Attachment 4 - Site Investigation and Slab Report
barrier systems within the masonry walling or requiring minor repair work such as repointing.
cavity. For situations where the damp-proof course Note that these fine cracks usually occur in the
is more than say 400 mm above the footing or the mortar joints where they often go unnoticed.
risk of cracking in this area must be minimised, it Damage in categories 3 and 4 will generally
is recommended that the articulation joint should require more substantial repairs.
extend down to the footing and allowance be made Thus while articulation allows a more flexible
for movement in any built-in components such as and therefore economical footing system for a
termite barriers. particular walling type and soil reactivity, the
Ideally, the wall layout for the building should expected performance levels of the standard
follow a basically straight grid pattern so the designs having articulated walling follows the same
beams of a raft slab can follow the wall pattern philosophy outlined above regarding acceptable
economically and simplify the division of the wall crack widths, ie the majority of articulated walls
into independent panels by articulation joints. on footing systems complying with AS 2870 will
The roof construction (framed, trussed or perform satisfactorily, some will display fine cracks
beam‑and-rafter) should include adequate bracing and a few will have noticeable cracking.
to prevent spreading of the roof framing and hence Articulation may therefore be used in two ways
the tops of walls being pushed out which could for any given walling type: it may be used to reduce
cause cracking of internal walls that are located the required footing size, or, by maintaining the
adjacent to the eaves. footing size required for the non-articulated case,
to further reduce the risk of walls cracking and
4 FOOTINGS FOR ARTICULATED WALLS windows and doors jamming. The latter approach is
One of the benefits of articulated walling is the recommended for walls containing arches, and for
reduction in the size and ultimate cost of footings buildings with rendered or painted finishes where
required for a building with masonry walls on any cracking that may occur is more noticeable.
reactive soils. Because an articulated structure has If one of the standard footing designs in AS 2870
sufficient flexibility to move in harmony with the (which ensure compatibility between footing design
footings without developing unacceptable cracks, and tolerable movement for the type of walling
the footing can be designed to be less rigid than system) is not used, the designer should consider
would be required for a non-articulated masonry the following points when determining the allowable
superstructure. deflection of the footings:
Regarding the ‘acceptability’ of cracking, ■ Materials and construction of internal and
AS 2870 includes guidance on this by classifying the external walls
damage that may occur to walls. Adoption of the ■ Surface finish of internal and external walls
deemed-to-comply or standard footing designs in ■ The number of articulation joints and their
AS 2870 should ensure that the majority of damage location
to walls falls into damage category 0 (either no ■ Length and plan arrangement of walls
cracking or hairline cracks less than about 0.1 mm ■ The inclusion of damage-prone elements such
in width), some may fall into category 1 (fine cracks as masonry arches.
less than about 1 mm in width which do not need
repair) and a few may fall into category 2 (noticeable Suggested maximum limits for the deflection
cracks less than about 5 mm in width that can be for the design of footings and rafts for various types
easily filled). Damage categories 3 and 4 include of construction given in AS 2870 are reproduced in
cracking from 5 mm to 15 mm and 15 to 25 mm Table 1. The limit adopted for a particular design
respectively with doors and windows jamming and, will depend on the form of construction and take
in the worst cases, possibly distorting. Damage account of factors such as the distance between
within these categories seldom occurs, and when articulation joints, number of storeys, first-floor
it does, is usually the result of some specific site construction materials, wall surface finish, and
problem. The range of categories acknowledges whether or not the masonry is reinforced. The
that standard footing designs on typical sites of a design limit for deflection should be nominated
particular soil classification (Class A, S, M and H) by an experienced engineer. Note that for
will generally perform satisfactorily, but that soil non‑articulated, full-masonry construction, a
conditions are variable. Thus, in some instances the deflection of the footing of around 5 mm over a
soil and therefore footing movements will be greater. 10-m span may cause cracking.
The Guide to Standards and Tolerances4 Should more than one form of construction be
produced by various State Government Authorities, used in a building, it is possible to design footings
refers to a category 2 crack as being a defect with different limits of deflection in separate parts
Page 4 Articulated Walling