Reticulation 25-0048_Hoy Road_EGX_rA010725
SITE LOCALITY
(SCALE: N.T.S.)
E
E
E
ELECTRICAL CERTIFICATION
THIS IS TO CERTIFY THAT THE DESIGN OF ENERGEX RETICULATION IS IN
ACCORDANCE WITH ENERGEX DESIGN MANUALS AND WORK CATEGORY
SPECIFICATION 47.1 & 47.3 WHERE APPLICABLE.
KRIS BOVEINIS (RPEQ 22272)
DATE
2/07/2025
!WARNING!
BUSHFIRE PRONE AREA
BUSHFIRE MESH MAY BE REQUIRED ON
OH POLES. REFER EQL STD A4748A
ISSUE FOR ENERGEX &
COUNCIL ACCEPTANCE ONLY
NOT FOR CONSTRUCTION
This drawing is to be considered preliminary until this
disclaimer is removed by Peter Eustace Pty. Ltd.
DATE 01.07.25 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PECE WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS PECE
CONSULTING NAME Energex OH REFER OHDM PARENT PROJECT NO. SCALE: 1:1000@A1
ISSUED FOR ENERGEX &
Energex UG
COUNCIL ACCEPTANCE
TBC REFER UDC WORK REQUEST NO. PROJECT / SUB PROJECT NO.
CHECKED KRIS BOVEINIS
ENGINEERS COMPANY NBN REFER NBN LOTS 1-9 INSTALL POLES, OVERHEAD LV & HV CONDUCTOR & POLE TRANSFORMER
ONLY. NOT FOR
CONSTRUCTION.
- GAS REFER GAS DESIGNER RILEY PORTER
R DESCRIPTION
STREET ADDRESS U14, 39 Lawrence Dr, Nerang QLD 4211
PHONE - HP GAS REFER GAS CANCELLING LOTS LOT 3 ON RP171041 PHONE (07) 5596 1425
9 LOT RURAL RESIDENTIAL SUBDIVISION
S1302446
POSTAL ADDRESS PO Box 2835, Nerang DC QLD 4211 MOBILE - WATER REFER CIVIL PLANNER LUKE ARACE
TELEPHONE (07) 5596 1425 FAX - STORMWATER REFER CIVIL LOCAL AUTHORITY NOOSA SHIRE COUNCIL PHONE (07) 5596 1425 44 HOY RD, LAKE MACDONALD
EMAIL [email protected]
WEB pece.com.au SEWERAGE REFER CIVIL UBD REF QLD, 4563 Sheet 1 of 7
24-0048- EGX- 01 OTHER REFER CIVIL PEGGED?
ISSUE DATE 01 JULY 2025
ISSUE NO: A
A
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 6 pages
Page 2
OVERHEAD WORKS SCHEDULE 1
POLES CONSTRUCTIONS (Note: KBS is top KB to top KB)
STN SITE I.D
LOCATION EDT EDT SST LST REMARKS
No. (POLE No) EXISTING RECOVER ERECT SINK FOOT COMP ID ALIGN LCC EXISTING RECOVER ERECT No KBS ANG LCC
ANG kN Kn Kn
HOY ROAD 1 X807835 165° 1.02 2.94 5.82 P12.5 P12.5 EX EX EX EX 11SC/HVTMO 11SC/HVTMO 1 EX
11LBSMPFFIS 11LBSMPFFIS 1 EX
HVE HVE 1
49° 0.45 1.92 3.75 P12.5/8-14 2 MDCF P1 SEE REMARKS 11TC/S 1 150 INSTALL POLE WITHIN 1m OF EXISTING LOCATION
HVTMO 3 UNDER EXISTING LINES
11TC/SCCT 1 850
SC0012768 3
SC0005996 3
SC0009924 3
11LBSMPFFIS 1 600
HVE 1
SC00601-1 1
2 P12740800 42° 4.19 6.48 13.06 P12.5/12-22 2 MDCF P1 6.0 EMT 11TC/SCCT 1 150
SC0012768 3
SC0005996 3
SC0009924 3
11TC/SCCT 1 850
SC0012768 3
SC0005996 3
SC0009924 3
SC00601-1 1
