Appendix F Engineering Report - 14-16 Mary Street, Noosaville - Bounce Hostels 15.6.2018

Attached to the e-mail Visitor Accommodation Type 4 Conventional - 122 beds (Engineering Report, Economic Study, Geotechnical Investigation, Flood Certificate, Accoustic Report, Management Plan) MCU18/0102.msg.

of 9

Page text shows just the words. Original shows the document exactly as it was published.

Appendix F – Engineering

MATERIAL CHANGE OF USE TO ESTABLISH RESIDENTIAL
USES - VISITOR ACCOMMODATION TYPE 4
CONVENTIONAL


14-16 Mary Street, NOOSAVILLE described as Lots 3 & 4 on RP
122928

Applicant: Bounce Hostel Noosa Pty Ltd ATF The Bounce Hostel
Unit Trust

Date: 15th June 2018




      Unit 5, 100 Pickering Street, Enoggera         1
Log in to download the original file

Appendix F Engineering Report - 14-16 Mary Street, Noosaville - Bounce Hostels 15.6.2018.pdf · 3.2 MB (large file)

The download may take up to a minute.

Full text of the other 8 pages

Page 2

     ENGINEERING REPORT
     Address:                     14-16 Mary Street, Noosaville
     Applicant/Client:            Bounce Hostels
1.       Background

     Tod Consulting have been engaged to provide technical advice on the impacts of a proposed
     development at 14-16 Mary Street, Noosaville (Lot 3&4 RP 122928). The property is within the flood
     hazard zone and within the Acid Sulphate Soils overlay area

     The site is also traversed by a 450mm diameter truck sewer located approximately 13m from the rear
     boundary. The site currently contains an existing building that is used for retail purposes. The building
     is surrounded by hardstand areas (a combination of compacted gravel and concrete pavements).

     A prelodgement meeting was held with Noosa Council in October 2017. At this meeting Council asked
     that the following engineering issues be addressed with the Material Change of Use development
     application:
         •    Flood – especially in regard to proposed basement car park
         •    Acid Sulphate Soils – Investigation and Management Plan
         •    Stormwater Management
         •    Access and car parking - particularly for service vehicles
         •    Any additional works or treatment in the vicinity of the trunk sewer including advice from
              Unitywater

     The purpose of this report is to address the above issues and provide likely engineering solutions for
     each.

2.       Flood impacts and protection of the basement car park

     A food certificate for the site has been obtained and it confirms that the defined flood level for the site
     is RL2.4 AHD for a 1% AEP Under 2100 Climate Change Conditions. The current levels on the site vary
     from RL 2.0 to RL 2.3 AHD. Preliminary Architectural drawings show proposed floor levels for the hostel
     rooms and facilities at RL 2.7 to provide adequate free board above the defined flood level. The existing
     kerb and channel invert levels in Mary Street at this location are between RL 1.6 and 1.7 AHD with the
     footpath level at RL 1.8 to 1.9 AHD.

     To protect the basement car park from flooding it is proposed to install a proprietary automatic flood
     barrier at the top for the ramp just inside the property boundary. There are several automatic flood gates
     on the market that use the rising flood levels and the associated hydraulic differential to activate the
     barrier and raise it to protect the car park from flood waters. They do not require power or human
     intervention. The flood gate will be located between the perimeter retaining walls that will be used to lift
     the site levels above the defined flood level. Refer architectural elevations and sections for further
     details. The links below are two examples of the type of flood barrier proposed.

     http://floodbreak.com

     https://flowdefence.com.au/



                                                                                                               1
     17699 - Bounce Hostel, 16 Mary Street Noosaville – Engineering Report – Rev A

