Attachment 5
Revised Stormwater Engineering
Report
Response to Council’s Information Request –
Combined Applications for a Development
Permit for a Material Change of Use and
Operational Works Permit to Establish Multiple
Dwellings (11 x Units)

5 Pearl Street and 54 Elm Street, Cooroy 4563 QLD
Lot 2 on RP153798 and Lot 2 on RP64750


4CD DEVELOPMENTS PTY LTD (A.B.N. 28 649 018 904)
Full text of the other 63 pages

Page 2

     STORMWATER ENGINEERING REPORT

     The Belvedere on Pearl
     5 Pearl Street
     Cooroy, QLD 4563
     Project No.: 21011

     Version: 2.0
     Version Date: 16/08/21




                                                                                                  Page 1 of
                                                                                                  36

P +61 7 5211 1003   A 37 Mary St, Noosaville Qld 4566   E [email protected]   recorconsulting.com

Page 3

            PROJECT INFORMATION



            Client:                              VIVIDO

            Site Location:                       5 Pearl Street / 54 Elm Street, Cooroy QLD 4563

            Lot & Plan:                          Lot 2 RP153798 & Lot 2 RP64750

            Proposed Development: ‘The Belvedere on Pearl’ residential development




            RECOR Consulting

            Project Reference:                   21011

            Contact Person:                      Benjamin Parry

            Contact Phone:                       (07) 5211 1003




            Document Control:




                      VERSION                        PREPARED              REVIEWED                DATE

                        1.0                             B. Parry            M. Poynter           02/07/2021


                        2.0                             B. Parry            M. Poynter           16/08/2021




                                                                                                                     Page i
P +61 7 5211 1003         A 37 Mary St, Noosaville Qld 4566         E [email protected]       recorconsulting.com

Page 4

            TABLE OF CONTENTS

            PROJECT INFORMATION .................................................................................................................................... I
            TABLE OF CONTENTS ........................................................................................................................................ II
            1. INTRODUCTION ............................................................................................................................................ 1
            2. SITE DETAILS ................................................................................................................................................. 1
               2. 1. E X I S T I N G S I T E D E S C R I P T I O N ................................................................................ 1
               2. 2. E X I S T I N G D R A I N A G E P A T T E R N S ............................................................................. 3
                 2.2.1 Existing Stormwater Infrastructure .................................................................................................... 3
                 2.2.1.1.          Roof Drainage ......................................................................................................................... 3
                 2.2.1.1.          Upstream Catchments............................................................................................................. 4
                 2.2.1 Stormwater Catchments .................................................................................................................... 5
               2. 3. P R O P O S E D D E V E L O P M E N T D R A I N A G E P A T T E R N .......................................................... 5
                 2.3.1 Stormwater Concept .......................................................................................................................... 5
                 2.3.2 Stormwater Catchments .................................................................................................................... 6
               2. 4. F L O O D C O N S I D E R A T I O N S .................................................................................... 7
            3. STORMWATER QUANTITY ............................................................................................................................ 8
               3. 1. D I S C H A R G E T O P E A R L S T R E E T ............................................................................... 8
            4. STORMWATER QUALITY ............................................................................................................................. 11
               4. 1. C O N S T R U C T I O N P H A S E ...................................................................................... 11
                 4.1.1 Erosion and Sediment Control Measures ......................................................................................... 11
                 4.1.2 Erosion and Sediment Control Monitoring ....................................................................................... 12
               4. 2. O P E R A T I O N A L ................................................................................................ 12
                 4.2.1 MUSIC Modelling ............................................................................................................................. 13
                 4.2.1.1.          Rainwater Tanks ................................................................................................................... 14
                 4.2.1.1.          Pit Inserts .............................................................................................................................. 16
                 4.2.1.1.          Bioretention Areas ................................................................................................................ 17
                 4.2.1.2.          MUSIC modelling results ....................................................................................................... 18
                 4.2.2 Operational Maintenance ................................................................................................................ 19
            5. CONCLUSION .............................................................................................................................................. 20
                                   PROPOSED DEVELOPMENT PLANS ........................................................................................ 22
                                   STORMWATER HGL ANALYSIS ............................................................................................... 23
                                   EXAMPLE ESC DEFECT DOCUMENTATION TEMPLATE ............................................................ 29
                                   ECOSOL LITTER BASKET TECHNICAL SPECIFICATION .............................................................. 31
                                   BIORETENTION INSPECTION CHECKLIST ................................................................................ 32




P +61 7 5211 1003                  A 37 Mary St, Noosaville Qld 4566                               E [email protected]                                 recorconsulting.com

Page 5

            1. INTRODUCTION
            RECOR Consulting has been commissioned to prepare a Stormwater Management Report
            to accompany a development application for a proposed residential unit development in
            Pearl Street, Cooroy.

            This report examines the stormwater management considerations for the existing and
            proposed development site and assesses how the run-off from the site is to be managed in
            accordance with Noosa Shire Council requirements for stormwater drainage.


            2. SITE DETAILS
                    2. 1. E X I S T I N G S I T E D E S C R I P T I O N

            The existing site is made up of two adjoining properties, Lot 2 on RP64750 (no. 54) and Lot
            2 on RP153798 (no. 5), with street frontages on Elm Street and Pearl Street, Cooroy,
            respectively. The neighbouring properties to the south-west, east and north-west are zoned
            residential, with the land to the north-east designated as environmental open space on the
            Council mapping service.




                                  Figure 2.1 - Site Locality Plan (Noosa Council Intramaps, 2021)


                                                                                                                 Page 1 of 33
P +61 7 5211 1003               A 37 Mary St, Noosaville Qld 4566         E [email protected]   recorconsulting.com

Page 6

            Lot 2 on RP64750 is accessed from the 21.456m frontage at 54 Elm St. The site has an area
            covering 1,516.4m² and currently houses a dilapidated detached dwelling and two free
            standing sheds on the western end of the site, and unmaintained vegetation on the eastern
            end.




                             Figure 2.2 – 54 Elm Street, view east from driveway access.

            Lot 2 on RP153798 has a 30.175m frontage which provides access to the property from 5
            Pearl Street. The site covers 758.2m² and contains a detached dwelling and double bay
            shed with predominately grass to the rear of the property.




                         Figure 2.3 – 5 Pearl Street, view west from south-eastern corner.

            The two sites cover a combined area of 2,274.6m², made up of approximately 418m² of roof
            area and 124m² of paved surfaces.

                                                                                                       Page 2 of 33
P +61 7 5211 1003       A 37 Mary St, Noosaville Qld 4566    E [email protected]      recorconsulting.com

Page 7

                    2. 2. E X I S T I N G D R A I N A G E P A T T E R N S

                        2.2.1 Existing Stormwater Infrastructure

            Data obtained from the detailed survey and Council’s interactive mapping show that there
            is no existing stormwater infrastructure on either of the site frontages nor property
            boundaries. Table drains convey stormwater drainage from the street along both Elm Street
            and Pearl Street.

            The nearest stormwater infrastructure is an existing 300mm diameter pipe located on the
            southern side of Pearl Street, which is then conveyed through stormwater infrastructure in
            Lot 0 SP260162 and Lot 48 C56013 towards an open drain in the environmental park) at
            Lot 5 CP889589 to the north-east of the site (refer Figure 2.1).

                             2.2.1.1.        Overland Flow

            The surface run-off from the site drains towards the north-eastern corner of the lots into the
            adjacent properties along the north and eastern boundary. No natural drainage channels
            occur within the lots causing the stormwater to drain as overland sheet flow across slopes
            of typically between 3% and 6%. From the north-eastern corner of the lot, the external
            natural topography indicates the surface water is conveyed overland towards the open
            drain in the environmental park at Lot 5 CP889589.

                             2.2.1.2.        Roof Drainage

            Within Lot 2 RP 64750, the roof drainage from the main dwelling is collected in gutters and
            downpipes that appear to discharge toward the northern boundary as overland flow, as no
            alternative discharge point was located on site nor into the road reserve. Neither of the free-
            standing shed structures had gutters, so water from these areas would contribute directly
            to overland flows.




                                                                                                                   Page 3 of 33
P +61 7 5211 1003               A 37 Mary St, Noosaville Qld 4566           E [email protected]   recorconsulting.com

Page 8

                    Figure 2.4 – Lot 2 RP 64750, roof downpipe draining towards northern boundary.

            Roof run-off from the dwelling on Lot 2 RP 153798 is similarly collected in downpipes and
            no outlet could be located within the property nor within the street drainage. It is assumed
            that this water must be discharged as overland flow on site as surface levels along the
            frontage are typically higher than within the property making gravity drainage to the street
            unlikely.

            Roof water from the garage on this property is collected and conveyed to a water tank on
            site of approximately 10,000L, with overflows discharged as overland flow within the
            property.

                         2.2.1.1.       Upstream Catchments

            Surface run-off from the upstream adjacent property on Lot 1 RP 153798 is expected to
            enter Lot 2 RP 153798 as overland flow due to the observed absence of any existing
            drainage infrastructure and the topography indicated by contour maps, however on site
            confirmation of runoff was not achieved due to lack of favourable conditions. Roof water
            from the dwelling on the upstream property appears to discharge directly to the table drain
            on pearl street through a piped outlet.

            Surface run-off from the road reserve is typically collected in the table drains along the street
            frontage and does not appear to enter the site.

                                                                                                            Page 4 of 33
P +61 7 5211 1003          A 37 Mary St, Noosaville Qld 4566    E [email protected]        recorconsulting.com

Page 9

                        2.2.1 Stormwater Catchments

            A schematic layout plan of the existing drainage catchments as described in the previous
            sections is shown below in Figure 2.5 – Existing Catchments Plan.




                                                   Figure 2.5 – Existing Catchments Plan.



                    2. 3. P R O P O S E D D E V E L O P M E N T D R A I N A G E P A T T E R N

                        2.3.1 Stormwater Concept

            Under existing conditions, the stormwater leaves the property as overland surface flows into
            the adjoining properties to the east and north of the proposed development. The proposed
            lawful point of discharge for the proposed development will be to the existing table drain
            on Pearl Street, which will have the benefit of reducing the impact of overland flow from the
            site on the adjoining property owners, and ensuring the runoff is discharged in a controlled
            manner into Council’s drainage network.



                                                                                                                   Page 5 of 33
P +61 7 5211 1003              A 37 Mary St, Noosaville Qld 4566            E [email protected]   recorconsulting.com

Page 10

            Roof run-off will be collected and flow via downpipes into four slim-line rainwater tanks with
            overflow into the internal drainage network within the site. Each tank is a nominal 5kL, with
            3.75kL allocated to reuse purposes and the remaining 1.25kL per tank being dedicated for
            attenuation. To minimise pollutants entering the tank, first flush diverters will be installed to
            divert the initial capture of roof water to irrigation of the vegetated areas on site.

            Finished surface levels will direct runoff to either stormwater pits or towards one of two
            bioretention areas at the east and west of the property. The bioretention areas will provide
            stormwater quality improvements to the run-off, as well as serving to provide additional
            attenuation.

            The attenuated run-off will be conveyed to a storage manhole to the south-east of the site
            from where it will be pumped off the site to the downstream receiving table drain. The
            transfer system (pump and drainage line) has been designed to ensure discharges are
            within the capacity of the receiving system.

            A stormwater drainage line will be installed along the south-western (upslope) boundary
            with Lot 1 on RP153798 with inlet pits to collect the surface run-off from the upstream
            catchments and divert it around the site, directly to the pump-out manhole. Similarly, a
            slotted drain will be installed across the proposed driveway at the property boundary to
            intercept upstream flows and convey them directly to the pump out storage area.

            The roof and allotment drainage system for the proposed site shall be designed to comply
            with:

                    1. Noosa Shire Council Planning Scheme Policy (PSP) - Engineering Design Standards
                       – Roads, drainage and earthworks;

                    2. The Queensland Urban Drainage Manual (QUDM); and

                    3. AS/NZS 3500.3:2015 - Plumbing and Drainage Part 3: Stormwater Drainage.

                       2.3.2 Stormwater Catchments




                                                                                                            Page 6 of 33
P +61 7 5211 1003           A 37 Mary St, Noosaville Qld 4566   E [email protected]        recorconsulting.com

Page 11

                                                                                                             Point of Discharge




                                                 Figure 2.6 – Proposed Catchments Plan.

                    2. 4. F L O O D C O N S I D E R A T I O N S

            The Noosa Shire Council Intramaps Flood Hazard Overlays show that the proposed
            development site is not likely to be subject to flooding or inundation up to and including an
            extreme (1 in 500 year) flood event.




                                                                                                              Page 7 of 33
P +61 7 5211 1003              A 37 Mary St, Noosaville Qld 4566       E [email protected]   recorconsulting.com

Page 12

            3. STORMWATER QUANTITY
                    3. 1. D I S C H A R G E T O P E A R L S T R E E T

            As the existing site and upstream catchments currently drain overland into private property
            to the north and east, and the proposal seeks to discharge the run-off to a new legal point
            of discharge in Pearl Street, a comparison of the pre-development discharges to post-
            development discharges at the point of discharge is not appropriate. To demonstrate the
            impact to the receiving environment (system), an assessment of the existing street drainage
            capacity in Pearl Street has been undertaken. This demonstrates that the receiving system
            (the street table drain system) has the capacity to carry the 1% AEP storm event from its
            contributing catchment (including the development site) to the sag point of Pearl Street to
            drain to the trunk stormwater drainage line.