3 P12740801 159° 2.91 6.29 12.93 P15.5/12-22 2.4 MDCF P1 3.0 RP BDY 11TD/NCCT 1 150
SC0005990 3
SC0009924 3
11TC/SCCT 1 650
SC0012768 3
SC0005996 3
SC0009924 3
SC00601-1 1
4 P12740802 350° 0.01 1.35 2.43 P14/8-14 2 MDCF P1 6.0 EMT 11TD/NCCT 1 150
SC0005990 3
SC0009924 3
SC00601-1 1
5 P12740803 241° 1.11 2.94 6.11 P12.5/8-14 2 MDCF P1 6.0 EMT 11TDA/NCCT 1 150
SC0005990 3
SC0009924 3
SC00601-1 1
6 P12740804 293° 0.93 2.65 5.33 P12.5/8-14 2 MDCF P1 6.0 EMT 11TDA/NCCT 1 150
SC0005990 3
SC0009924 3
SC00601-1 1
7 P12740805 360° 0 1.1 1.98 P12.5/8-14 2 MDCF P1 6.0 EMT 11TD/NCCT 1 150
SC0005990 3
SC0009924 3
SC00601-1 1
8 SP12740806 246° 2.34 4.46 8.95 P14/12-22 2.4 MDCF P1 6.0 EMT 11TC/SCCT 1 150
SC0012768 3
SC0005996 3
SC0009924 3
11TC/SCCT 1 150
SC0012768 3
SC0005996 3
SC0009924 3
PAGE7-53-3 1
11EDO3 3 1000
S22442 1 2150
SC0014228 3
SC4451 1
SC19910 1
S1B/W 1
PTSMNW 1
PTSEP 1
SGECROD 1
SC00601-1 1
9 P12740807 26° 2.33 4.33 8.52 P12.5/12-22 2.2 MDCF P1 6.0 EMT 11TC/S 1 150
HVTRA 3
11TC/SCCT 1 850
SC0012768 3
SC0005996 3
SC0009924 3
SC00601-1 1
10 SP16941-A 280° 4.34 7.93 13.94 P14/12-22 EX EX EX EX 11SC/HVTRA 1 EX
60° 0.81 1.71 3.26 11EDO3 1 EX
11PT/25B 1 EX
STAY 1 EX
LVABC/T 1 EX
PTSEP 1 EX
SGECROD 1 EX
OVERHEAD CONDUCTOR SCHEDULE
SAG (m) CONDUCTOR LENGTH (m) PROPOSED LV GEOGRAPHIC - SP12740587 & SP12740806
STATIONS No. OF SAG SPAN
LOCATION VOLTS EXISTING TRANSFER RECOVER ERECT DIST (m) STRING M.E.S LCC REMARKS
FROM-TO SPANS TABLE FROM - TO
15° 30° NEW REC
HOY ROAD 1 - 2 11kV 3-11CCT1350 1 45 660 45 1-2 1.3 1.4 135
1 - 23 11kV 3-7/4.75 3-7/4.75 4 455 EX EX EX EX EX 455
2 - 8 11kV 3-11CCT1350 6 325 440 62 3-4 2.8 3 975
8 - 9 11kV 3-11CCT1350 1 34 660 34 8-9 0.8 0.9 105
9 - 10 11kV 2-3/4/2.50 2-3/4/2.50 2-3/4/2.50 1 62 660 62 9 - 10 2.5 2.6 70
9 - 21 11kV 2-3/4/2.50 2-3/4/2.50 1 352 EX EX EX EX EX 582
MEADOW LANE 3 - 13 11kV 3-11CCT1350 3 250 440 84.91 3 - 11 4 4.1 750
13 - 17 11kV 3-11CCT1350 4 221 440 57.45 13 - 14 2.2 2.4 665
17 - 18 11kV 3-11CCT1350 1 56 660 56 17 - 18 2.1 2.2 170
18 - 19 11kV 3-7/4.75 3-7/4.75 3-7/4.75 1 48 220 48 18 - 19 1 1.1 145
19 23 11kV 3-7/4.75 3-7/4.75 1 114 EX EX EX EX EX 342
11 - 13 LV 1-ABCLV95 2 155 440 78.08 11 - 12 3 3.2 160
13 - 15 LV 1-ABCLV95 2 130 440 62.45 13 - 14 2.2 2.4 135
PROPOSED SP12740587 PROPOSED SP12740806
PHASING BALANCE PHASING BALANCE
A B C A B C
CCT 3 3 2 CCT 1 0 0
ISSUE FOR ENERGEX &
COUNCIL ACCEPTANCE ONLY
NOT FOR CONSTRUCTION
This drawing is to be considered preliminary until this
disclaimer is removed by Peter Eustace Pty. Ltd.
