7.1.3 Wall Ties
Face of lintel may To provide support for wall panels at articulation
be sealed
joints, the BCA requires wall ties to be provided
on each side of the joint and spaced horizontally
no more than 300 mm from the joint. The vertical
spacing of wall ties at articulation joints must also
be halved, effectively doubling the number of ties
at these locations. In order to suit brick or block
courses, the vertical spacing could vary from 200 to
400 mm but should average the required 300-mm
spacing (ie half of the normal 600-mm vertical
spacing).
For cavity and unreinforced single-leaf masonry
walls, lateral support across the joint (to carry
horizontal loads and to maintain alignment) should
be provided. To achieve this, and also to allow the
joint to open and close, masonry expansion (sliding/
Figure 22 Bed joint along lintel may also require extendable) ties are used Figure 23. The strength,
sealing at articulation joints number and spacing of ties should be sufficient to
transfer the calculated loads across the joint. As a
Articulation joint Articulation joint
Figure 23 Examples of masonry expansion (sliding/extendable) ties