            Based on contours of the locality, surface run-off generally drains to the northeast towards
            the existing drainage channel in the environmental park to the north. The existing
            contributing catchment is predominately comprised of residential properties, road and
            verge strips. The area currently draining to the street drainage system (where the new
            proposed legal point of discharge is located) is shown below in Figure 3.1 – Existing Street
            Drainage Catchments.




                                          Figure 3.1 – Existing Street Drainage Catchments.

            The peak storm event for the 1% AEP was modelled using the Autodesk Storm and Sanitary
            Analysis module, with the catchment hydrology configured in accordance with the Bureau
            of Meteorology’s IFD curves for the locality, and a minimum time of concentration of 5
            minutes for each catchment. All catchments for the proposed development and the internal
            drainage network and storage areas have been modelled, along with the upstream and
            downstream catchments within Pearl Street (estimated based on contour maps and site
            inspections), and the street drainage characteristics to determine a maximum discharge
            from the development. The catchment details for the proposed development site (Figure
            2.6 – Proposed Catchments Plan.) are shown below in Table 3.1-Development Catchment
            Areas.



                                                                                                               Page 8 of 33
P +61 7 5211 1003              A 37 Mary St, Noosaville Qld 4566        E [email protected]   recorconsulting.com

Page 13

                                         Table 3.1-Development Catchment Areas

                                   Catchment            Area (Ha)    Run-off Coefficient

                                   C1                   0.0167       0.96

                                   C2                   0.0196       0.96

                                   C3                   0.0279       0.96

                                   C4                   0.0168       0.96

                                   C5                   0.0168       0.96

                                   C6                   0.0354       0.76

                                   C7                   0.0030       0.33

                                   C8                   0.0097       0.33

                                   C9                   0.0191       0.33

                                   C10                  0.0168       0.76

                                   C11                  0.0369       0.76

                                   C12                  0.0082       0.33

                                   E2                   0.0442       0.34

                                   E3                   0.0667       0.34

                                   E4                   0.0372       0.77

                                   E5                   0.0204       0.96

                                   E6                   0.0331       0.37

                                   E7                   0.0277       0.77



            Using the modelling, a suitable pump-out rate for the development to discharge into Pearl
            Street can be established for the 100-year storm event. It was determined that discharging
            from the proposed development at a rate limited to 64L/s (including the discharge of
            upstream catchments that are conveyed through the property), will ensure that the
            discharge is able to be conveyed in the street drainage system with minimal impacts to the
            upstream or downstream properties.

            The modelling also demonstrates that the storage areas, comprised of the 4 x 5,000L
            rainwater tanks (attenuation portion only), the bioretention areas and the pump-out storage
            manhole provide sufficient capacity so that the internal drainage network is not exceeded


                                                                                                           Page 9 of 33
P +61 7 5211 1003       A 37 Mary St, Noosaville Qld 4566           E [email protected]   recorconsulting.com

Page 14

            for the 1% AEP storm event with this pump out rate. The output of the hydraulic modelling
            showing the maximum Hydraulic Grade Lines (HGL) for the development is provided in
            Appendix B Stormwater HGL Analysis.




                                                                                                     Page 10 of 33
P +61 7 5211 1003       A 37 Mary St, Noosaville Qld 4566   E [email protected]     recorconsulting.com

Page 15

            4. STORMWATER QUALITY
            The following sections discuss the stormwater quality considerations for the construction
            and operational phase of the development. Refer to Appendix A Proposed Development
            Plans for the proposed stormwater drainage layout plan.


                    4. 1. C O N S T R U C T I O N P H A S E

                        4.1.1 Erosion and Sediment Control Measures

            During construction, it is necessary to manage stormwater run-off to avoid potential
            contamination of downstream waterways from sediments and other pollutants from the site.
            Best practice erosion and sediment controls shall be installed to minimise the discharge of
            potential contaminants from the site, in accordance with the objectives of Appendix 2 of the
            SPP (DERM, July 2017) shown below in Figure 4.1.




               Figure 4.1 SPP 2017 Construction Phase Stormwater Management Design Objectives

            Appendix A (Proposed Development Plans) contains the site-specific erosion and sediment
            control (ESC) Plan prepared for the development. The measures proposed for the site
            include:



                                                                                                          Page 11 of 33
P +61 7 5211 1003              A 37 Mary St, Noosaville Qld 4566   E [email protected]   recorconsulting.com

Page 16

                    1. Sediment fencing is to be installed along the northern and eastern boundaries of the
                       site to capture sediment from leaving the site. Drainage paths will be inspected to
                       ensure the sediment fences are not being bypassed as a result.

                    2. A shakedown area is to be installed at the construction entry/exit to the site to
                       minimise sediment being transported to and from the site.

            In addition to these measures, stockpiles and construction materials will not be stored within
            the road reserve and shall be contained using sediment fencing downstream of these areas.
            Turfed diversion swales will be provided at upstream boundaries to reduce flows to
            earthworks areas and sediment disposal from the site shall be undertaken to the satisfaction
            of Noosa Shire Council.

                        4.1.2 Erosion and Sediment Control Monitoring

            The control measures described above will be maintained in an effective operational
            condition during the construction works. Regular inspections will be carried out by the
            contractor and any defects in the erosion and sediment control devices specified will be
            remedied as soon as practicable. Inspections (in accordance with SPP 2017) are to be
            carried out as follows:

                             1. Routine Inspection – is to be carried out daily while work is being carried out
                                on site, or weekly while works are not being carried out.
                             2. Preventative inspection – to be carried out a maximum of 24 hours before
                                rain is forecast.
                             3. Reactive inspection – to be carried out within 18 hours of a rainfall event
                                sufficient to mobilise surface sediment on the site.

            Documentation of any defects will also be carried out in accordance with SPP 2017, which
            includes recording the date the defect was identified, a description of the defect, the
            cause of the defect and measures that can be implemented to reduce the likelihood of the
            defect reoccurring. Once the device has been repaired, the date of repair and the solution
            implemented will also be recorded in the documentation. An example template for this
            documentation has been provided in Appendix C Example ESC Defect Documentation
            Template.


                    4. 2. O P E R A T I O N A L P H A S E

            The development is to comply with the Noosa Council Water Quality and Drainage Code,
            AO6.2 which states:

            “All stormwater runoff is treated to achieve maximum removal of nutrients, gross pollutants
            and suspended solids as determined by cost to efficiency ratios. (e.g. bioretention basins
            must be sized to achieve at least 80% reduction in total suspended solids, 60% reduction in
            total phosphorous, 45% reduction in total nitrogen and 90% reduction in gross pollutants
            >5mm).”

            It is proposed that the following measures to be implemented will provide the required
            level of stormwater quality improvement to minimise impacts to the downstream network:


                                                                                                               Page 12 of 33
P +61 7 5211 1003              A 37 Mary St, Noosaville Qld 4566    E [email protected]       recorconsulting.com

Page 17

                    •   First-flush divertors will be installed for roof-water drainage to divert initial run-off
                        capture to irrigation of the vegetated areas on site.
                    •   4 x 5,000L Slimline Rainwater tanks will be used to capture roof run-off, with 75% of
                        the tank volume allocated to reuse, and 25% to detention storage.
                    •   2 x Bioretention areas will be used to treat and detain stormwater run-off from
                        driveway areas.
                    •   Ecosol Litter baskets (or similar) with 200µm mesh are to be provided within all
                        field inlet pits minimise sediment and gross pollutants from entering the drainage
                        line. Refer to Appendix D Ecosol Litter Basket Technical Specification for details.

                        4.2.1 MUSIC Modelling

            The proposed development and the above treatment train have been modelled in MUSIC
            (Model for Urban Stormwater Improvement Conceptualisation) software in accordance
            with the Water by Design MUSIC Guidelines 2018.

            The climatic data has been modelled using the rainfall and PET data at station 40059
            (Cooroy Composite) in 6-minute timesteps. The rainfall run-off parameters have been set
            as defined for the Southeast Queensland region, shown below in Figure 4.2 - Rainfall run-
            off parameters for SEQ.




                                           Figure 4.2 - Rainfall run-off parameters for SEQ

            The source nodes have been created using a split catchment approach, with the roof,
            driveway and other ground areas separated with stochastic pollutant generation for each
            of the surface types as per Table 4.1 - Urban Residential Split Node Pollutant Generation
            Parameters. The area and impervious fractions for each catchment are actual values based
            on the design plans.




                                                                                                                 Page 13 of 33
P +61 7 5211 1003             A 37 Mary St, Noosaville Qld 4566       E [email protected]       recorconsulting.com

Page 18

                    Table 4.1 - Urban Residential Split Node Pollutant Generation Parameters

             Flow Type      Surface          TSS LOG¹º                TP LOG¹º VALUES               TN LOG¹º VALUES
                            Type             Mean      St. Dev        Mean       St. Dev            Mean      St. Dev
             Baseflow  Roof                     N/A            N/A      N/A            N/A            N/A        N/A
                       Driveway                 1.00           0.34    -0.97           0.31           0.20       0.20
                       Ground                   1.00           0.34    -0.97           0.31           0.20       0.20
             Stormflow Roof                     1.30           0.39    -0.89           0.31           0.26       0.23
                       Driveway                 2.43           0.39    -0.30           0.31           0.26       0.23
                       Ground                   2.18           0.39    -0.47           0.31           0.26       0.23

            The proposed treatment train has been modelled as shown in Figure 4.3 - MUSIC
            Stormwater Treatment Train. The details of the treatments are described in the following
            sections




                                        Figure 4.3 - MUSIC Stormwater Treatment Train



                         4.2.1.1.       Rainwater Tanks

            The rainwater tanks collecting roof water are connected to the source nodes representing
            their drained catchments. Each of the tanks to be provided is modelled as a 5kL storage
            volume, with 3.75kL allocated for re-use (assumed to be full at beginning of the modelling)
            and the remaining portion being for attenuation purposes.




                                                                                                                         Page 14 of 33
P +61 7 5211 1003          A 37 Mary St, Noosaville Qld 4566           E [email protected]              recorconsulting.com

Page 19

                                              Figure 4.4 – Typical Tank node configuration

            Each tank is to be fitted with a first flush diverter to prevent potential sediments from
            entering the tanks. This is modelled by assuming the first 25L of rainfall falling over the roof
            area is diverted to the first flush diverter and discharged to irrigate vegetated areas on site,
            equating to a 0.12mm increase to the rainfall threshold on the upstream roof source node.

            The tanks will be plumbed for internal and external reuse which has been modelled in
            accordance with the Water by Design MUSIC Modelling guidelines. The reuse demands
            have been determined as follows:

                    -   Internal Reuse

                           o     All homes are assumed to be fitted with full water saving devices,

                                      ▪     26L/Person/day for laundry

                                      ▪     21L/Person/day for toilets

                           o     ½ Pod C roof run-off:

                                      ▪     2x2 bed = 3.2 persons

                                      ▪     3.2 * 47L = 150.4L/day




                                                                                                                Page 15 of 33
P +61 7 5211 1003              A 37 Mary St, Noosaville Qld 4566         E [email protected]   recorconsulting.com

Page 20

                           o     ½ Pod C & Pod B roof run-off:

                                      ▪     2x2 bed = 3.2 persons

                                      ▪     2x3 bed = 4.6 persons

                                      ▪     7.8 * 47L = 367L/day

                           o     ½ Pod A roof run-off:

                                      ▪     2x2 bed = 3.2 persons

                                      ▪     3.2 * 47L = 150.4L/day

                    -   External Reuse

                           o     75% of the pervious area in proximity to the tank will be irrigated at
                                 548mm/year

                           o     ½ Pod C roof run-off

                                      ▪     0.75 * 110m² * 0.548 = 45kL/year

                           o     ½ Pod C & Pod B roof run-off

                                      ▪     0.75 * 162m² * 0.548 = 67kL/year

                           o     ½ Pod A roof run-off

                                      ▪     0.75 * 15m² * 0.548 = 6kL/year


                           4.2.1.1.         Pit Inserts

            All grated inlet pits within the development are to be fitted with Ecosol Litter baskets with
            200µm filter Bags. These have been certified by the manufacturer as having the pollutant
            removal efficiencies shown in Figure 4.5 - Ecosol Litter Basket Pollutant Removal Efficiencies.
            The inserts are modelled using generic treatment nodes, with a high flow bypass of 53L/s
            and concentration-based capture efficiency set in accordance with manufacturers
            guidelines. Refer to Appendix D Ecosol Litter Basket Technical Specification for further
            details on the devices.




                                                                                                             Page 16 of 33
P +61 7 5211 1003              A 37 Mary St, Noosaville Qld 4566      E [email protected]   recorconsulting.com

Page 21

                          Figure 4.5 - Ecosol Litter Basket Pollutant Removal Efficiencies


                      4.2.1.1.       Bioretention Areas

            Two 12.5m² bioretention areas are to be provided within the development to capture and
            treat surface run-off from road areas as well as overflows from attenuation tanks. The
            bioretention areas are modelled in accordance with the Water by Design MUSIC Guidelines
            2018 with the node configuration for one of the areas shown below in Figure 4.6 –
            Bioretention Node details.




