Attachment 4 - Site Investigation and Slab Report
If length greater than
spacing in Table 2,
provide articulation joints
Open articulation Sealed articulation
joint between masonry joint between single-
fence and house and two-storey wall
Figure 5 Articulation joints at changes of wall height
For footings designed by an engineer, the the opening thereby reducing the loads that the
maximum spacing of joints will depend on the lintel must support. If the articulation joint is in
maximum deflection adopted in the design. If the line with the edge of the opening (Figure 8 (b)
joint spacing exceeds four times the average wall and Figure12), lintel sizes selected from
height or 12 m, the walls should be considered standard design tables should be checked for
as non-articulated and the maximum deflection adequacy as masonry can no longer be assumed
for this case should be selected on the basis of to arch over the opening.
non‑articulated masonry construction5. Also, ■ Changes in wall thickness Figure 14. Note that
‘sections of walls without openings may be engaged piers are not considered to be a change
considered as fully articulated if the distance in thickness.
between joints is not more than twice the average ■ Junctions of walls built of different masonry
height, nor 6 m.’ This is in agreement with the materials (clay, concrete, calcium silicate or
maximum 6-m spacing adopted in Table 2. stone) Figure 14;
For Class E (extremely reactive) sites, the ■ Joints between masonry walls and structural
footings should be designed in accordance with reinforced concrete or steel elements;
engineering principles, with the joint spacing ■ Deep chases or rebates for service pipes
depending on the maximum deflection adopted. Figure 15. Note that chases deeper than 25%
Note that deemed-to-comply or standard footing of the leaf thickness should be regarded as a
designs are not provided for Class E sites in AS 2870. change in thickness.
■ At offsets in walls. Note that the internal corner
6 LOCATION OF ARTICULATION JOINTS is an inconspicuous location for a joint Figure 16.
In addition to locations determined by the maximum ■ At changes in plan geometry where differences
spacing, articulation joints should also be located in movement may occur, eg where the family
at positions where concentrations or variations in room shown in Figure 4 is connected to the
the potential development of stress may occur, for remainder (and basic rectangular shape) of the
example: house.
■ Where the height of the wall changes abruptly by
more than 20% of its lesser height eg changes of For other than brick veneer walls (which are
storey height Figure 5. attached to a structural/supporting framework),
■ Control or construction joints in slab-on-ground articulation joints should be located either at or
or strip footings. within 300 mm of wall junctions or engaged piers
■ Window and door openings Figures 6 to 9. For that serve as lateral supports. Note that their
two-storey buildings, positioning openings to positioning should not interfere with the required
allow easier location of articulation joints is lateral support Figure 17.
desirable Figure 8. Note that most lintel design
methods assume arching of the masonry over
Articulated Walling Page 7