DATE 01.07.25 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PECE WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS PECE
CONSULTING NAME Energex OH REFER OHDM PARENT PROJECT NO. SCALE: N.T.S.
ISSUED FOR ENERGEX &
Energex UG
COUNCIL ACCEPTANCE
TBC REFER UDC WORK REQUEST NO. PROJECT / SUB PROJECT NO.
CHECKED KRIS BOVEINIS
ENGINEERS COMPANY NBN REFER NBN LOTS 1-9 INSTALL POLES, OVERHEAD LV & HV CONDUCTOR & POLE TRANSFORMER
ONLY. NOT FOR
CONSTRUCTION.
- GAS REFER GAS DESIGNER RILEY PORTER
R DESCRIPTION
STREET ADDRESS U14, 39 Lawrence Dr, Nerang QLD 4211
PHONE - HP GAS REFER GAS CANCELLING LOTS LOT 3 ON RP171041 PHONE (07) 5596 1425
9 LOT RURAL RESIDENTIAL SUBDIVISION
S1302446
POSTAL ADDRESS PO Box 2835, Nerang DC QLD 4211 MOBILE - WATER REFER CIVIL PLANNER LUKE ARACE
TELEPHONE (07) 5596 1425 FAX - STORMWATER REFER CIVIL LOCAL AUTHORITY NOOSA SHIRE COUNCIL PHONE (07) 5596 1425 44 HOY RD, LAKE MACDONALD
EMAIL [email protected]
WEB pece.com.au SEWERAGE REFER CIVIL UBD REF QLD, 4563 Sheet 2 of 7
24-0048- EGX- 02 OTHER REFER CIVIL PEGGED?
ISSUE DATE 01 JULY 2025
ISSUE NO: A
A
Page 3
OVERHEAD WORKS SCHEDULE 2
POLES CONSTRUCTIONS (Note: KBS is top KB to top KB)
STN SITE I.D
LOCATION EDT EDT SST LST REMARKS
No. (POLE No) EXISTING RECOVER ERECT SINK FOOT COMP ID ALIGN LCC EXISTING RECOVER ERECT No KBS ANG LCC
ANG kN Kn Kn
MEADOW LANE 11 P12740585 174° 3.58 6.8 13.09 P15.5/12-22 2.4 MDCF P1 3.0 RP BDY 11TDA/NCCT 1 150
SC0005990 3
SC0009924 3
LVABC/T 1 1800
S1B/W 1
SGECROD 1
SC00601-1 1
12 P12740586 267° 2.25 6.81 13.04 P14/12-22 2.2 MDCF P1 3.0 RP BDY 11TDA/NCCT 1 150
SC0005990 3
SC0009924 3
LVABC/SU3 1 1600
S1B/W 1
SC00601-1 1
13 SP12740587 277° 0.07 2.58 4.71 P15.5/12-22 2.6 MDCF P1 3.0 RP BDY 11SC/SCCT 1 150
SC0012768 3
SC0005996 3
SC0009924 3
PAGE7-53-3 1
11EDO3 1 1000
S21650 1 2150
SC0014228 3
SC4458 1
SC2622 1
LVABC/S 1 1000
S1B/W 1
PTSMNW 1
PTSEP 1
SGECROD 1
SC00601-1 1
14 P12740588 360° 0 2.29 4.13 P15.5/8-14 2.15 MDCF P1 3.0 RP BDY 11TD/NCCT 1 150
SC0005990 3
SC0009924 3
LVABC/S 1 1600
S1B/W 2
SC00601-1 1
15 P12740589 355° 3.65 6.87 13.3 P14/12-22 2.2 MDCF P1 3.0 RP BDY 11TDA/NCCT 1 150
SC0005990 3
SC0009924 3
LVABC/T 1 1800
S1B/W 3
SGECROD 1
SC00601-1 1
16 P12740799 295° 0.33 1.73 3.26 P12.5/8-14 2 MDCF P1 6.0 EMT 11TDA/NCCT 1 150
SC0005990 3
3-120CCT HV VEGETATION CLEARING PROFILE DETAIL 'A'
SC0009924 3
SC00601-1 1
17 P12740590 61° 3.82 6.9 13.37 P12.5/12-22 2.2 MDCF P1 6.0 EMT 11TC/SCCT 1 150
SC0012768 3
SC0005996 3
SC0009924 3
11TC/SCCT 1 850
SC0012768 3
SC0005996 3
SC0009924 3
SC00601-1 1
18 P12740591 306° 2.31 5.41 10.89 P12.5/12-22 2.2 MDCF P1 6.0 EMT 11TC/SCCT 1 150
SC0012768 3
SC0005996 3
SC0009924 3
11TC/S 1 850
HVTMO 3
SC00601-1 1
19 SP79-D 23° 2.27 5.27 10.51 P14/20-36 EX EX EX EX 11SC/HVTMO 1 EX
23° 2.27 4.98 10.19 11T/HVTMA 1 EX
11PT/63 1 EX
S1B/W 2 EX