                                            Figure 4.6 – Bioretention Node details

                                                                                                         Page 17 of 33
P +61 7 5211 1003       A 37 Mary St, Noosaville Qld 4566         E [email protected]   recorconsulting.com

Page 22

            Table 4.2 – Bioretention Area Plantings below (based on the Brisbane City Council Water
            Sensitive Urban Design Engineering Guidelines) presents a sample of suitable plants that
            shall be used to provide effective nutrient removal in the bioretention areas.

                                              Table 4.2 – Bioretention Area Plantings

                                                                                                                           Planting
                                                                                                                           Density
             Scientific Name                                   Common Name                      Form         Height (mm)   (Qty/m²)
             Myoporum parvifolium                              Creeping Boobialla               Prostrate           150    4-6
             Cymbopogon refractus                              Barbed Wire Grass                Tufted              300    8-10
             Cyperus polystachyos                              Bunchy Sedge                     Tufted              600    6-8
             Dianella brevipendunculata                        Flax Lily                        Tufted              500    4-6
             Dianella caerulea cv ‘Breeze’                     Blue Flax-lily                   Tufted              600    4-6
             Dianella caerulea cv ‘Little Jess’                Blue Flax-lily                   Tufted              400    4-6
             Dianella longifolia var. longifolia               Pale Flax-lily                   Tufted              550    6-8
             Dichelachne crinita                               Long Haired Plume Grass          Tufted              200    6-8
             Erograstis elongata cv ‘Elvera’                   Elvera                           Tufted              300    6-8
             Imperata cylindrica                               Blady Grass                      Tufted              500    4-6
             Lepidosperma laterale                             Variable Sword Sedge             Tufted              750    8-10
             Lomandra confertifolia                            Matting Lomandra                 Tufted              300    4-6
             Lomandra confertifolia subs pallida               Mat Rush                         Tufted              400    4-6
             Lomandra longifolia                               Matt Rush                        Tufted             1000    4-6
             Lomandra longifolia cv 'Tanika'                   Tanika                           Tufted              500    4-6
             Poa labillardiere cv ‘Eskdale’                    Eskdale                          Tufted              450    6-8
             Themeda australis                                 Kangaroo Grass                   Tufted              400    6-8
             Themeda australis cv ‘Mingo                       Mingo                            Tufted              200    8-10



                        4.2.1.2.        MUSIC modelling results

            The proposed treatment train is able to achieve the required water quality improvements
            as shown below in Table 4.3 - MUSIC Modelling results.

                                                Table 4.3 - MUSIC Modelling results

                                                      Sources              Residual           Percentage        Percentage
                                                                           Load               Target            Reduction

             Total Suspended Solids (kg/yr)              560.37                 94.50                 80             83.14

             Total Phosphorus (kg/yr)                      1.24                 0.41                  60             66.93

             Total Nitrogen (kg/yr)                        7.47                 4.07                  45             45.49

             Gross Pollutants (kg/yr)                     66.58                 0.00                  90            100.00




                                                                                                                                  Page 18 of 33
P +61 7 5211 1003          A 37 Mary St, Noosaville Qld 4566                    E [email protected]            recorconsulting.com

Page 23

                     4.2.2 Operational Maintenance

            Periodic maintenance and monitoring of the stormwater infrastructure proposed for this
            development will be carried out to ensure they are operating effectively during the post-
            construction phase. After the on-maintenance period, the responsibility for these
            maintenance activities shall be the body corporate for the site who may appoint a suitably
            qualified maintenance contractor to undertake these activities.

            The field inlet grates, pits and underground pipes shall be inspected for blockage or
            damage at least six monthly or after significant rainfall event. Any blockages shall be
            cleared from the system, and damage assessed to determine if it impacts on the function
            of the system or may pose a hazard that will require repair.

            The litter baskets shall be maintained in accordance with the manufacturer’s specifications.
            Refer to Appendix D Ecosol Litter Basket Technical Specification for further details.

            The bioretention areas shall be maintained following a schedule of routine inspections
            undertaken after every significant rainfall event (30mm of rainfall in a 24-hour period) or on
            a three monthly basis within the first twelve months and on a six monthly basis thereafter.
            The inspection shall ensure the proper functioning and condition of the bioretention area
            and ensure that the planting and vegetation health is suitably maintained. An inspection
            checklist from the Healthy Waterways Technical Design Guidelines for Southeast
            Queensland has been provided in Appendix E Bioretention Inspection Checklist that
            provides the structure for the inspections to be undertaken.

            In addition to regular inspections, the first 4 months of establishment of the bioretention
            areas requires a watering frequency of:

               i.    Week 1 - 6: 5 times per week

               ii.   Week 6-10: 3 times per week

              iii.   Week 11-15: 2 times per week

            After 5 months, watering frequency shall be adjusted based on the local conditions to
            ensure plants are maintained in a healthy state.




                                                                                                          Page 19 of 33
P +61 7 5211 1003         A 37 Mary St, Noosaville Qld 4566   E [email protected]        recorconsulting.com

Page 24

            5. CONCLUSION
            This Stormwater Management Report has outlined how the stormwater run-off from the site
            is to be managed to comply with the relevant requirements and minimise any adverse
            impacts to the downstream catchments.

                    •   The existing site and upstream catchments’ drainage patterns currently discharge
                        from the site as overland (potentially nuisance) flows into adjacent properties to the
                        north and east of the proposed development site.

                    •   The proposed legal point of discharge for the site will be to the stormwater drainage
                        system on Pearl Street.

                    •   As none of the existing catchments currently drain to the street, a pre-development
                        to post-development comparison of site discharges is not suitable for the
                        development. The existing capacity of the Pearl Street drainage system has been
                        analysed to determine an allowable discharge from the development to the legal
                        point of discharge.

                        The proposed development site, and the upstream and downstream catchments
                        draining to the Pearl Street drainage system have been modelled under the 1% AEP
                        storm event conditions to determine an appropriate discharge rate from the site that
                        will serve to minimise the impacts to the upstream or downstream network and
                        adjacent properties. It was found that with a maximum pump out rate of 64L/s from
                        the site, both the proposed internal stormwater network and the street drainage
                        system can suitably convey storms up to the 1% AEP.

                    •   During construction, erosion and sediment control measures will be implemented
                        to minimise potential contaminants impacting the downstream receiving
                        environment. These measures are to be inspected and maintained regularly during
                        construction.

                    •   In the operational phase of the development, a stormwater treatment train will
                        provide quality improvements as required by the Noosa Council Planning Scheme
                        Policy. Roof run-off is to be directed towards 4 x 5,000L rainwater reuse and
                        attenuation tanks that will be fitted with first-flush divertors to will divert initial roof
                        run-off to on site irrigation of vegetated areas. The tanks are to be plumbed for reuse
                        for internal (laundry and toilets) and external (irrigation) purposes that will serve to
                        provide both treatment and reduce the volume of run-off entering the drainage
                        network. Overflows from the tanks, as well as overland flows from the ground areas,
                        are to be directed toward the site’s stormwater treatment devices. These are
                        principally made up of two 12.5m2 bioretention areas that will treat the majority of
                        run-off from the driveway areas while also attenuating run-off volumes. Ecosol litter
                        baskets with 200µm filter screens will also be provided to all pits within the
                        development to ensure treatment for any run-off that bypasses or is unable to be
                        captured by the bioretention areas. The stormwater system will convey run-off to a
                        manhole chamber providing further attenuation storage prior to pump-out from the
                        site. Water pumps, to be specified by a hydraulic engineer, will be used to pump


                                                                                                                   Page 20 of 33
P +61 7 5211 1003             A 37 Mary St, Noosaville Qld 4566      E [email protected]          recorconsulting.com

Page 25

                        stormwater into the legal point of discharge on Pearl Street at a maximum rate of
                        64L/s from the development.

                        By implementing the proposed stormwater treatments, the development will reduce
                        the quantity of stormwater pollutants by more than 90% of gross pollutants, 80% of
                        total suspended solids, 60% total phosphorous and 45% total nitrogen, exceeding
                        the pollutant reduction targets required for the site.

                    •   By implementing the proposed stormwater solution, it is considered that stormwater
                        layout proposed will minimise any adverse impacts to the downstream environment
                        and neighbouring properties arising from the stormwater run-off while also meeting
                        the stormwater quality targets required for the development.




                                                                                                          Page 21 of 33
P +61 7 5211 1003            A 37 Mary St, Noosaville Qld 4566   E [email protected]     recorconsulting.com

Page 26

                                                  Proposed Development Plans




                                                                                                 Page 22 of 33
P +61 7 5211 1003   A 37 Mary St, Noosaville Qld 4566     E [email protected]   recorconsulting.com

Page 27

                                                                                                                                                                                                  OP WORKS
THE BELVEDERE ON PEARL                                                                                                                                                                                    ISSUE


5 PEARL STREET, COOROY QLD 4562
CIVIL WORKS


 NOTE:                                                                    6.   THE CONTRACTOR IS TO CHECK THROUGH LOCATING, POTHOLING AND
                                                                               SURVEY ALL CRITICAL CONNECTION POINTS FOR ALL CIVIL WORKS SHOWN
 THE FOLLOWING INSPECTIONS MUST BE COMPLETED BY RECOR ENGINEERS                ON THE DRAWINGS INCLUDING ANY POTENTIAL EXISTING SERVICES
 BEFORE                                                                        CLASHES PRIOR TO COMMENCEMENT OF CIVIL WORKS. CONTRACTOR TO
 ENGINEERING CERTIFICATION WILL BE ISSUED. THE CONTRACTOR IS TO PROVIDE        IMMEDIATELY REPORT ANY DISCREPANCIES TO RECOR AND AWAIT FORMAL
 A                                                                             DIRECTION PRIOR TO COMMENCING CIVIL WORKS.

 MINIMUM OF 72 HOURS NOTICE TO RECOR FOR REQUIRED INSPECTIONS. SHOULD     7.   ON COMPLETION OF SERVICES INSTALLATION, ALL DISTURBED AREAS SHALL
 THE                                                                           BE RESTORED TO ORIGINAL LEVEL, INCLUDING KERBS, FOOTPATHS,
                                                                               CONCRETE AREAS, GRAVEL AREAS, GRASSED AREAS AND ROAD
 CONTRACTOR FAIL TO REQUEST AN INSPECTION, THE CONTRACTOR WILL BE              PAVEMENTS.
 RESPONSIBLE FOR ALL COSTS TO ALLOW FOR THE WORKS TO BE INSPECTED TO      8.   CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY DAMAGE TO
 THE                                                                           AUTHORITY/COUNCIL'S INFRASTRUCTURE. SUCH REPAIR OR
 SATISFACTION OF RECOR. ANY INSPECTIONS THAT FAIL ARE TO BE                    REINSTATEMENT TO BE CARRIED OUT IMMEDIATELY TO THE SATISFACTION
 RE-INSPECTED WITH                                                             OF INFRASTRUCTURE OWNER/MANAGER / AUTHORITY/COUNCIL.

 ALL REINSPECTION COSTS TO BE PAID BY THE CONTRACTOR.                     9.   CONTRACTOR TO UNDERTAKE ALL WORKS IN ACCORDANCE WITH ALL
                                                                               WORKPLACE HEALTH AND SAFETY REQUIREMENTS.
 a.   PRESTART
                                                                          10. WHERE ANY EXCAVATION OR CONSTRUCTION WORKS ARE TO BE IN CLOSE                         SITE BOUNDARY
 b.   EARTHWORKS - FINAL STRIPPING OF TOPSOIL, INSTALLATION OF SEDIMENT       PROXIMITY TO NEIGHBOURING LOT BOUNDARIES OR INFRASTRUCTURE,
      AND EROSION CONTROL MEASURES UNSUITABLE GROUND                          CONTRACTOR TO ALLOW IN SCOPE OF WORKS TO PROVIDE ALL MEASURES
 c.   SIDE AND CUT OFF DRAINS                                                 NECESSARY TO ENSURE THE INTEGRITY OF EXISTING BOUNDARIES AND
                                                                              INFRASTRUCTURE. THIS MAY INCLUDE THE USE OF LOW VIBRATION
 d.   STORMWATER PIPE LAID ON BEDDING PRIOR TO BACKFILL                       EQUIPMENT, TRENCH SHORING ETC AS REQUIRED.
 e.   STORMWATER TRENCH BACKFILLED PRIOR TO PAVEMENT PLACEMENT            11. PRIOR TO THE CONTRACTOR COMMENCING ANY WORKS DETAILED ON
 f.   STORMWATER STRUCTURE BASE SLABS                                         THESE DRAWINGS, THE CONTRACTOR IS TO NOTIFY RECOR AND RECEIVE
                                                                              WRITTEN CONFIRMATION THAT WORKS CAN COMMENCE.
 g.   SEWER RETICULATION
                                                                          12. CONTRACTOR TO PROVIDE AS CONSTRUCTED DRAWINGS FOR ALL
 h.   WATER RETICULATION                                                      CONSTRUCTED WORKS IN ACCORDANCE WITH LOCAL GOVERNMENT
 i.   PAVEMENT SUBGRADE                                                       REQUIREMENTS. UNLESS OTHERWISE ADVISED BY RECOR CONTRACTOR TO
                                                                              NOTE COUNCILS ADAC REQUIREMENTS.
 j.   PAVEMENT REINFORCING
                                                                          13. CONTRACTOR TO UNDERTAKE ALL WORKS IN ACCORDANCE WITH RELEVANT
 k.   PAVEMENT PRIOR TO SEALING (PRESEAL)                                     APPROVALS.
 l.   RETAINING WALL FOOTING REINFORCING                                  14. CONTRACTOR TO ALLOW TO LIASE/CO-ORDINATE WITH ELECTRICAL,
 m.   RETAINING WALL BLOCKWORK PRIOR TO CORE FILL                             LANDSCAPE AND OTHER SERVICE CONTRACTORS THROUGHOUT CIVIL
                                                                              CONSTRUCTION.
 n.   STEEL REINFORCEMENT OF CONCRETE STRUCTURES
                                                                          15. CONTRACTOR TO ORGANISE ALL DEMOLITION PERMITS PRIOR DEMOLITION
 o.   PRACTICAL COMPLETION                                                    WORKS COMMENCING ON SITE.
 p.   ON MAINTENANCE                                                      16. CONTRACTOR TO ALLOW TO DEMOLISH ALL EXISTING STRUCTURES, ROADS
 q.   OFF MAINTENANCE                                                         AND SERVICES WITHIN LIMIT OF WORKS AND REMOVE FROM SITE U.N.O.