Page 3

     The access ramp to the basement carpark will be exposed to the weather and therefore run off from
     the ramp will need to be collected and disposed of. It is proposed to install a grated drain at the base of
     the ramp to collect runoff. This will be discharged into a sealed storage tank and pump below the
     basement car park which would be set up to pump to the street during a rainfall event. It is necessary
     to have a sealed collection tank instead of a soak away pit due to the groundwater levels for the site
     being above the basement level. A soak away drain located at the basement level connected to the
     grated drain would, at times, act in reverse and allow ground water into the basement. (Refer Geotech
     report). The catchment area of the ramp is approximately 84m2, so a 2500 litre tank would also provide
     emergency storage for the equivalent of a 30mm rainfall in the event of a power failure. In an extreme
     event, coinciding with a power failure, the basement area would offer additional storage capacity. For
     example, if 500mm of rain was to fall with power being off, the depth of water accumulating in the
     basement would be only 53mm in depth. To put this in perspective, data from the Bureau of
     Meteorology indicates that the maximum daily rainfall recorded at Tewantin was 310mm in August
     2007 – refer attached. The grated drain, storage tank and pump system would also be able to dewater
     the basement area once the power was restored. It should be noted that the storage tank and pump is
     not required to keep flood waters out of the basement.

3.       Acid Sulphate Investigation and Management

     Please refer to the separate report prepared by Core Consultants.

4.       Stormwater Management

         4.1. Existing network and legal point of discharge

     Stormwater from the site would need to be piped to the street and discharged to the kerb and channel
     using kerb adaptors as there is no existing stormwater pits in front of the development site to connect
     to. The nearest stormwater pit is located approximately 40m to the east. An inspection of this pit has
     identified that the invert level is less than 1.0m below the road surface. Based on minimum allowable
     pipe grades and sizes, and existing road levels there would insufficient cover if a pipe was extended
     from this pit to the closest point in front of the development site. Note the existing kerb and channel
     has a grade of less than 0.5% and falls both east and west from the area in front of the site. ie the site
     is located at the crest of the road. The discharge from the site would therefore be split to the east and
     west side of the building and discharged to the street at both sides of the property. The reception area
     roof area could be separately piped directly to the kerb and channel. The number of discharge points
     can be determined during the detailed design of the building hydraulic plans.

         4.2. Stormwater Quantity

     The existing building and concrete pavement areas on the site have a combined area of 875m2. In
     addition to this there is over 1080m2 of unsealed compacted gravel hardstand parking area surrounding
     the existing building – this is best viewed in the 2015 aerial photo. Refer marked up aerial plan below
     showing these areas. Given the nature of this hardstand pavement we believe that, conservatively,
     50% of this area can be included in the impervious area of the existing site. As such the total impervious
     area for the existing site is effectively 1415m2. The proposed development includes buildings and
     impervious (paved areas) totalling 1433m2. Note the drying area on east side of building will be either
     permeable paving or turfed. As there is only a minor increase in the impervious area we contend that
     on-site detention is not necessary.




                                                                                                              2
     17699 - Bounce Hostel, 16 Mary Street Noosaville – Engineering Report – Rev A

Page 4

Existing Roof and Paved areas




Existing Gravel Hardstand areas




                                                                                3
17699 - Bounce Hostel, 16 Mary Street Noosaville – Engineering Report – Rev A

Page 5

    4.3. Stormwater Quality

Under the State Planning Policy – Water, the assessment benchmark for water quality treatment states
that treatment of stormwater is required only if a material change of use application involves premises
greater than 2,500m2. As the development is on a land area of 2293m2, the requirement for stormwater
quality treatment is therefore not triggered. Notwithstanding, it has been suggested by Council officers
that Division 20 of the Noosa Plan — Water Sensitive Design Code, which outlines water quality
objectives, needs to be addressed and in particular objective items O1, O7 and O10. Extracts from
these codes follow:


             column 1 Specific Outcomes                                  column 2 Probable solutions
 Maintenance of environmental values                          S1.1 Development meets the applicable
 and water quality objectives                                 performance outcomes of the State Planning
 O1- Downstream ecosystems, properties                        Policy Appendix 2 SPP Code: Water Quality; AND
 and infrastructure are not adversely                         S1.2 Design and construction methods for
 impacted by either changes to flow, water                    stormwater quality treatment assets are in
 quality or ecosystem health caused by                        accordance with Healthy Waterways Water By
 development.                                                 Design Guidelines; AND
                                                              S1.3 Commitments are made to implement a
                                                              cost effective maintenance strategy for the life
                                                              cycle of any engineered water quality treatment
                                                              device; AND
                                                              S1.4 Water quality nutrient load modelling is
                                                              undertaken in accordance with Water by Design
                                                              Music Modelling Guidelines to demonstrate
                                                              compliance with the SPP nutrient reduction
                                                              requirements; AND
                                                              S1.5 Stormwater outlets that directly discharge
                                                              to naturally acidic environments are managed to
                                                              prevent eutrophication; AND
                                                              S1.6 Suitable methods are incorporated to
                                                              prevent the spread of invasive environmental
                                                              weed species at stormwater outlets.