LVT120 1 EX
PTSEP 1 EX
SGECROD 1 EX
20 P12316-A EX EX EX EX P12.5/8-14 P12.5/8-14 EX EX EX EX 11P/MO 11P/MO 1 EX
21 P12315-A EX EX EX EX 45 FT LG MED 45 FT LG MED EX EX EX EX 11SC/HVTMO 11SC/HVTMO 1 EX
11TC/HVTRA 11TC/HVTRA 1 EX
STAY STAY 1 EX
22 P12314-A EX EX EX EX 40 FT LG MED 40 FT LG MED EX EX EX EX 11P/MO 11P/MO 1 EX
23 P12313-B EX EX EX EX 35 FT LG MED 35 FT LG MED EX EX EX EX 11P/MO 11P/MO 1 EX
1-95ABC LV OVERHEAD CLEARANCE PROFILE DETAIL 'B'
ISSUE FOR ENERGEX &
COUNCIL ACCEPTANCE ONLY
NOT FOR CONSTRUCTION
This drawing is to be considered preliminary until this
disclaimer is removed by Peter Eustace Pty. Ltd.
DATE 01.07.25 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PECE WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS PECE
CONSULTING NAME Energex OH REFER OHDM PARENT PROJECT NO. SCALE: N.T.S.
ISSUED FOR ENERGEX &
Energex UG
COUNCIL ACCEPTANCE
TBC REFER UDC WORK REQUEST NO. PROJECT / SUB PROJECT NO.
CHECKED KRIS BOVEINIS
ENGINEERS COMPANY NBN REFER NBN LOTS 1-9 INSTALL POLES, OVERHEAD LV & HV CONDUCTOR & POLE TRANSFORMER
ONLY. NOT FOR
CONSTRUCTION.
- GAS REFER GAS DESIGNER RILEY PORTER
R DESCRIPTION
STREET ADDRESS U14, 39 Lawrence Dr, Nerang QLD 4211
PHONE - HP GAS REFER GAS CANCELLING LOTS LOT 3 ON RP171041 PHONE (07) 5596 1425
9 LOT RURAL RESIDENTIAL SUBDIVISION
S1302446
POSTAL ADDRESS PO Box 2835, Nerang DC QLD 4211 MOBILE - WATER REFER CIVIL PLANNER LUKE ARACE
TELEPHONE (07) 5596 1425 FAX - STORMWATER REFER CIVIL LOCAL AUTHORITY NOOSA SHIRE COUNCIL PHONE (07) 5596 1425 44 HOY RD, LAKE MACDONALD
EMAIL [email protected]
WEB pece.com.au SEWERAGE REFER CIVIL UBD REF QLD, 4563 Sheet 3 of 7
24-0048- EGX- 03 OTHER REFER CIVIL PEGGED?
ISSUE DATE 01 JULY 2025
ISSUE NO: A
A
Page 4
PROPOSED EASEMENT DETAIL
EXISTING HV GEOGRAPHIC
PROPOSED HVGEOGRAPHIC
PROPOSED COMMISSIONING SCHEDULE
TENTATIVE ONLY SUBJECT TO AMENDMENT BY SWITCHING CO-ORDINATOR
ITEM No LOCATION APPARATUS ACTION
COMMISSION NEW PT - LV AND HV SWITCHING
1 ADVISE CONTRACT SUPERVISOR SWITCHING TO COMMENCE
2 RECEIVE CLEARANCE FROM WORK CREWS ALL WORK COMPLETED
3 NOTIFY ALL WORK CREWS TREAT PILLARS AS LIVE
4 *CRITICAL LOAD - 1RP105072* PINE TREE DR WEST SP44-B GENSET INSTALL
5 LAKE MACODNALD DR SP2538-E GENSET INSTALL
6 PINE TREE DR SP5430-B GENSET INSTALL
7 OLD TEWANTIN RD X24306-B [BACKFEED CRY2A] ABS CLOSE
8 LAKE MACDONALD DR X48335-A ABS OPEN
9 PINE TREE DR X90683-A ABS OPEN
10 MEADOW LN & HOY RD NEW EQUIPMENT CONNECT & MAKE READY
11 REVERSE REVERSE
12 MEADOW LN SP12740587 COMMISSION
13 HOY RD SP12740596 COMMISSION
14 MEADOW LN & HOY RD NEW LV EQUIPMENT COMMISSION & TEST
15 ADVISE CONTRACT SUPERVISOR SWITCHING COMPLETE
ISSUE FOR ENERGEX &
COUNCIL ACCEPTANCE ONLY
NOT FOR CONSTRUCTION
This drawing is to be considered preliminary until this
disclaimer is removed by Peter Eustace Pty. Ltd.