 r.   ANY OTHER INSPECTION AS SPECIFIED BY LOCAL COUNCIL (REFER           17. CONTRACTOR TO UNDERTAKE DILAPIDATION REPORT FOR ADJOINING
      DEVELOPMENT APPROVAL)                                                   PROPERTIES AND COUNCIL ROADS AND VERGES PRIOR TO COMMENCEMENT
                                                                              OF ANY WORKS ON SITE.
 s.   ANY OTHER INSPECTION AS REQUIRED BY UNITY WATER AND WHERE
                                                                          18. CONTRACTOR TO CLEAR AND GRUB ALL VEGETATION ON SITE AS IDENTIFIED
      RELEVANT TO THEIR CERTIFICATION SCHEME
                                                                              IN THE APPROVED VEGETATION MANAGEMENT PLAN. CONTRACTOR TO
                                                                                                                                                   LOCALITY PLAN
                                                                              ENSURE ALL TREE ROOTS AND STUMPS ARE COMPLETELY REMOVED AND            NOT TO SCALE
 GENERAL NOTES                                                                BACKFILLED TO LEVEL 1 SUPERVISION. CONTRACTOR TO ALLOW TO MULCH
                                                                              ALL CLEARED VEGETATION AND STOCKPILE ON SITE OR REMOVE FROM SITE
 1.   ALL DIMENSIONS SHOWN ARE IN METERS UNLESS OTHERWISE SHOWN.              AS DIRECTED.
 2.   ALL SETOUT ON SITE IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.    19. DRAWINGS TO BE READ IN CONJUNCTION WITH THE FOLLOWING
      CONTRACTOR TO ALLOW FOR ALL MEANS NECESSARY TO ACCURATELY               CONSULTANTS/CONTRACTORS DRAWINGS:                                                                     02/07/21   ISSUED FOR OPW                -    MVP
      SETOUT THE WORKS.                                                                                                                                                              DATE              REVISION             MARK CHK
                                                                                     SURVEYOR:     SKYLINE SURVEYORS
 3.   ALL WORKS TO BE CONSTRUCTED IN ACCORDANCE WITH PROJECT                                                                                                                        PROJECT ENGINEER
                                                                                     ARCHITECT:    ZEST BUILDING GROUP
      SPECIFICATIONS AND WHERE FURTHER DETAILS ARE REQUIRED THE
      CONTRACTOR SHALL REFER TO NOOSA SHIRE COUNCIL DEVELOPMENT                      HYDRAULICS:   TBC
      GUIDELINES, LOCAL WATER AUTHORITY GUIDELINES, ASSOCIATED
      STANDARD DRAWINGS AND SPECIFICATIONS U.N.O.                                    STRUCTURAL:   RECOR

 4.   SHOULD ANY OF THE CONSTRUCTED WORKS BE CONSTRUCTED OUTSIDE OF                  LANDSCAPE:    ZEST BUILDING DESIGN
      THE TOLERANCES SPECIFIED WITHIN THE PROJECT SPECIFICATION AND       20. CONTRACTOR TO PREPARE AND HAVE APPROVED BY RELEVANT AUTHORITY:
      LOCAL AUTHORITY REQUIREMENTS, THE CONTRACTOR WILL RECTIFY AT            ROAD OPENING PERMIT AND TRAFFIC MANAGEMENT PLAN FOR ALL WORKS
      THEIR COST INCLUSIVE OF ANY ADDITIONAL COSTS INCURRED BY RECOR.         WITHIN COUNCIL ROAD RESERVES. CONTRACTOR TO ALLOW FOR ALL COSTS                                        E [email protected]
                                                                              ASSOCIATED WITH IMPLEMENTATION OF THE TMP.
 5.   EXISTING SERVICES HAVE BEEN PLOTTED FROM SUPPLIED DATA AND AS                                                                                                                  A 37 MARY ST NOOSAVILLE, QLD
      SUCH THEIR ACCURACY CANNOT BE GUARANTEED. NO RESPONSIBILITY IS      21. ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE FOLLOWING                                             P +61 7 5211 1003
      TAKEN BY RECOR OR THE PRINCIPAL FOR THE ACCURACY AND                    LOCAL AUTHORITY APPROVALS: T.B.A
      COMPLETENESS OF THIS INFORMATION. IT IS THE RESPONSIBILITY OF THE                                                                                                             CLIENT
      CONTRACTOR TO ACCURATELY ESTABLISH THE LOCATION AND LEVEL OF        22. CONTRACTOR TO UNDERTAKE ALL WORKS IN ACCORDANCE WITH OPW
      ALL EXISTING SERVICES PRIOR THE COMMENCEMENT OF ANY WORKS. ANY          APPROVALS BY COUNCIL.                                                                                   VIVIDO
      DISCREPANCIES SHALL BE REPORTED TO THE SUPERINTENDENT.              23. NO WORKS ARE TO BE UNDERTAKEN ON LAND OUTSIDE OF THE SITE                                             PROJECT
      CONTRACTOR TO LOCATE AND PROTECT SERVICES AS REQUIRED DURING            BOUNDARY WITHOUT FORMAL APPROVAL BY THE OWNER/CUSTODIAN OF
      PROPOSED WORKS.                                                         THAT LAND INCLUDING BUT NOT LIMITED TO PRIVATE PROPERTY, ROAD                                           THE BELVEDERE ON PEARL
                                                                              RESERVE, PARKS/OPENSPACE, EASEMENTS.
                                                                                                                                                                                      5 PEARL STREET, COOROY
                                                                          24. THE CONTRACTOR SHALL HAVE AN APPROVED SET OF CONSTRUCTION
                                                                              DRAWINGS AND APPROVALS ON SITE AT ALL TIMES.
                                                                                                                                                                                    TITLE
                                                                          25. ALL WATER AND SEWER RETICULATION WORKS TO BE CONSTRUCTED IN
                                                                              ACCORDANCE WITH THE SEQ WATER SUPPLY AND SEWERAGE DESIGN AND                                            COVER SHEET AND
                                                                              CONSTRUCTION CODE (2013).
                                                                                                                                                                                      LOCALITY PLAN

                                                                                                                                                                                    PROJECT NO.      DRAWING NO.   STATUS

                                                                                                                                                                                       21011           C01         OPW
                                                                                                                                                                                    DRAWN            DESIGNED      SCALE         ISSUE

                                                                                                                                                                                        MVP            BRP           1:200        A

Page 28

                                                                                                                                                                                                                                         OP WORKS
                                                                                                                                                                                                                                                  ISSUE
NOTE:
1.   FOR GENERAL NOTES REFER DWG No. C01, WHICH IS TO BE REQUESTED AND VIEWED PRIOR
     TO COMMENCEMENT OF CONSTRUCTION IF NOT SUPPLIED.                                                                                                                                                                                    LEGEND
2.   THE CONTRACTOR WILL MAKE HIMSELF FULLY AWARE OF THE EXISTING FEATURES OF THIS                                                                                                                                                                FIRE HYDRANT
     SITE AND ENSURE ANY ADDITIONAL WORKS NOT SHOWN ON THIS PLAN ARE INCLUDED IN THE                                                                                                                                                              SIGN
     CONTRACT.                                                                                                                                                                                                                                    PALM TREE
                                                                                                                                                                                                                                                  TREE
3.   CONTRACTOR TO LOCATE AND PROTECT ALL EXISTING SERVICES ON SITE PRIOR TO
                                                                                                                                                                                                                                                  WATER METER
     COMMENCEMENT OF WORKS.
                                                                                                                                                                                                                                                  SURVEY STN
4.   CONTRACTOR TO ORGANISE ALL DEMOLITION PERMITS PRIOR TO ANY DEMOLITION WORKS                                                                                                                                                                  PERMANENT SURVEY MARK
     COMMENCING ON SITE.                                                                                                                                                                                                                          POWER POLE
5.   SERVICES ON NEIGHBOURS DEVELOPMENTS SHOWN AS EXISTING AS ASSUMED WILL BE                                                                                                                                                                     STREET LIGHT
                                                                                                                                                                                                                                                  ELECTRICITY MARKER
     CONSTRUCTED PRIOR TO COMMENCEMENT OF WORKS.
                                                                                                                                                                                                                                                  ELECTRICITY PILLAR
6.   ALL VEGETATION WITHIN THE LIMIT OF WORKS TO BE CLEARED, MULCHED AND REMOVED                                                                                                                                                                  TELECOMMUNICATIONS MARKER
     FROM SITE IN ACCORDANCE WITH APPROVED VEGETATION CLEARING PLAN (BY OTHERS) OR                                                                                                                                                                GAS LINE MARKER
     IF SCHEDULED STOCKPILE FOR USE BY LANDSCAPER. REFER VEGETATION CLEARING PERMIT                                                                                                                                                               WATER LINE MARKER
     FOR DETAILS.                                                                             EXISTING POWER CONNECTION TO BE                                                                                                                     STORMWATER M/H
                                                                                              REMOVED. REMOVAL AND ANY                                                                                                                            WATER VALVE
7.   CONTRACTOR TO LOCATE ALL EXISTING UTILITIES ON SITE AND MAKE SUITABLE                                                                                                                                                                        SEWER MANHOLE
                                                                                              REPLACEMENT REQUIRED TO BE ARRANGED
     ARRANGEMENTS TO HAVE DISCONNECTED.                                                                                                                                                                                                           TRAFFIC LIGHTS
                                                                                              BY SITE SUPERINTEND
8.   PRIOR TO THE CONTRACTOR COMMENCING ANY WORKS DETAILED ON THIS DRAWING, THE                                                                                                                                                                   TRAFFIC SIGNAL CONTROL BOX
     CONTRACTOR IS TO NOTIFY RECOR AND RECEIVE WRITTEN CONFIRMATION THAT WORKS                                                                                                                                                                    TELSTRA PIT
     CAN COMMENCE.                                                                                                                                                                                                                                STORM WATER
                                                                                                                                      EXISTING BUILDING TO
9.   CONTRACTOR TO UNDERTAKE DILAPIDATION REPORT FOR ADJOINING PROPERTIES AND                                                                                                                                                                     SEWER MAIN
                                                                                                                                      BE DEMOLISHED AND
     COUNCIL ROADS AND VERGES PRIOR TO COMMENCEMENT OF ANY WORKS ON SITE.                                                             REMOVED OFFSITE                                                                                             GAS MAIN
10. CONTRACTOR TO ALLOW TO DEMOLISH ALL EXISTING STRUCTURES, ROADS AND SERVICES                                                                                                                                                                   WATER MAIN
    WITHIN LIMIT OF WORKS AND REMOVE FROM SITE U.N.O.
                                                                                                                                                                                                                                                  COMMUNICATION CABLES
                                                                                                                                                                                                                                                  TELSTRA CONDUIT
                                                                                                                                                                                                                                                  ELECTRICITY
             NOTE:                                                                                                                                                                                                                                SITE BOUNDARY
             EXCEPT WHERE NOTED ON PLAN AND ASSOCIATED DESIGN
             DRAWINGS, ALL IN-GROUND SERVICES WITHIN THE PROPERTY
             BOUNDARY INCLUDING BUT NOT LIMITED TO: STORMWATER
             DRAINAGE,    SEWERAGE,   WATER,    GAS,  ELECTRICAL  AND
             COMMUNICATIONS TO BE SAFELY BE DISCONNECTED, REMOVED
             FROM SITE AND CAPPED OFF AT SITE BOUNDARY. CONTRACTOR TO                                                               EXISTING BUILDING TO
             ARRANGE ALL NECESSARY APPLICATIONS AND PERMITS WITH THE                               EXISTING DRIVEWAY
                                                                                                   TO BE DEMOLISHED                 BE DEMOLISHED AND
             RELEVANT    AUTHORITIES.  SERVICES   TO   BE CAPPED IN                                                                 REMOVED OFFSITE
             ACCORDANCE      WITH     RELEVANT     SERVICE   PROVIDER
             SPECIFICATIONS AND STANDARD DETAILS