 O7 Natural treatment strategies, including                   S7.1 No probable solution
 grass swales and bio-retention systems,
 vegetated filtration strips and gross pollutant
 traps, are used wherever possible.
 O10 Development design and operation                         S10.1 Methods to prevent gross pollutants
 facilitates nil increase in gross pollutants                 entering stormwater systems and waterways
 entering stormwater systems.                                 are adopted that— a) are low maintenance; b)
                                                              prevent nutrient leaching in the event scheduled
                                                              maintenance is delayed; and c) facilitate human
                                                              behaviour change (e.g. signage, bins)




                                                                                                                 4
17699 - Bounce Hostel, 16 Mary Street Noosaville – Engineering Report – Rev A

Page 6

With respect to Objective O1 the first item of the probable solutions states that development meets the
applicable performance outcomes of the state planning Policy. Given that the performance outcomes
under the SPP are not triggered by extension the remaining objectives within objective O1 should not
apply.

Objective O7 & O10 suggests natural treatment strategies are used wherever possible and that
methods should be implemented to reduce gross pollutants from entering the stormwater system. Given
the flat nature of the site and the road frontage, and the necessity to discharge stormwater to the kerb
and channel as outlined above, there is insufficient fall available to provide on site treatment by the way
of gross pollutant traps or bio-retention systems. In addition, to meet plumbing and building codes, roof
water cannot be discharged to the surface which eliminates the possibility of providing grass swales or
filtration strips. As noted above the existing site contains large areas of unsealed gravel pavement, the
run off from which flows across the site to the street frontage taking with it sediments from the gravel
surface. Roof water from the existing building also discharges onto the gravel surface at the rea of the
building. Photos below show evidence of gravel silt accumulating in the kerb and channel.
Notwithstanding the fact that treatment of stormwater is not triggered by the State Planning Policy, as
the development proposal includes landscaped areas covering in excess of 35% of the site and an
underground car park, which eliminates oils and grease mixing with stormwater, it is expected that the
quality of the run off from the site will improve compared to its current use.




                                                                                                         5
17699 - Bounce Hostel, 16 Mary Street Noosaville – Engineering Report – Rev A

Page 7

5.       Car park and Service Vehicle access

     The ramp to the basement car park is shown on architectural drawing DA.06 by Zest Building Design.
     Tod consulting have checked the longitudinal grades and grade changes and confirm that the ramp
     meets the requirements of AS2890.1.2004 and Council standard drawing IPWEAQ RS-50. The car
     park layout shown on preliminary architectural drawing DA-03 provides car parking spaces that exceed
     the requirements of AS2890.1 for a user class 2 car park.

     Architectural Drawing DA01 by Zest shows the proposed service bay area on the eastern side of the
     site fronting Mary Street. Attached is a swept path diagram showing proposed movements for a service
     vehicle into and out of this space. Ref 17699-SK001. This diagram demonstrates that a service vehicle
     can enter and exit the site in a forward motion.



6.       Existing Sewer

     As noted in the introduction a 450 diameter trunk sewer crosses the site approximately 13m from the
     rear boundary. The sewer is currently 2.5 to 2.8m below existing surface levels but as a result of the
     higher floor levels required (as noted in section 2) the sewer will ultimately be over 3.0m deep.
     Discussions with Unitywater have confirmed that for a 3m deep sewer they require the proposed
     buildings to be set back a minimum of 3m from the centreline of the sewer and founded below the zone
     of influence. Architectural concept drawings have been amended to reflect this requirement. Structural
     drawings will be prepared as part of the detailed design.