DATE 01.07.25 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PECE WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS PECE
CONSULTING NAME Energex OH REFER OHDM PARENT PROJECT NO. SCALE: N.T.S.
ISSUED FOR ENERGEX &
Energex UG
COUNCIL ACCEPTANCE
TBC REFER UDC WORK REQUEST NO. PROJECT / SUB PROJECT NO.
CHECKED KRIS BOVEINIS
ENGINEERS COMPANY NBN REFER NBN LOTS 1-9 INSTALL POLES, OVERHEAD LV & HV CONDUCTOR & POLE TRANSFORMER
ONLY. NOT FOR
CONSTRUCTION.
- GAS REFER GAS DESIGNER RILEY PORTER
R DESCRIPTION
STREET ADDRESS U14, 39 Lawrence Dr, Nerang QLD 4211
PHONE - HP GAS REFER GAS CANCELLING LOTS LOT 3 ON RP171041 PHONE (07) 5596 1425
9 LOT RURAL RESIDENTIAL SUBDIVISION
S1302446
POSTAL ADDRESS PO Box 2835, Nerang DC QLD 4211 MOBILE - WATER REFER CIVIL PLANNER LUKE ARACE
TELEPHONE (07) 5596 1425 FAX - STORMWATER REFER CIVIL LOCAL AUTHORITY NOOSA SHIRE COUNCIL PHONE (07) 5596 1425 44 HOY RD, LAKE MACDONALD
EMAIL [email protected]
WEB pece.com.au SEWERAGE REFER CIVIL UBD REF QLD, 4563 Sheet 4 of 7
24-0048- EGX- 04 OTHER REFER CIVIL PEGGED?
ISSUE DATE 01 JULY 2025
ISSUE NO: A
A
Page 5
PROPOSED OVERHEAD PROFILE HOY ROAD STN 1 - 5
PROPOSED OVERHEAD PROFILE HOY ROAD STN 5 - 10
ISSUE FOR ENERGEX &
COUNCIL ACCEPTANCE ONLY
NOT FOR CONSTRUCTION
This drawing is to be considered preliminary until this
disclaimer is removed by Peter Eustace Pty. Ltd.
DATE 01.07.25 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PECE WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS PECE
CONSULTING NAME Energex OH REFER OHDM PARENT PROJECT NO. SCALE: N.T.S.
ISSUED FOR ENERGEX &
Energex UG
COUNCIL ACCEPTANCE
TBC REFER UDC WORK REQUEST NO. PROJECT / SUB PROJECT NO.
CHECKED KRIS BOVEINIS
ENGINEERS COMPANY NBN REFER NBN LOTS 1-9 INSTALL POLES, OVERHEAD LV & HV CONDUCTOR & POLE TRANSFORMER
ONLY. NOT FOR
CONSTRUCTION.
- GAS REFER GAS DESIGNER RILEY PORTER
R DESCRIPTION
STREET ADDRESS U14, 39 Lawrence Dr, Nerang QLD 4211
PHONE - HP GAS REFER GAS CANCELLING LOTS LOT 3 ON RP171041 PHONE (07) 5596 1425
9 LOT RURAL RESIDENTIAL SUBDIVISION
S1302446
POSTAL ADDRESS PO Box 2835, Nerang DC QLD 4211 MOBILE - WATER REFER CIVIL PLANNER LUKE ARACE
TELEPHONE (07) 5596 1425 FAX - STORMWATER REFER CIVIL LOCAL AUTHORITY NOOSA SHIRE COUNCIL PHONE (07) 5596 1425 44 HOY RD, LAKE MACDONALD
EMAIL [email protected]
WEB pece.com.au SEWERAGE REFER CIVIL UBD REF QLD, 4563 Sheet 5 of 7
24-0048- EGX- 05 OTHER REFER CIVIL PEGGED?