                                                                                       EXISTING DRIVEWAY TO
                                                                                       BE DEMOLISHED AND                                                     EXISTING BUILDING TO
                                                                                       AREA MADE GOOD                                                        BE DEMOLISHED AND      EXISTING WATER TANLK
                                                                                                                                                             REMOVED OFFSITE        TO BE DEMOLISHED
                                                                                                                                                                                    AND
                                                                                                                                                                                    REMOVED OFFSITE




                                                                                                                                                                                     EXISTING POWER CONNECTION TO BE
                                                                                                                                                                                     REMOVED. REMOVAL AND ANY
                                                                                                                                                                                     REPLACEMENT REQUIRED TO BE ARRANGED
                                                                                                                                                                                     BY SITE SUPERINTENDENT




                                                                                                                                                                                                                           02/07/21   ISSUED FOR OPW                      -    MVP
                                                                                                                                                                                                                            DATE              REVISION                   MARK CHK
                                                                                                                               EXISTING DRIVEWAY TO BE                                                                     PROJECT ENGINEER
                                                                                                                               DEMOLISHED AND REPLACED
                                                                                                                               WITH NEW FULL SITE
                                                                                                                               FRONTAGE. REFER TO DWG
                                                                                                                               C30 FOR DETAILS




                                                                                                                                                                                                                            E [email protected]
                                                                                                                                                                                                                            A 37 MARY ST NOOSAVILLE, QLD
                                                                                                                                                                                                                            P +61 7 5211 1003
                                                                                                                                                                                                                           CLIENT

                                                                                                                                                                                                                             VIVIDO
                                                                                                                                                                                                                           PROJECT

                                                                                                                                                                                                                              THE BELVEDERE ON PEARL
                                                                                                                                                                                                                              5 PEARL STREET, COOROY
                                                                                                                                                                                                                           TITLE

                                                                                                                                                                                                                             EXISTING FEATURES
                                                                                                                                                                                                                             LAYOUT PLAN

                                                                                                                                                                                                                           PROJECT NO.      DRAWING NO.         STATUS

                                                                                                                                                                                                                              21011         C02                 OPW
                                                                                                                                                                                                                           DRAWN            DESIGNED            SCALE         ISSUE

                                                                                                                                                                                                                               MVP            BRP                 1:200        A

Page 29

SEDIMENT RELEASE GUIDELINES
1.   ALL RELEASES OF STORMWATER CAPTURED ONSITE, UNLESS OTHERWISE
                                                                          FIELD INLET
                                                                          15. FOR FIELD INLET STANDARD DETAIL AND SPECIFICATION REFER TO
                                                                                                                                                                       OP WORKS
     NOTED IN THIS STANDARD, MUST NOT EXCEED THE FOLLOWING LIMITS:
                                                                              INTERNATIONAL EROSION CONTROL ASSOCIATION AUSTRALASIA (IECA) BEST                                 ISSUE
                                                                              PRACTICES STANDARD DRAWING ESC-02 GRATED STORMWATER (FIELD)
  1.1.   50mg/L OF TOTAL SUSPENDED SOLIDS (TSS) AS A MAXIMUM
                                                                              INLET SEDIMENT TRAP.
         CONCENTRATION;
  1.2.   TURBIDITY (NTU) VALUE LESS THAN 10% ABOVE BACKGROUND;
                                                                          OPERATION AND MAINTENANCE
  1.3.   pH VALUE MUST BE IN THE RANGE 6.5 TO 8.5 EXCEPT WHERE, AND TO
         THE EXTENT THAT, THE NATURAL RECEIVING WATERS LIE OUTSIDE THIS
                                                                          16. IN ACCORDANCE WITH NC ESC GUIDELINES, ALL ESC MEASURES SHALL BE                             LEGEND
                                                                              INSPECTED:
         RANGE.
                                                                              · AT LEAST DAILY (WHEN WORK IS OCCURRING ON SITE) OR WEEKLY (WHEN
2. THE CONCENTRATION OF TSS RELEASED BY DEWATERING MAY ONLY                                                                                                                       CONSTRUCTION ENTRY/EXIT
                                                                                 WORK IS NOT OCCURRING ON SITE)
     EXCEED 50mg/L WHERE IT CAN BE DEMONSTRATED AND SUPPORTED                                                                                                                     SHAKEDOWN AREA
                                                                              · WITHIN 24 HOURS OF EXPECTED RAIN; AND
     THROUGH DOCUMENTATION THAT:
                                                                              · WITHIN 18 HOURS OF A RAINFALL EVENT (I.E. AN EVENT OF SUFFICIENT
  2.1.   FURTHER SIGNIFICANT RAINFALL IS FORECAST TO OCCUR BEFORE THE                                                                                                             SEDIMENT FENCE
                                                                                 INTENSITY AND DURATION TO MOBILISE SEDIMENT ON SITE).
         TSS CONCENTRATION IS LIKELY TO BE REDUCED TO 50mg/L;                                                                                                                     (INDICATIVE LOCATION)
                                                                          17. IN ACCORDANCE WITH NC ESC GUIDELINES, MAINTENANCE OF ESC
  2.2.   RELEASING A HIGHER CONCENTRATION OF TOTAL SUSPENDED SOLIDS
                                                                              MEASURES SHALL OCCUR IN ACCORDANCE WITH THE FOLLOWING TABLE:
         WILL RESULT IN A BETTER ENVIRONMENTAL OUTCOME BY PROVIDING
         STORAGE FOR THE CAPTURE AND TREATMENT OF RUN-OFF FROM THE
         IMMINENT RAINFALL AND RUN-OFF.                                                           MAINTENANCE SCHEDULE
  2.3.   ALL REASONABLE AND PRACTICABLE STEPS HAVE BEEN TAKEN TO               ESC MEASURES           MAINTENANCE TRIGGER
                                                                                                                              TIMEFRAME FOR COMPLETION
                                                                                                                                   OF MAINTENANCE
         TREAT THE WATER WITHIN BEST-PRACTICE TIME FRAMES;
  2.4.   FLOCCULENT HAS BEEN APPROPRIATELY APPLIED AND THE
         CONCENTRATION OF TSS IN THE CAPTURED WATER HAS ALREADY
         SIGNIFICANTLY DECREASED.
3. FOR ALL OTHER STORMWATER RELEASES, FLOWS AND DISCHARGES FROM
     THE SITE, THE RELEASE LIMIT PRESCRIBED IN (1a) ABOVE MUST NOT BE     REPORTING
     EXCEEDED UNLESS THE DEVELOPMENT IS IN FULL COMPLIANCE WITH THIS      18. CONTRACTOR IS TO PROVIDE AN UPDATED PROGRAM OF ESC MAINTENANCE
     STANDARD.                                                                AND CONTROL OF ALL STAGES OF WORK FOR APPROVAL BY THE
                                                                              SUPERINTENDENT.
NOTE:     IT IS RECOMMENDED THAT A SITE-SPECIFIC RELATIONSHIP BETWEEN
TURBIDITY AND SUSPENDED SOLIDS IS DETERMINED FOR EACH SEDIMENT BASIN.
ONCE A CORRELATION BETWEEN SUSPENDED SOLIDS AND TURBIDITY HAS BEEN        NOTES
ESTABLISHED FOR A SEDIMENT BASIN, TESTING STORMWATER FOR COMPLIANCE
WITH RELEASE LIMITS, PRIOR TO RELEASE, CAN BE DONE ON SITE WITH A         1.   CONTRACTOR TO PROVIDE FINAL ESC DESIGN TO SUIT
TURBIDITY TUBE OR CALIBRATED TURBIDITY METER. THIS HAS THE ADVANTAGE           PROPOSED CONSTRUCTION METHODOLOGY
OF PROVIDING IMMEDIATE ASSESSMENT TO JUSTIFY A RELEASE RATHER THAN        2.   ALL DISTURBED SURFACES TO BE LANDSCAPED IN
WAITING FOR LABORATORY RESULTS TO CONFIRM CONCENTRATION LEVELS                 ACCORDANCE WITH LANDSCAPE CONSULTANTS DRAWINGS
AND COMPLIANCE. NOTE THAT     POST-RELEASE TSS VALIDATION IS              3.   CONCRETE WASHOUT TO NOT BE UNDERTAKEN ON SITE, OR
APPROPRIATE TO DEMONSTRATE THAT THE NTU/TSS CORRELATION IS BEING               TO BE UNDERTAKEN ON A DESIGNATED LOCATION.
MAINTAINED.                                                                    CONTRACTOR TO ESTABLISH CONCRETE WASHOUT AS PER
                                                                               IECA GUIDELINES.
SEDIMENT CONTROL
1.   ALL SEDIMENT AND EROSION CONTROL MEASURES TO BE IN ACCORDANCE
     WITH INTERNATIONAL EROSION CONTROL ASSOCIATION (IECA) AUSTRALIA
     GUIDELINES AND THE SPECIFICATIONS.
2.   SEDIMENT AND EROSION CONTROL DETAILS SHOWN ARE MINIMUM
     REQUIREMENTS. IT IS THE CONTRACTORS RESPONSIBILITY TO INSTALL
     ADDITIONAL CONTROL MEASURES AS DEEMED NECESSARY THROUGHOUT
     CONSTRUCTION.
3.   THE CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL SEDIMENT CONTROL
     DEVICES IN A FUNCTIONAL ORDER AND REPLACE ALL BLOCKED SEDIMENT
     DEVICES AS REQUIRED UNTIL SUCCESSFUL OFF MAINTENANCE OF WORKS.
4.   CONSTRUCTION OF ALL SEDIMENT MANAGEMENT DEVICES TO THE
     SATISFACTION OF THE SUPERINTENDENT. SHALL BE COMPLETED AND
     EFFECTIVE PRIOR TO:
     a. STRIPPING OF TOPSOIL AND GRASS.
     b. BULK EARTHWORKS TO THE SITE.
     c. SERVICES INSTALLATION.
     d. PAVEMENT CONSTRUCTION
5.   ALL SEDIMENT MANAGEMENT MEASURES ARE TO REMAIN IN PLACE UNTIL
     INSTRUCTION IS RECEIVED IN WRITING FROM THE SUPERINTENDENT TO
     REMOVE ALL OR PART OF THE SILT CONTROL APPLICATIONS.
6.   THE BULK EARTHWORKS AND SEDIMENT CONTROL LAYOUT PLAN SHALL BE
     READ IN CONJUNCTION WITH THE APPROVED DRAWINGS.
7.   PRIOR TO COMMENCEMENT OF CONSTRUCTION APPROVAL IS TO BE
     OBTAINED FROM THE SUPERINTENDENT FOR THE LOCATION OF THE SITE
     ACCESS POINT AND WASH DOWN AREA WHICH ARE TO BE MAINTAINED
     THROUGHOUT THE CONSTRUCTION PERIOD.
8.   IF SEDIMENT AND EROSION CONTROL DEVICES HAVE BEEN FOUND TO BE
     DIFFERENT OR FAILED IN SERVICE, CORRECTIVE ACTION IS TO BE                  SEDIMENT AND EROSION CONTROL:
     UNDERTAKEN IMMEDIATELY WHICH MAY INCLUDE AMENDMENTS' ADDITIONS              CONTRACTOR TO ALLOW FOR PROVISION OF ALL
     TO THE ORIGINAL APPROVED EROSION CONTROL PLANS. SUCH                        REQUIRED SEDIMENT AND EROSION CONTROL
     AMENDMENTS ARE TO BE APPROVED BY SUPERINTENDENT, IF DEEMED                  DEVICES IN ACCORDANCE WITH IECA AND NOOSA
     NECESSARY AND RELEVANT.                                                     COUNCIL POLICIES AND GUIDELINES

9.   OVERALL
     a. TEMPORARY DRAINAGE CONTROL FLOWS SHOULD BE DIVERTED
        AROUND THE WORK SITE WHERE POSSIBLE.
     b. ALL DRAINAGE, EROSION AND SEDIMENT CONTROLS TO BE INSTALLED
        AND BE OPERATIONAL BEFORE COMMENCING UP-SLOPE EARTHWORKS.
     c. IN AREAS WHERE RUNOFF TURBIDITY IS TO BE CONTROLLED, EXPOSED
        SURFACES TO BE EITHER MULCHED, COVERED WITH EROSION CONTROL
        BLANKETS OR TURFED IF EARTHWORKS ARE EXPECTED TO BE DELAYED
        FOR MORE THAN 14 DAYS.

SEDIMENT FENCE                                                                                                                                           02/07/21   ISSUED FOR OPW                        -    MVP
10. FOR SEDIMENT FENCE STANDARD DETAIL AND SPECIFICATION REFER TO
                                                                                                                                                          DATE              REVISION                MARK CHK
    INTERNATIONAL EROSION CONTROL ASSOCIATION AUSTRALASIA (IECA) BEST
    PRACTICES STANDARD DRAWINGS SF-01 AND SF-02 SEDIMENT FENCE.                                                                                          PROJECT ENGINEER

TEMPORARY CONSTRUCTION ENTRY/EXIT
11. FOR CONSTRUCTION ENTRY / EXIT STANDARD DETAIL AND SPECIFICATION
    REFER TO INTERNATIONAL EROSION CONTROL ASSOCIATION AUSTRALASIA
    (IECA) BEST PRACTICES STANDARD DRAWINGS EXIT-01 AND EXIT-02
    CONSTRUCTION EXIT - ROCK PAD (CONSTRUCTION SITES ONLY), EXIT-03 -
    ROCK PADS FOR BUILDING SITES AND EXIT-04 AND EXIT-05 CONSTRUCTION
    EXIT - VIBRATION GRID.

