Natural Hazards Overlay Code
____________________________________________________________________________________________________________________
ACCEPTABLE
SOLUTION ALTERNATIVE SOLUTIONS / COUNCIL USE
SPECIFIC OUTCOMES PROBABLE SOLUTIONS
COMPLIANCE COMMENTS ONLY
(/)
AEP 1:100 year ARI) flood event. contamination are—
a) located above the level of a 1% AEP
(1:100 ARI) flood event; or
b) are designed and constructed to
exclude water inundation or
infiltration and resist hydrostatic and
hydrodynamic forces as a result of
inundation.
O18 S18.1
Community Uses and Infrastructure Community Uses and Infrastructure N/A Community Uses and Infrastructure
Uses are able to function effectively during Uses are sited and constructed to ensure Uses are not proposed.
and immediately after flood events. that floor levels are not less than the AEP
(or ARI) levels identified below—
a) Emergency service facilities- 0.2%
AEP (1:500 ARI);
b) Emergency shelter- 0.5% AEP (1:200
ARI);
c) Police station- 0.5% AEP (1:200
ARI);
d) Hospital- 0.2% AEP (1:500 ARI);
e) Electricity substation- 0.2% AEP
(1:500 ARI);
f) Water treatment plant- 0.2% AEP
(1:500 ARI);
g) Power station- 0.5% AEP (1:200
ARI);
Noosa Plan - Code Compliance