ISSUE DATE 01 JULY 2025
ISSUE NO: A
A
Page 6
PROPOSED OVERHEAD PROFILE MEADOW LANE 3 - 13
PROPOSED OVERHEAD PROFILE MEADOW LANE 13 - 19
ISSUE FOR ENERGEX &
COUNCIL ACCEPTANCE ONLY
NOT FOR CONSTRUCTION
This drawing is to be considered preliminary until this
disclaimer is removed by Peter Eustace Pty. Ltd.
DATE 01.07.25 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PECE WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS PECE
CONSULTING NAME Energex OH REFER OHDM PARENT PROJECT NO. SCALE: N.T.S.
ISSUED FOR ENERGEX &
Energex UG
COUNCIL ACCEPTANCE
TBC REFER UDC WORK REQUEST NO. PROJECT / SUB PROJECT NO.
CHECKED KRIS BOVEINIS
ENGINEERS COMPANY NBN REFER NBN LOTS 1-9 INSTALL POLES, OVERHEAD LV & HV CONDUCTOR & POLE TRANSFORMER
ONLY. NOT FOR
CONSTRUCTION.
- GAS REFER GAS DESIGNER RILEY PORTER
R DESCRIPTION
STREET ADDRESS U14, 39 Lawrence Dr, Nerang QLD 4211
PHONE - HP GAS REFER GAS CANCELLING LOTS LOT 3 ON RP171041 PHONE (07) 5596 1425
9 LOT RURAL RESIDENTIAL SUBDIVISION
S1302446
POSTAL ADDRESS PO Box 2835, Nerang DC QLD 4211 MOBILE - WATER REFER CIVIL PLANNER LUKE ARACE
TELEPHONE (07) 5596 1425 FAX - STORMWATER REFER CIVIL LOCAL AUTHORITY NOOSA SHIRE COUNCIL PHONE (07) 5596 1425 44 HOY RD, LAKE MACDONALD
EMAIL [email protected]
WEB pece.com.au SEWERAGE REFER CIVIL UBD REF QLD, 4563 Sheet 6 of 7
24-0048- EGX- 06 OTHER REFER CIVIL PEGGED?
ISSUE DATE 01 JULY 2025
ISSUE NO: A
A
Page 7
PROPOSED POLETOP CONSTRUCTIONS DIAGRAM HOY ROAD 2 - 9
PROPOSED POLETOP CONSTRUCTIONS DIAGRAM MEADOW LANE 11 - 18
ISSUE FOR ENERGEX &
COUNCIL ACCEPTANCE ONLY
NOT FOR CONSTRUCTION
This drawing is to be considered preliminary until this
disclaimer is removed by Peter Eustace Pty. Ltd.
DATE 01.07.25 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PECE WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS PECE
CONSULTING NAME Energex OH REFER OHDM PARENT PROJECT NO. SCALE: N.T.S.
ISSUED FOR ENERGEX &
Energex UG
COUNCIL ACCEPTANCE
TBC REFER UDC WORK REQUEST NO. PROJECT / SUB PROJECT NO.
CHECKED KRIS BOVEINIS
ENGINEERS COMPANY NBN REFER NBN LOTS 1-9 INSTALL POLES, OVERHEAD LV & HV CONDUCTOR & POLE TRANSFORMER
ONLY. NOT FOR
CONSTRUCTION.
- GAS REFER GAS DESIGNER RILEY PORTER
R DESCRIPTION
STREET ADDRESS U14, 39 Lawrence Dr, Nerang QLD 4211
PHONE - HP GAS REFER GAS CANCELLING LOTS LOT 3 ON RP171041 PHONE (07) 5596 1425
9 LOT RURAL RESIDENTIAL SUBDIVISION
S1302446
POSTAL ADDRESS PO Box 2835, Nerang DC QLD 4211 MOBILE - WATER REFER CIVIL PLANNER LUKE ARACE
TELEPHONE (07) 5596 1425 FAX - STORMWATER REFER CIVIL LOCAL AUTHORITY NOOSA SHIRE COUNCIL PHONE (07) 5596 1425 44 HOY RD, LAKE MACDONALD
EMAIL [email protected]
WEB pece.com.au SEWERAGE REFER CIVIL UBD REF QLD, 4563 Sheet 7 of 7
24-0048- EGX- 07 OTHER REFER CIVIL PEGGED?
ISSUE DATE 01 JULY 2025
ISSUE NO: A
A