KERB INLET
12. FOR KERB INLET STANDARD DETAIL AND SPECIFICATION REFER TO
                                                                                                                                                          E [email protected]
    INTERNATIONAL EROSION CONTROL ASSOCIATION AUSTRALASIA (IECA) BEST                                                                                     A 37 MARY ST NOOSAVILLE, QLD
    PRACTICES STANDARD DRAWING ESC-03 KERB INLET SEDIMENT TRAPS
                                                                                                                                                          P +61 7 5211 1003
CHECK DAMS
13. FOR CHECK DAM STANDARD DETAIL AND SPECIFICATION REFER TO                                                                                             CLIENT
    INTERNATIONAL EROSION CONTROL ASSOCIATION AUSTRALASIA (IECA) BEST
    PRACTICES STANDARD DRAWING RCD-01 CHECK DAMS.                                                                                                          VIVIDO
REVEGETATION                                                                                                                                             PROJECT
14. FOR REVEGETATION STANDARD SPECIFICATION REFER TO INTERNATIONAL
    EROSION CONTROL ASSOCIATION AUSTRALASIA (IECA) BEST PRACTICES                                                                                           THE BELVEDERE ON PEARL
    STANDARD DRAWING R-01 REVEGETATION GENERAL.
                                                                                                                                                            5 PEARL STREET, COOROY
                                                                                                                                                         TITLE

                                                                                                                                                           EROSION AND SEDIMENT
                                                                                                                                                           CONTROL PLAN

                                                                                                                                                         PROJECT NO.      DRAWING NO.      STATUS

                                                                                                                                                            21011         C10               OPW
                                                                                                                                                         DRAWN            DESIGNED          SCALE             ISSUE

                                                                                                                                                             MVP            BRP                1:200           A

Page 30

EARTHWORKS NOTES                                                                        OP WORKS
1.  FOR GENERAL NOTES REFER DWG C01, WHICH IS TO BE REQUESTED AND                                ISSUE
    VIEWED PRIOR TO COMMENCEMENT OF CONSTRUCTION IF NOT SUPPLIED.
2. GRASS AND TOPSOIL SHALL BE STRIPPED TO A MINIMUM DEPTH OF 100MM
    OVER THE EXTENT OF THE WORKS UNLESS DIRECTED OTHERWISE AND
    STOCKPILED FOR FUTURE USE AS NON-STRUCTURAL FILL IF REQUIRED, OR
    REMOVE FROM SITE.
                                                                                           LEGEND
3. WHERE SITE TOPSOIL IS TO BE RESPREAD ON SITE, CONTRACTOR TO
    ALLOW TO SCREEN THE TOPSOIL OF ALL UNSUITABLE AND OVERSIZED                                  PROPOSED 1m MAX. HEIGHT
    MATERIAL. ALL UNSUITABLE MATERIAL GENERATED FROM SCREENING TO BE                             RETAINING WALL
    REMOVED FROM SITE AT CONTRACTORS EXPENSE.
                                                                                                 FINISHED SURFACE LEVEL
4. CONTRACTOR TO ALLOW FOR ALL COSTS ASSOCIATED WITH ROCK
    EXCAVATION WITHIN CONTRACT RATES.                                                            PROPOSED CUT
5. COMPACT THE EXPOSED SUBGRADE OR LOOSE TOP LEVEL MATERIAL TO A                                 EARTHWORKS
    MINIMUM 98% STANDARD MAXIMUM DRY DENSITY TO AS1289 5.1.1. ANY 'SOFT
    SPOTS' IDENTIFIED BY THE PROOF ROLLING SHALL BE REMOVED AND                                  PROPOSED FILL EARTHWORKS
    REPLACED WITH A COMPACTED IMPORTED GENERAL FILL MATERIAL TO THE
    ABOVE COMPACTION REQUIREMENTS.
6. IMPORTED GENERAL FILL MATERIAL SHALL BE SUPPLIED AND COMPACTED
    WHERE NECESSARY TO OBTAIN SUBGRADE/PLATFORM LEVEL. IMPORTED
    GENERAL FILL MATERIAL SHALL BE CLEAN GRADED MATERIAL FREE OF
    ORGANIC MATTER AND STONES GREATER THAN 150mm AND CAPABLE OF
    BEING COMPACTED INTO COHERENT FILLING TO THE SPECIFIED STANDARD.
    THE MATERIAL SHALL HAVE A LINEAR SHRINKAGE NOT GREATER THAN 8%
    AND A MINIMUM C.B.R. OF 10%.
7. ANY PROPOSED RETAINING WALL WORKS MUST BE WHOLLY WITHIN THE
    PROPERTY BOUNDARY OF THE SUBJECT SITE, INCLUDING REAR OF
    RETAINING WALL DRAINAGE INFRASTRUCTURE FOR RETAINING WALLS IN
    CUT.
8. REFER ARCHITECT/LANDSCAPE ARCHITECT DRAWINGS FOR CONFIRMATION
    OF RETAINING WALL COLOUR AND FINISH.
9. ALL RETAINING WALL STRUCTURAL DESIGN AND CONSTRUCTION
    CERTIFICATION BY MANUFACTURER / INSTALLER.
10. ALL EARTHWORKS OPERATIONS SHALL BE CARRIED OUT WITH 'LEVEL 2' SOIL
    ENGINEERING SUPERVISION IN ACCORDANCE WITH APPENDIX B OF AS 3798.
    THE NOMINATED GEOTECHNICAL TESTING AUTHORITY SHALL PROVIDE
    CERTIFICATION THAT ALL GENERAL EARTHWORKS OPERATIONS HAVE BEEN
    CARRIED OUT IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS
    AND THE CONTROLLED FILL IS SUITABLE FOR PURPOSE WITH A MINIMUM
    150KPA BEARING CAPACITY UNDER THE PLATFORM/STRUCTURES.
11. ALL EARTHWORKS FILL AND EXCAVATED AREAS SHALL BE COMPACTED TO
    98% STANDARD MAXIMUM DRY DENSITY (AS 1289 5.1.1) IN LAYERS NOT
    EXCEEDING 150MM COMPACTED THICKNESS.
12. THE NOMINATED GEOTECHNICAL TESTING AUTHORITY SHALL PROVIDE
    CERTIFICATION THAT ALL GENERAL EARTHWORKS OPERATIONS HAVE BEEN
    CARRIED OUT IN ACCORDANCE WITH THE DRAWINGS.
13. CONTRACTOR TO UNDERTAKE ALL EARTHWORKS TESTING TO COMPLY WITH
    THE PROJECT SPECIFICATION AND LOCAL AUTHORITY REQUIREMENTS.
14. FINISHED SURFACES TO ALL DISTURBED AREAS ARE TO BE TREATED IN
    ACCORDANCE WITH LANDSCAPE DRAWINGS.
15. FINISHED EARTHWORKS SURFACES TO BE STABILISED
16. ALL EARTHWORKS TO BE CARRIED OUT AT +/- 2% OPTIMUM MOISTURE
    CONTENT.
17. ALL NEW WORKS TO MATCH NEATLY INTO EXISTING.
18. ALL WORKS TO BE CONSTRUCTED IN ACCORDANCE WITH APPROVED
    MANAGEMENT PLANS.
19. CONTRACTOR TO ENSURE SUITABLE EROSION CONTROL MEASURES ARE
    INSTALLED INCLUDING BUT NOT LIMITED TO SHAKE DOWNS, SILT FENCE ETC.
20. ADEQUATE SAFETY FENCING/BARRIERS TO BE APPLIED TO ALL BATTERS OR
    RETAINING WALLS (TEMPORARY OR PERMANENT) AS PER RELEVANT
    AUSTRALIAN STANDARDS AND LEGISLATION.
21. DUST CONTROL MEASURES ARE TO INCLUDE SPRAYING WATER ON
    UNPAVED ROADS, ACCESS TRACKS AND STOCKPILES AT A SUFFICIENT
    LEVEL TO SUPPRESS DUST GENERATION. ADDITIONALLY CONTRACTORS
    ARE TO COVER OR ENCLOSE STOCKPILES WHERE REASONABLY PRACTICAL
    TO RESTRICT DUST MOVEMENT.
22. PRIOR TO THE CONTRACTOR COMMENCING ANY WORKS DETAILED ON THIS
    DRAWING, THE CONTRACTOR IS TO NOTIFY RECOR AND RECEIVE WRITTEN
    CONFIRMATION THAT WORKS CAN COMMENCE.
23. ALL BATTERS TO BE KEYED/STEPPED INTO EXISTING MATERIAL AS DIRECTED
    BY GEOTECHNICAL ENGINEER. CONTRACTOR TO ALLOW FOR ALL
    KEYING/STEPPING AS REQUIRED.
24. ALL TEMPORARY AND FINAL BATTER SLOPES ARE TO BE INSPECTED AND
    APPROVED BY GEOTECHNICAL ENGINEER. CERTIFICATION OF LONG TERM
    STABILITY TO BE PROVIDED BY GEOTECHNICAL ENGINEER PRIOR TO
    PRACTICAL COMPLETION.
25. CONTRACTOR'S RPEQ GEOTECHNICAL ENGINEER IS TO CONFIRM THAT ALL
    CONSTRUCTED CUT/FILL BATTERS AND RETAINING STRUCTURES ON THE
    SITE HAVE ACHIEVED ADEQUATE STABILITY WITH A LONG-TERM FACTOR OF
    SAFETY GREATER THAN OR EQUAL TO 1.5 AGAINST GEOTECHNICAL
    FAILURES.
26. EARTHWORKS LEVELS SHOWN ARE FINISHED SURFACE LEVELS INCLUSIVE
    OF TOPSOIL LAYER. REFER TO STRUCTURAL ENGINEERING DRAWINGS FOR
    BUILDING SLAB THICKNESSES AND HYDRAULIC DRAWINGS FOR SUB-FLOOR
    DRAINAGE FOR DETERMINATION OF REQUIRED BULK EARTHWORKS
    SURFACE.
                                                                          02/07/21   ISSUED FOR OPW                  -     MVP
27. EARTHWORKS LEVELS SHOWN ARE FINISHED SURFACE LEVELS INCLUSIVE
    OF 100mm TOPSOIL LAYER.                                                DATE              REVISION              MARK CHK
28. FOR DETAILED GEOTECHNICAL INFORMATION, REFER GEOTECHNICAL             PROJECT ENGINEER
    INVESTIGATION REPORT. IT IS RECOMMENDED THAT THE GEOTECHNICAL
    CONSULTANT BE CONTACTED TO CONFIRM THE SOIL CONDITIONS PRIOR TO
    EARTHWORKS COMMENCING.
29. WHERE NOMINATED ON THE PROJECT DRAWINGS, PRELOADING IS TO
    OCCUR IN ACCORDANCE WITH THE PROJECT DRAWINGS, PROJECT
    SPECIFICATION AND GEOTECHNICAL REPORT. CONTRACTOR TO ALLOW FOR
    THE IMPORT AND REMOVAL OF ALL NECESSARY MATERIAL TO UNDERTAKE
    THE PRELOADING OPERATIONS. CONTRACTOR TO ALLOW TO INSTALL
    SETTLEMENT PLATES AT LOCATIONS NOMINATED BY THE GEOTECHNICAL
    ENGINEER AND ALLOW FOR WEEKLY MONITORING AND REPORTING BY
    SURVEY. PRELOAD IS NOT TO BE REMOVED UNTIL DIRECTED BY THE             E [email protected]
    SUPERINTENDENT.                                                        A 37 MARY ST NOOSAVILLE, QLD
30. REFER ARCHITECTURAL DRAWINGS FOR BUILDING SETOUT.
                                                                           P +61 7 5211 1003
                                                                          CLIENT

                                                                            VIVIDO
                                                                          PROJECT

                                                                             THE BELVEDERE ON PEARL
                                                                             5 PEARL STREET, COOROY
                                                                          TITLE

                                                                            SITE EARTHWORKS PLAN


                                                                          PROJECT NO.      DRAWING NO.    STATUS

                                                                             21011         C20            OPW
                                                                          DRAWN            DESIGNED       SCALE           ISSUE

