Council archive · source document
REFERENCE DOCUMENTS - RAL25/0004 (As Published)
Very large file (40.5 MB): the whole original can take several minutes to open, especially on a phone. Text is quick to read.
Original PDF page 939, section 1. The text section number identifies this passage in the reader.
Page : 2 of 11
Work Order : EB2409053
Client : ENVIRONMENTAL ADVISORS
Project : 125 NSC LAKE McDONALD DVE, COOROY
General Comments
The analytical procedures used by ALS have been developed from established internationally recognised procedures such as those published by the USEPA, APHA, AS and NEPM. In house developed procedures
are fully validated and are often at the client request.
Where moisture determination has been performed, results are reported on a dry weight basis.
Where a reported less than (<) result is higher than the LOR, this may be due to primary sample extract /digestate dilution and/or insufficient sample for analysis. Where the LOR of a reported result differs from
standard LOR, this may be due to high moisture content, insufficient sample (reduced weight employed) or matrix interference.
Key : Anonymous = Refers to samples which are not specifically part of this work order but formed part of the QC process lot
CAS Number = CAS registry number from database maintained by Chemical Abstracts Services. The Chemical Abstracts Service is a division of the American Chemical Society.
LOR = Limit of reporting
RPD = Relative Percentage Difference
# = Indicates failed QC
* = The final LOR has been raised due to dilution or other sample specific cause; adjusted LOR is shown in brackets. The duplicate ranges for Acceptable RPD% are applied to the final LOR where
applicable.
Laboratory Duplicate (DUP) Report
The quality control term Laboratory Duplicate refers to a randomly selected intralaboratory split. Laboratory duplicates provide information regarding method precision and sample heterogeneity. The permitted ranges
for the Relative Percent Deviation (RPD) of Laboratory Duplicates are specified in ALS Method QWI -EN/38 and are dependent on the magnitude of results in comparison to the level of reporting: Result < 10 times LOR:
No Limit; Result between 10 and 20 times LOR: 0% - 50%; Result > 20 times LOR: 0% - 20%.
Sub-Matrix: WATER Laboratory Duplicate (DUP) Report
Laboratory sample ID Sample ID Method: Compound CAS Number LOR Unit Original Result Duplicate Result RPD (%) Acceptable RPD (%)
EA015: Total Dissolved Solids dried at 180 ± 5 °C (QC Lot: 5677448)
EB2409004-001 Anonymous EA015H: Total Dissolved Solids @180°C ---- 10 mg/L 1870 1870 0.3 0% - 20%
EB2409118-001 Anonymous EA015H: Total Dissolved Solids @180°C ---- 10 mg/L 351 348 0.8 0% - 20%
EG035F: Dissolved Mercury by FIMS (QC Lot: 5673708)
EB2409053-001 MB1-1 EG035F-LL: Mercury 7439-97-6 0.00004 mg/L <0.00004 <0.00004 0.0 No Limit
EG094F: Dissolved Metals in Fresh Water by ORC-ICPMS (QC Lot: 5671709)
EB2409053-001 MB1-1 EG094A-F: Cadmium 7440-43-9 0.05 µg/L <0.05 <0.05 0.0 No Limit
EG094A-F: Lead 7439-92-1 0.1 µg/L 0.1 0.1 0.0 No Limit
EG094A-F: Arsenic 7440-38-2 0.2 µg/L <0.2 <0.2 0.0 No Limit
EG094A-F: Chromium 7440-47-3 0.2 µg/L <0.2 <0.2 0.0 No Limit
EG094A-F: Copper 7440-50-8 0.5 µg/L 4.3 4.3 0.0 No Limit
EG094A-F: Nickel 7440-02-0 0.5 µg/L 2.6 2.5 0.0 No Limit
EG094A-F: Zinc 7440-66-6 1 µg/L 13 13 0.0 0% - 50%
EP080/071: Total Petroleum Hydrocarbons (QC Lot: 5673899)
EB2409053-001 MB1-1 EP080: C6 - C9 Fraction ---- 20 µg/L <20 <20 0.0 No Limit
EB2409055-006 Anonymous EP080: C6 - C9 Fraction ---- 20 µg/L <20 <20 0.0 No Limit
EP080/071: Total Recoverable Hydrocarbons - NEPM 2013 Fractions (QC Lot: 5673899)
EB2409053-001 MB1-1 EP080: C6 - C10 Fraction C6_C10 20 µg/L <20 <20 0.0 No Limit
EB2409055-006 Anonymous EP080: C6 - C10 Fraction C6_C10 20 µg/L <20 <20 0.0 No Limit
EP080: BTEXN (QC Lot: 5673899)
EB2409053-001 MB1-1 EP080: Benzene 71-43-2 1 µg/L <1 <1 0.0 No Limit
Document Set ID: 23717062
Version: 0, Version Date: 01/01/1900
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
REFERENCE DOCUMENTS - RAL25/0004 (As Published)Related documentApplication case desk ↗
About this file
- File size
- 40.5 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.