7.       Conclusion

     We believe that this report demonstrates that the engineering aspects of the proposed development
     can be successfully and suitably managed, and as such we seek Councils support for the development
     application.


     Prepared by



     Doug Reynolds (RPEQ 9072)
     Tod Consulting Pty Ltd
     28 March 2018




                                                                                                         6
     17699 - Bounce Hostel, 16 Mary Street Noosaville – Engineering Report – Rev A

Page 8

Daily Rainfall (millimetres)
TEWANTIN RSL PARK
Station Number: 040908 · State: QLD · Opened: 1995 · Status: Open · Latitude: 26.39°S · Longitude: 153.04°E · Elevation: 6 m


   Statistics for this station calculated over all years of data
                         Jan       Feb        Mar        Apr       May         Jun        Jul       Aug        Sep        Oct      Nov      Dec
   Mean                  144.2     226.4      221.0      158.0     146.2       123.2        70.2      86.0       57.1     100.4      99.6   139.5
   Median                122.4     162.6      170.6      131.6     126.5       105.1        61.4      31.3       29.2       69.2     85.0   129.6
   Highest daily         181.2     252.0      188.8      161.2     152.0         83.8       94.0    310.2        85.0     232.6    135.0      99.4
   Date of highest        10th       9th       15th       14th      20th          3rd      25th      24th         7th        9th      6th    10th
   daily                  2011      1999       2017       2009      1999        2012       1999      2007       2007       2010     1997     2004




      1) Calculation of statistics
        Summary statistics, other than the Highest and Lowest values, are only calculated
        if there are at least 20 years of data available.

      2) Gaps and missing data
        Gaps may be caused by a damaged instrument, a temporary change to the site operation, or
        due to the absence or illness of an observer.

      3) Further information
        http://www.bom.gov.au/climate/cdo/about/about-rain-data.shtml.




                       Product code: IDCJAC0009 reference: 36343374 Created on Wed 28 Mar 2018 11:36:27 AM EST
                       © Copyright Commonwealth of Australia 2018, Bureau of Meteorology.
                       Prepared using Climate Data Online, Bureau of Meteorology http://www.bom.gov.au/climate/data
                       Contact us using details on http://www.bom.gov.au/climate/how/contacts.shtml.
                       We have taken all due care but cannot provide any warranty nor accept any liability for this information.
                       http://www.bom.gov.au/other/copyright.shtml                                                                    Page 2 of 2

Page 9

                                                                                                                                                                                                                                                     ENS




                                                                                                                                                                                                                                                                                                                                                                                                   COLD ROOM




                                                                                                                                                                                                                                                                                                                                                                                                                                                           DRYING COURT
                                                                                                                                                                                                                                                                                                                                                                                        UP
                                                                                                                                                                                                                                       TV




                                                                                                                                                                                                                                                                UP
                                                                                                                                                                                                                                                     ENS
                                                                                                                                                                                                                                                                                                                                CAFE




                                                                                                                                                                                                                                                                                                                                                                                                   PANTRY
                                                                                                                                                                                                                                                     ENS




                                                                                                                                                                                                                                                                                                                                                                                                               LIFT
                                                                                                                                                                                                                                                                                                                                                                                                                       DRY STORE




                                                                                                                                                                                                                                       TV
                                                                                                                                                                                                                                                                                                                                                                  AMBULANT




                                                                                                                                                                                                                                                                                       Travel Desk
                                                                                                                                                                                                                                                                     UNISEX




                                                                                                                                                                                                                                                                                                                                                                                 UNISEX
                                                                                                                                                                                                                                                                      PWD
                                                                                                                                                                                                                                                                                                                                                                                                  1:14.5          Wheelchair Ramp Access



                                                                                                                                                                                                                              DRAINAGE POINT                         LOCKERS / LUGGAGE




                                                                                                                                                                                                                                                                                                                                                  UP




                                                                                                                                                                                                                                                                                                                                                                                                                                                 SETBACK
                                                                                                                                                                                                                                                                                                                                                                                                                                                 3M SIDE
                                                                                                                                                                                                                         DRIVEWAY CATCHMENT AREA                                                                          RECEPTION