                                                                              MVP            BRP             1:200         A

Page 31

ROADWORKS AND DRAINAGE NOTES                                                                                                                                                                                                                                                                                                                                                                        OP WORKS
                                                                                                                                                                                                                                                                                                                                                                                                            ISSUE
1.  REFER HYDRAULIC DRAWINGS FOR BUILDING DRAINAGE DETAILS.
2.  ALL ROADWORKS AND DRAINAGE (EXTERNAL TO SITE BOUNDARIES AND/OR COUNCIL OWNED DRAINAGE
    PIPES INTERNAL TO THE SITE BOUNDARIES) CONSTRUCTION AND TESTING TO BE IN ACCORDANCE WITH
    NOOSA SHIRE COUNCIL DEVELOPMENT GUIDELINES, DRAWINGS AND SPECIFICATIONS.
3. ALL DRAINAGE CONSTRUCTION (PRIVATELY OWNED DRAINAGE LINES INTERNAL TO THE SITE BOUNDARIES)                                                                                                                                                                                                                                                                                                        LEGEND
    CONSTRUCTED AND TESTED TO BE IN ACCORDANCE WITH RELEVANT AUSTRALIAN STANDARDS.
4. DRAINAGE PITS TO BE PROVIDED WITH Ø150 STUB FOR FUTURE HYDRAULIC CONNECTION TO BE MINIMUM
                                                                                                                                                                                                                                                                                                                                                                                                            DRAINAGE PIPE
    50mm ABOVE INVERT OF PIT.
5. ALL STORMWATER DRAINAGE PIPES INTERNAL TO SITE SHALL BE MINIMUM:                                                                                                                                                                                                                                                                                                                                         FIELD INLET PIT
  a) Ø225 PP BLACKMAX OR APPROVED EQUIVALENT.
  b) Ø450 TO Ø600 PP SN8 RUBBER RING JOINTED, BLACKMAX OR APPROVED EQUIVALENT.                                                                                                                                    PROVIDE 2X5,000L SLIMLINE                           600x600 GRATED                                                                                                                        JUNCTION PIT
6. ALL STORMWATER DRAINAGE PIPES EXTERNAL TO SITE SHALL BE Ø300 AND GREATER CLASS 2 OR 3 R.C.                                                                                                                     RAINWATER ATTENUATION TANKS AS                      INLET SL: 105.87
    RUBBER RING JOINTED                                                                                                                                                                                           PER DETAIL B. OVERFLOWS TO PIT                      CLASS B GRATED LID
                                                                                                                                                                                                                  LITTER BASKET.                                                                                                                                                                            ATTENUATION TANK
7. ALL STORMWATER PIPES ARE TO BE MANUFACTURED TO RELEVANT AUSTRALIAN STANDARDS INCLUDING
    BUT NOT LIMITED TO AS4058 AND AS1992.
8. STORMWATER DRAINAGE AND STRUCTURES HAVE BEEN DESIGNED FOR OPERATIONAL LOADS ONLY.                                                                                                                                                                                                                                                                                                            1
                                                                                                                                                                                                                                                                                                                                                                                                A           SW PIT ID
    CONTRACTOR TO CONSIDER CONSTRUCTION LOADINGS AND ENSURE NO EXCESSIVE LOADS ARE PLACED
                                                                                                                                                                                     PROVIDE 5,000L SLIMLINE RAINWATER                                           1
    ON STORMWATER DRAINAGE OR STRUCTURES.                                                                                                                                                                                                                        C
9. ALL PRECAST END STRUCTURES TO BE CONSTRUCTED WITH REINFORCED CONCRETE END WALL.                                                                                                   ATTENUATION TANK AS PER DETAIL B.
                                                                                                                                                                                                                                                                                                                                                                                                            BIORETENTION AREA
10. CONTRACTOR TO CONFIRM LOCATION AND LEVEL OF EXISTING STORMWATER DRAINAGE WHERE                                                                                                   OVERFLOWS DIRECTED TO BIOGARDEN
    CONNECTING ON TO EXISTING.                                                                                                                                                                                                                                                                                 300mm PP PIPE                 12.5m² BIORETENTION AREA.
11. CONTRACTOR TO NOTIFY THE SUPERINTENDENT OF ANY UNSUITABLE FOUNDING MATERIAL WITHIN                                                                                                                                                                                                                         USIL: 104.81                                                                                 EXISTING ROAD
                                                                                                                                                                                                                                                                                                                                             650MM FILTER MEDIA
    DRAINAGE TRENCH OR STORMWATER STRUCTURES AND AWAIT DIRECTION PRIOR TO LAYING OF PIPES.                                                                                                                                         600x600 GRATED                                  1080Ø JUNCTION PIT          DSIL: 104.72                  150MM EXTENDED DETENTION DEPTH
12. TRENCH BACKFILL UNDER PAVEMENT TO BE COMPACTED TO 100% STANDARD DRY DENSITY (AS1289 5.1.1)                                                                                                                                     INLET SL: 105.87                                MANHOLE COVER               LENGTH: 13.57m                                                                               PROPOSED 2.0m WIDE
                                                                                                                                                                                                                                                                                                                                             REFER TO DETAIL A.
    IN LAYERS NOT EXCEEDING 150mm OF CBR 15 MATERIAL OR APPROVED EQUIVALENT. TRENCH BACKFILL IN                                 12.5m² BIORETENTION AREA.                                                                          CLASS B GRATED LID                              SL: 105.83                  GRADE: 0.6%                                                                                  FOOTPATH
    ROADS TO BE MINIMUM CBR15 MATERIAL UP TO ROAD SUBGRADE LEVEL.                                                               400MM FILTER MEDIA                                                                                                                                 CLASS B GRATED LID
13. ALL STORMWATER GRATES/LIDS WITHIN TRAFFICABLE AREAS TO BE CLASS "D" IN ACCORDANCE WITH                                      100MM EXTENDED DETENTION DEPTH                                                                                                                                                                                                                                              PROPOSED TYPE 'A'
                                                                                                                                                                                                                                                                                                                                             EXISTING 225 SEWER UNDER
    AS3996.                                                                                                                     REFER TO DETAIL A.                                                                                                                                                                                                                                                          DRIVEWAY CROSSOVER
                                                                                                                                                                                                                                                                                                                                             APPROX IL 104.05
14. ALL GRATES AND LIDS SHALL SIT FLAT WITH ITS SURROUND AND NOT BE LOOSE OR MOVE UNDER WHEEL                                                                                                                                                                                                                                                CONTRACTOR TO CONFIRM DEPTH ONSITE                             VERGE TURFED AREA. REFER
    LOADS.                                                                                                                                                    1
                                                                                                                                                                                                                                                                                                                                                                                                            ARCHITECTS PLANS.
15. ALL STORMWATER STRUCTURES TO BE CONSTRUCTED IN ACCORDANCE WITH PROJECT SPECIFICATION,                                                                     A                                                                                                                                                                       4
    AND LOCAL AUTHORITY GUIDELINES AND SPECIFICATIONS. WHERE STRUCTURES EXCEED MAXIMUM                                                                                                                                                                                                                                                A      600x600 GRATED
    DEPTH AS IDENTIFIED WITHIN STANDARD DRAWINGS THE CONTRACTOR WILL ENSURE AN ADEQUATE                                                                                                                                                                                                                                                      INLET SL: 105.60
    STRUCTURAL DESIGN IS UNDERTAKEN FOR THE SUBJECT STRUCTURE TO BE CONSTRUCTED TO.                                                                                                                                                                                                                                                          CLASS B GRATED LID                                           DESIGN SPOT HEIGHT
16. CONTRACTOR TO ENSURE ALL MANHOLE STRUCTURES COMPLY WITH THE MAXIMUM DEPTH SPECIFIED IN                                                                                                                                                                                               3
    THE PROJECT SPECIFICATION OR LOCAL AUTHORITY FROM FINISHED SURFACE LEVEL TO UNDERSIDE OF                                                                                                                                                                 2                           A
                                                                                                                                                                                                                                                             A                                                                                  TURF BLOCK PARKING AREA TO
    ROOF SLAB. ANY NON CONFORMANCE IS TO BE RECTIFIED AT THE CONTRACTORS EXPENSE.                                                                                                                                                                                                                                                               ARCHITECTURAL SPECIFICATION                                 ASPHALT DRIVEWAY
17. ALL FOOTPATHS TO BE CONSTRUCTED IN ACCORDANCE WITH ARCHITECTURAL/LANDSCAPING DRAWINGS                                                                                                                                                                                                                                                                                                                   CONCRETE EDGED
    AND RELEVANT AUTHORITY STANDARD DRAWINGS AND SPECIFICATIONS. FOOTPATHS TO BE                                                                                                                                                                                                                                                                                                                            150mm COMPACTED ROADBASE
                                                                                                                                                                                                             CONTRACTOR TO LOCATE
    CONSTRUCTED WITH MAXIMUM 2.5% CROSSFALL. SHOULD CONSTRUCTED FOOTPATHS EXCEED 2.5%                                                                                                    225mm PP PIPE                                                225mm PP PIPE                                                                                                                                         30mm AC14 WEARING COURSE
                                                                                                                                                                      600x600 GRATED                         EXISTING SEWER CONNECTION                                                                                                        PROVIDE 5,000L SLIMLINE RAINWATER
    CROSSFALL, THE CONTRACTOR WILL BE REQUIRED TO RECTIFY BY REMOVING AND REPLACING AT THEIR                                    TURF BLOCK PARKING AREA TO                               USIL: 105.12                                                 USIL: 104.93
                                                                                                                                                                      INLET SL: 105.70                       FROM ADJACENT LOT ON SITE                                                              225mm PP PIPE                             ATTENUATION TANK AS PER DETAIL B.
    COST.                                                                                                                       ARCHITECTURAL SPECIFICATION                              DSIL: 104.95                                                 DSIL: 104.83
                                                                                                                                                                      CLASS B GRATED LID                                                                                                            USIL: 104.95                              OVERFLOWS DIRECTED TO BIOGARDEN
18. WHERE A STORMWATER DRAINAGE TRENCH HAS BEEN CONSTRUCTED LONGITUDINALLY IN THE ROAD,                                                                                                  LENGTH: 31.5m                                                LENGTH: 9.10m
    THEN THE FINAL PAVEMENT SURFACE REPAIR WIDTH IS TO MATCH THE EXISTING LANE WIDTH AND                                                                                                 GRADE: 0.5%                        600x600 GRATED            GRADE: 1%                                     DSIL: 104.88
    TERMINATE 50mm CLEAR OF THE ROAD CENTERLINE OR LANE LINE LINEMARKING TO ALLOW FOR THE                                                                                                                                   INLET SL: 105.9                                                         LENGTH: 9.65m
    BITUMEN EMULSION JOINT SEAL. REINSTATEMENT OF SURFACE ADJACENT TO THE KERB OR ROAD                                                                                                                                      CLASS B GRATED LID                                                      GRADE: 0.65%                            300mm PP PIPE
    PAVEMENT EDGE TO EXTEND FULLY TO THE KERB LINE OR EDGE OF PAVEMENT.                                                                                                                                                                                                                                                                     USIL: 104.70
19. THE CONTRACTOR IS TO CONFIRM THE LOCATION OF SERVICE CONDUITS WITH THE SUPERINTENDENT                                                                                                                                                        1                                                                                          DSIL: 104.30
                                                                                                                                                                                                                                                                                           1
    PRIOR TO LAYING STORMWATER DRAINAGE. ALL TRENCH EXCAVATION AND CONSTRUCTION SHALL                                                                                                                                                            D                                                                                          LENGTH: 25.80m
                                                                                                                                                                                                                                                                                           B
    COMPLY WITH THE REQUIREMENTS OF THE QUEENSLAND WORKPLACE HEALTH AND SAFETY ACT 2011.                                                                                                                                                                                                                                                    GRADE: 1.5%
20. ROADBASE MATERIAL SHOULD BE PLACED IN LAYERS AT LEAST 75 MM THICK BUT NOT EXCEEDING 150 MM                                                                                                                                                                                                      600x600 GRATED
    IN THICKNESS, AND COMPACTED TO A MINIMUM DENSITY OF 95% OF THE MAXIMUM DRY DENSITY AS                                                                                                                                                                                                           INLET SL: 106.07
                                                                                                                                                                                                                                                        600x600 GRATED
    DETERMINED IN ACCORDANCE WITH AUSTRALIAN STANDARD AS1289.6.2.                                                                                                                                          225mm PP PIPE                                                                            CLASS B GRATED LID
                                                                                                                                                                                                                                                        INLET SL: 105.97                                                                   1200Ø JUNCTION PIT MANHOLE COVER
21. CONTRACTOR TO UNDERTAKE ROADWORKS TESTING IN ACCORDANCE WITH NOOSA SHIRE COUNCIL                                                                                                                       USIL: 105.29
                                                                                                                                                                                                                                                        GRATED LID                                                                         WITH STEP IRONS. PROVIDE WATER
    GUIDELINES, DRAWINGS AND SPECIFICATIONS.                                                                                                                                                               DSIL: 105.24
                                                                                                                                                                                                                                                                                                                                           PUMPS (MAX 64L/S) TO HYDRAULIC
22. ECOSOL LITTER BASKETS (200um filter) OR SIMILAR TO BE PROVIDED TO STORMWATER INLET PITS IN                                                                                                             LENGTH: 10.27m
                                                                                                                                                                                                                                                                                                                                           ENGINEERS SPECIFICATION.
    ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS.                                                                                                                                                          GRADE: 0.5%
                                                                                                                                                                                                                                                                                                                                           SL: 106.00
23. GRADE LANDSCAPED AND VEGETATED AREAS LOCALLY TOWARDS DRAINAGE.
                                                                                                                                                                                                                                                                                                                                           IL:103.8
                                                                                                                                                                                                    RETAINING WALL TO STRUCTURAL
                                                                                                                                                                                                    ENGINEERS SPECIFICATION
                                                                                                                                                                                                                                                  2
STANDARD SIGNS AND LINE MARKING NOTES                                                                                                                                                                                                             D
                                                                                                                                                                                                                                                                                                                                  5
                                                                                                                                                                                                                                                                                                                                          RETAINING WALL TO STRUCTURAL
1.     GENERAL                                                                                                                                                                                                                                                                                                                    A
                                                                                                                                                                                                                  225mm PP PIPE                                                                                                           ENGINEERS SPECIFICATION
  1.1.    ALL SIGNS AND PAVEMENT MARKING IS TO BE IN ACCORDANCE WITH THE QUEENSLAND TRANSPORT                                                                                                                     USIL: 105.22
         MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES (CURRENT EDITION).                                                                                                                                             DSIL: 104.70
2. SIGNS                                                                                                                                                                                                          LENGTH: 26.15m
  2.1.   ALL SIGNS TO BE REFLECTORISED CLASS 1 TO AS1906.1:2007 UNLESS NOTED OTHERWISE.                                                                                                                           GRADE: 2%
  2.2.   SIGNS ARE TO BE INSTALLED WITH THE FOLLOWING CLEARANCES TO EDGE OF SIGN: LOCATION
         CLEARANCE NO KERB 600 BEHIND GUIDE POSTS BARRIER KERB 300 FROM FACE MOUNTABLE KERB 500
         FROM FACE OF KERB.                                                                                                                                                                                                                                                                                                                    EXISTING PROPERTY ACCESS TO BE
  2.3.   PARKING CONTROL SIGNS TO BE MOUNTED TO FACE APPROACHING TRAFFIC AT 45° TO KERB OR                                                                                                                                                                                                                                                     DEMOLISHED AND REPLACED WITH NEW
         CARRIAGEWAY EDGE. ALL OTHER SIGNS TO BE TURNED AWAY BY 5° FROM THE NORMAL TO                                                                                                                                                                                                                                                          FOOTPATH, TURF, KERB & CHANNEL FOR
          APPROACHING HEADLIGHT.                                                                                                                                                                         ACO GRATED DRAIN K2-00 /                                                                                                              FULL SITE FRONTAGE. BATTER TO MAKE
3. SIGN SUPPORTS                                                                                                                                                                                         KS2-00 OR SIMILAR. 150Ø                                                                                                               SMOOTH JOIN TO EXISTING LEVELS
  3.1.    SLEEVED SIGNS SUPPORTS ARE TO BE PROVIDED IN ALL AREAS WHERE THEY ARE IN A PAVED                                                                                                               OUTLET
         SURFACE.
                                                                                                                                                                                                                                                                                                                                                       600x600 GRATED
4. LINEMARKING
                                                                                                                                                                                          2m WIDE FOOTPATH IN                                                                                                                                          INLET SL: 106.70
  4.1.   REDUNDANT LINEMARKING IS TO BE GROUND OFF.
                                                                                                                         NOTE: RAINWATER ATTENUATION TANKS TO BE INSTALLED                ACCORDANCE WITH IPWEA                                                                                                                                        CLASS B GRATED LID
  4.2.   THERMOPLASTIC LINEMARKING TO BE USED FOR ALL CONCRETE.                                                                                                                                                                                                                                                       1
                                                                                                                         AS PER MANUFACTURERS SPECIFICATION AND AS PER                    STANDARD DWG RS-065. MATCH                                                                                                  E                                      300mm RCP PIPE
                                                                                                                         DETAIL. ROOF DRAINAGE TO BE FITTED WITH FIRST FLUSH              TO EXISTING LEVELS AT ENDS.
                                                                                                                                                                                                                                                                                                                                                             USIL: 106.34
                                                                                                                         DIVERTERS TO ON-SITE IRRIGATION. TANKS TO BE                                                                                                                                                                                        DSIL: 106.23
                                                                                                                         PLUMBED FOR INTERNAL AND EXTERNAL REUSE.                                                                                                                                                                                            LENGTH: 5.36m
                                                                                                                                                                                                                                                                                                                                                             GRADE: MATCH EXISTING   17/08/21   UPDATE FOR RFI                        -    MVP
                                                                                                                                                                                                                                                                                                                                                                                     02/07/21   ISSUED FOR OPW                        -    MVP
                                                                                                                                                                                                                                                                                                                                          PROVIDE M1 KERB AS PER IPWEA                DATE              REVISION                  MARK CHK
                                                                                                                                                                                                                                                                                                                                          STANDARD DWG RS-080. SAW CUT
                                                                                                                                                                                                                                                                                                                                          300mm INTO EXISTING AND MAKE               PROJECT ENGINEER
                                                                                                                                                                                                            300mm RCP PIPE                              TYPE A DRIVEWAY ENTRY IN
                                                                                                                                                                                                            USIL: 106.93                                ACCORDANCE WITH IPWEA                                                             SMOOTH JOIN. REFER DETAIL C.
                                                                                                                                                                                                            DSIL: 106.36                                STANDARD DWG RS-051.                       REMOVE EXISTING CULVERTS AND
                                                                                                                                                                                                            LENGTH: 24.59m                              250mm ABOVE KERB INVERT AT 3.5m            HEADWALLS AND REPLACE WITH NEW
                                                                                                                                                                                                            GRADE: MATCH EXISTING                                                                  MIN. Ø300 RCP AND HEADWALLS,
                                                                  DETAIL A - TYPICAL BIORETENTION GARDEN                                                                                                                                                                                           MATCHING NEATLY TO EXISTING.
                                             EXTENDED DETENTION
                                                DEPTH VARIES




