Attachment 4 - Site Investigation and Slab Report
Return wall Return wall required 300
required for for lateral restraint max.
lateral restraint
Articulation joint
with sliding ties Articulation joint Articulation joint
INCORRECT 7 CORRECT 3 CORRECT 3
Figure 17 Location of articulation joints to maintain stability
7.1.1 Minimum Width Sealants should be applied towards the end of
The minimum width of articulation joints should the construction after any initial movement has
take into consideration the height of the wall and occurred.
the expected movement, especially if the joint is to For clay bricks which tend to grow, sealants
serve the dual function of articulation and expansion must allow for long-term, permanent compression;
or contraction. Table 2 gives suitable joint spacings for concrete or calcium silicate bricks and blocks
for both 10- and 15-mm-wide joints for walls up to which tend to shrink, the sealants must allow for
8.5 m high. long-term tension.
The joint widths in Table 2 will also The geometry of the sealant is important to
accommodate some expansion or contraction of ensure that the material is able to comply with the
the masonry wall panels. Designers and builders stated performance. If the depth of the sealant is
should, however, consider whether there is potential too great it will act more like a rigid ‘block’ than a
for greater movement than can be accommodated thin elastic member and will not be able to extend/
by a 10- or 15-mm joint width, eg in mine contract properly. Generally, the depth of sealant
subsidence areas. Where the control joint functions should not be more than the joint width for joints up
both as an articulation joint and an expansion to 12 mm in width, and no more than half the joint
joint, either the overall width of the joint should width for wider joints. The joint filler or a backer
be increased to 0.7 times the sum of the required rod, are typically used to provide the correct joint
widths for each separate function, or the joint geometry. The manufacturer’s recommendations
spacing should be reduced for the 10- or 15-mm- should be followed for each specific material.
wide joints. Note that sealants may need to be replaced every
10 to 15 years (depending on type and exposure
7.1.2 Joint Sealants condition) as part of building maintenance.
Sealant materials typically include silicones and Where articulation joints occur at the ends of
polyurethanes. For painted finishes, either a lintels (ie at the sides of window/door openings)
specialist silicone sealant that can be painted, or and movement of the lintel along the bed joint
more commonly, a polyurethane sealant should be is expected, this joint may also be sealed as the
used. Polysulphide materials (able to be painted) movement will typically cause cracking and loss of
are also available but as they are two-component the mortar from the joint Figure 22.
products, they are not commonly used. Sealants If the wall of a Class 1 building (house) is located
should have a minimum extensibility of 50% closer than 900 mm to a property boundary (other
(ie ±25%) and be suitable for the clay or concrete than a boundary adjoining a road or other public
masonry walling material used. Some sealants may space), the BCA requires a fire resistance level
require priming of the joint to promote bonding to (FRL) of not less than 60/60/60. However, the BCA
the substrate. Sealants are gunned into the joint states that small openings in the masonry such
and are available in a variety of colours, either to as sub‑floor vents, weepholes and control joints
match the masonry or mortar colour to assist in (including articulation joints) do not need to be fire
reducing the visual impact of the joint. It is also rated. For fire separating walls of attached Class 1
possible to dust the surface of freshly applied buildings and other building types, the use of a
sealant with crushed mortar, thereby giving it a fire‑rated sealant in articulation joints should be
texture and colour that closely matches the mortar provided. For such buildings, the sealant may also
joints in the surrounding brickwork. Note that need to provide acoustic performance.
sealants and/or filler materials should be recessed
back from the outside face to prevent the sealant
being squeezed out of the joint if the maximum
expected compression of the joint occurs Figure 21.
Page 12 Articulated Walling