                                                                                                                                                                                   2000mm Accoustic Fence




                                                                                                                                                                                                                                                                                                                                                                     STORE




                                                                                                                                                                                                                                                                                                                                                                                                                          Delivery Bay
                                                                                                                                                                                                            SETBACK
                                                                                                                                                                                                            3M SIDE




                                                                                                                                                                                                                                 Down to basement
                                                                                                                                                                                                                                 carpark




                                                                                                                                                                                                                                                                                                                                                                                                                                                            Bin Enclosure
                                                                                                                                                                                                                                                                                                                                                                                                                                                               Bunded
                                                                                                                                                                                                                                                                                                                                                                             Turn Bay
                                                                                                                                                                                                                      FLOOD BARRIER - REFER TO DETAIL




                                                                                                                                                                                                                                                                                                       PROPOSED CONCRETE FOOTPATH




                                                                                                                                                                                                                                                PROPOSED CONCRETE                                                                                                                                                                                                                 PROPOSED CONCRETE
                                                                                                                                                                                                                                                CROSSOVER TO                                                                                                                                                                                                                      CROSSOVER FOR
                                                                                                                                                                                                                                                BASEMENT CARPARK                                                                                                                                                                                                                  DELIVERY BAY




                                                                                                                                            M A R Y                                                                                                                                                                                                                                                                                                                                                                                       S T R E E T
J:\2017\17699SD1_Subdivision_14-16_Mary_Street_Noosaville\4.CADD\#ACAD\17699_SK001.dwg




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           0    1       2     3      4     5m

                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           1:100 (A1)             1:200 (A3)



                                                                                              COPYRIGHT ©                                                                 Associated Consultants                        Client                                                                                                         Drawn           Verified                         Project                                                                             Drawing Title                                                        Scale                     Sheet Size
                                                                                         This drawing is subject to                                                                                                                                                                                                                    NV              DR
                                                                                         copyright in accordance with the                                                                                              FUQIANG                                                                                                         Designed        Verified
                                                                                                                                                                                                                                                                                                                                                                                        BOUNCE HOSTEL 14-16 MARY ST                                                         SERVICE VEHICLE                                                     AS SHOWN A1
                                                                                         agreement between Tod
                                                                                         Consulting pty ltd (tc) and tc's
                                                                                         client. This drawing shall only be
                                                                                                                                                                                                                       INVESTMENTS PTY LTD                                                                                             NV              DR                               NOOSAVILLE QLD 4566                                                                 TURNING MANOEUVRE                                                    Drawing Number
                                                                                                                                                                                                                                                                                                                                       Approved        RPEQ No
                                                                                         used for this specific project.
                                                                                                                                                                                                                                                                                                                                       D. REYNOLDS     9072                             RDP                                                                                                                                                             17699-SK001
                                                                                         This drawing shall not be used
                                                                                                                                                                                                                                                                                              Noosa: 07 5449 9600                                                                       LOCAL AUTHORITY
                                                                                                                                                                                                                                                                              Sunshine Coast: 07 5329 3190 Mackay: 07 4840 2337
                                                                                                                                                                                                                                                                                                                                       Signed                                           MCU APPROVAL                                     HORIZ DATUM                                        0     10     20    30     40    50       60          Sheet                         Revision
                                                                                         for construction until marked as                                                                                                                                                              PO Box 61, Noosaville, QLD 4566
                                                                                                                               A   28.03.18 ISSUED FOR APPROVAL    NV                                                                                                                                                                                                                   ROL APPROVAL                                     VERT DATUM
                                                                                         'issued for construction' in the
                                                                                         revision description.                Rev Date Revision Description       Drawn
                                                                                                                                                                                                                                                                            [email protected]      www.todconsulting.com
                                                                                                                                                                                                                                                                                              ABN 39 128 805 336
                                                                                                                                                                                                                                                                                                                                                                      28.03.18          OPW APPROVAL                                     RL DATUM                                               MEASUREMENT BAR - INCREMENTS IN mm
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            1 of 1               A