PUMPS SHALL BE PROGRAMMED TO WORK ALTERNATIVELY SO AS TO ALLOW BOTH PUMPS TO
HEAD HAVE CONTINUOUS OPERATION.
45° JUNCTION
100 MIN
FLASHING TO 2. A LOW LEVEL FLOAT SHALL BE PROVIDED TO ENSURE THAT THE MINIMUM REQUIRED WATER LEVEL
DRIVEWAY EXTEND 1200 INTO
Ø100 DOWN PIPE
IS MAINTAINED WITHIN THE SUMP AREA OF THE BELOW GROUND TANK. IN THIS REGARD THIS FLOAT
ROOF SPACE MAIN STORMWATER WILL FUNCTION AS THE CUT-OUT SWITCH.
90° ELBOW
TO SPEC's LINE AS SPECIFIED
LONGITUDNAL 3. IN THE EVENT THAT A PUMP FAILS TO OPERATE WHEN THE WATER IN THE WET WELL REACHES THE
PUMP START, THE OTHER PUMP SHALL BE ACTIVATED AND A VISIBLE ALARM INITIATED. IN THE
SLOPE 1% STORMWATER PIPE EVENT THAT BOTH PUMPS FAIL TO OPERATE, AN AUDIBLE ALARM SHALL BE INITIATED.
150 AS SPECIFIED
4. PUMPING EQUIPMENT SHALL BE SECURELY FIXED TO THE WET WELL USING CORROSION
TYPICAL GRATED DRAIN DETAIL RAINWATER OUTLET WITH BOX GUTTER DETAIL TYPICAL DOWNPIPE CONNECTION DETAIL RESISTANT FIXINGS.
NTS SCALE 1:20 SCALE 1:50 5. PUMPS SHALL HAVE FLANGES OR UNIONS TO FACILITATE REMOVAL.
6. PUMPS SHALL HAVE MINIMUM 10L/s CAPACITY.
PLANTING SOIL
PAVEMENT AS SPECIFIED
75mm DEEP BLUE METAL
100
SUB-GRADE AS SPECIFIED RELN PIT
GEO-FABRIC MEMBRANE
Ø100 UPVC STUB
10mm CRUSHED ROCK
WRAPPED IN GEOFABRIC
100
Ø90 SUBSOIL [email protected]% FALL
FALL 1% MIN.
MIN.300 CAP OFF OPENING OR
RUN PIPE INTO 'T' PIECE
SUB-SOIL IN PAVED AREAS Ø100 UPVC 'T' PIECE
TYPICAL PLANTER DRAIN DETAIL
SCALE 1:20 A FOR D.A.. SUBMISSION 02/05/23
REMOVABLE TRIANGULAR
LIGHT DUTY HINGED CHILD
SCREEN HOT DIPPED
2.250x450 PROOF LOCK WITH SPRUNG
GALVANISED LYSAGHT
J BOLT GALVANISED (TYPE A)
N. KOLOFF & ASSOCIATES
MAXIMESH TYPE RH3030
WITH HANDLE
OUTLET Ø100 UPVC
CONNECTED TO EXISTING
INLET STORMWATER PIPE CIVIL & STRUCTURAL ENGINEERS
INLET A.B.N. 15 657 583 235
REPLACEABLE
GEOTEXTILE
POSTAL ADDRESS: PHONE: (02) 9560 0064
FILTER FABRIC
FOUR 1/2 BRICK P.O. BOX 99, ANNANDALE FAX: (02) 9560 0065
KEEPERS
NSW 2038, AUSTRALIA [email protected] MOBILE: 0417 485 481
DESCRIPTION OF WORKS AT : INDEX 1018A/2021
Nikolai Koloff
SHEET C7.00 B
PROPOSED NEW DUPEX
PERMANENT GEOTEXTILE FILTER 4 x Ø100 RELIEF DRAINS WITH
FABRIC SURROUNDING 14mm GRAVEL SURROUND WRAPPED
AGGREGATE IN GEOTEXTILE FABRIC APPROVED BY:................................
NO. 36 ELAND STREET N. Koloff - Structural Engineer
SILT ARRESTOR PIT P1 DETAIL SUNSHINE BEACH QLD 4567 B.E. (Hon.), L.G.E. M.I.E. AUST,. M.Eng. C.P. Eng.
Registration No.616868 NER
SCALE 1:20
STORMWATER DRAINAGE DETAILS DATE : 02/05/2023
GSEducationalVersion
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
OPW23/0139 - Appendix B - Engineering PlansRelated documentApplication case desk ↗
About this file
- File size
- 4.1 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.