                                                                        PLANTING SPECIES TO PROVIDE EFFECTIVE
     MAINTENANCE HATCH                                                  REMOVAL OF NUTRIENTS. PLANT VARIETIES                                                                                                                                                                                                                                                                         E [email protected]
     SECURE CAPPED END                                                  AND PLANTING DENSITIES TO ARCHITECTURAL
                                                                        SPECIFICATIONS                                                                                                                                                                                                                                                                                                A 37 MARY ST NOOSAVILLE, QLD
     WITH SCREWS
                                                                                                                                                                                                                                                                                                                                                                                      P +61 7 5211 1003
                 600x600 RAISED GRATE
                    FIELD INLET PIT S.L.                                                                                                                                                                                                                                                                                                                                             CLIENT
                                                                                                                                                     DETAIL B - RAINWATER ATTENUATION TANK                         ROOF DOWNPIPE CONNECTION TO                       DETAIL C - KERB AND CHANNEL TIE IN
                                                                                    1 IN 4
                                                                                             MAX
                                                                                                    EXTEND GEOFABRIC 500MM
                                                                                                                                                                                          100Ø HIGH FLOW OUTLET
                                                                                                                                                                                                                   HYDRAULIC ENGINEERS SPECIFICATIONS                                                                                       CONSTRUCT NEW M1 KERB                      VIVIDO
                                                                                                     AND PIN UNDER TOPSOIL                                                                                                                                                                                                                  AS PER IPWEA STD DWG
                                                                                                                                                                                                                                                                     SAW CUT INTO                                         300MM             RS-080                                   PROJECT
                                                                                                                                    LOW FLOW JUNCTION WITH SCREW CAP DETAIL                          5,000L SLIMLINE RAINWATER TANK                                  EXISTING SURFACE
                                                                                               SANDY LOAM FILTER MEDIA -                                      ORIFICE PLATE DISK
                                                                                                                                                              WITH 25mm ORIFICE
                                                                                                                                                                                                                                                                     AND PAVEMENT
                                                                                                                                                                                                                                                                                                                                                                  GRADE SURFACE TO
                                                                                                                                                                                                                                                                                                                                                                  MATCH TO KERB
                                                                                                                                                                                                                                                                                                                                                                                        THE BELVEDERE ON PEARL
                                                                                               DEPTH VARIES
                                                                                               (0.45MM AVERAGE PARTICLE SIZE)
                                                                                                                                                                                                               ATTENUATION VOLUME
                                                                                                                                                                                                                                                                                                                                                                                        5 PEARL STREET, COOROY
                                                                                                                                        HIGH FLOW                  TANK WALL                                         1.25KL                                                                    EXISTING SEAL
                                                                                                                                        OUTLET
                                                                                                   100MM COARSE SAND                                                                                                                                                                           EXISTING PAVEMENT                                                                     TITLE
                                                                                                   TRANSITION FILTER MEDIA
                                                                                                   (NOMINAL SIZE 0.5 - 2MM)        SCREW ON
                                                                                                                                   ACCESS CAP
                                                                                                                                                              RETENTION LEVEL
                                                                                                                                                                                                                                                                                                                                     NEW SUB-BASE COURSE                               ROADWORKS AND
                                                                                                                                                                                                            RAINWATER REUSE VOLUME
       PROVIDE
       END CAP
                                            PROVIDE SUBSOIL DRAIN AT
                                            MIN 0.5% GRADE TO PIT                   NOMINAL 200MM GRAVEL
                                                                                                                                                                                                                    3.75KL                                                                                                                                                             DRAINAGE LAYOUT PLAN
                                                                                    DRAINAGE LAYER                                                                                                                                                                                      REPLACE 150MM
                                           BIDIM A34 GEOFABRIC OR SIMILAR           (FINE AGG., NOMINAL SIZE 2 - 5MM)                    OUTLET TO        ORIFICE DISK TO BE GLUED                                                                                                      WIDE OF BASE
                                           TO BE WRAPPED AROUND                                                                          DRAINAGE         INSIDE JUNCTION. uPVC                                                                                                         COURSE MATERIAL                      150MM                           150MM
          SUBSOIL DRAIN CLEANOUT                                                                                                         NETWORK                                                                                                                                                                                                                                     PROJECT NO.      DRAWING NO.       STATUS
                                                                                                                                                          OUTLET FROM TANK TO BUTT
        (NON-SLOTTED PVC) AND 135°          WALLS AND BASE OF FILTER MEDIA                                                                                UP AGAINST ORIFICE DISK
               ELBOW CONNECTOR                                                                                                                                                                                                                                                                                                                                                          21011         C30               OPW
                                                                                                                                                                                                                                                                                                                                                                                     DRAWN            DESIGNED          SCALE             ISSUE

                                                                                                                                                                                                                                                                                                                                                                                         MVP            BRP                   1:200        B

Page 32

          EXISTING SITE CATCHMENT AREAS                                            DEVELOPED SITE CATCHMENT AREAS                                                    OP WORKS
                                                                                                                                                                              ISSUE


                                                                                                                                                                       LEGEND


                                                                                                                   C9                            C12
                                                                                                                                                                              DRAINAGE PIPE

                                                                                                                                                                              DRAINAGE PIT

                                                                                                                                                                              JUNCTION PIT

                                                                                                                                                                              BIORETENTION AREA

      C1                                                                                  C1          C2                               C3
                                                                                                                                                                              ATTENUATION TANK

                                                                                                                                                                              EXTERNAL USPTREAM
                                                                                                                                                                              CATCHMENT

                              C2                                            C6
                                                                                                                                                                              INTERNAL CATCHMENT

                                                                                                                                                                              CATCHMENT DRAINAGE
                                                                                                                         C11                                                  DIRECTION




                                                                                                                    C7

E1                                                                     E1
                                                                                                                        C4                  C5

                                                             C4
           E4                                                                        E4
                                                                                                                               C10
                                                                                                 E2
                                                C3                                                                  C8
                         E2
                                                                                                                         E5



                 E3                                               E3                                                            E6




      EXISTING CATCHMENT AREAS                                              DEVELOPMENT CATCHMENT AREAS
                                             FRACTION                                                                  FRACTION
CATCHMENT             AREA (Ha)                                         CATCHMENT               AREA (Ha)
                                          IMPERVIOUS (%)                                                            IMPERVIOUS (%)
     C1                         0.030                 50.0                   C1                            0.017               100.0
     C2                         0.166                 18.9                   C2                            0.020               100.0
                                                                                                                                                       02/07/21   ISSUED FOR OPW                      -    MVP
     C3                         0.004                100.0                   C3                            0.028               100.0                    DATE              REVISION                MARK CHK

     C4                         0.028                 18.8                   C4                            0.017               100.0
                                                                                                                                                       PROJECT ENGINEER


     E1                         0.054                 20.2                   C5                            0.017               100.0
     E2                         0.092                 20.6                   C6                            0.035                37.5
     E3                         0.058                 67.4                   C7                            0.003                 0.0
     E4                         0.020                100.0                   C8                            0.010                 0.0
                                                                                                                                                        E [email protected]
                                                                             C9                            0.019                 0.0                    A 37 MARY ST NOOSAVILLE, QLD
                                                                             C10                           0.017                70.4                    P +61 7 5211 1003
                                                                             C11                           0.037                54.7                   CLIENT

                                                                             C12                           0.008                 0.0                     VIVIDO
                                                                             E1                            0.044                20.4                   PROJECT


                                                                             E2                            0.067                29.3                      THE BELVEDERE ON PEARL
                                                                             E3                            0.037                76.9                      5 PEARL STREET, COOROY
                                                                             E4                            0.020               100.0                   TITLE

                                                                             E5                            0.033                23.1                     STORMWATER CATCHMENT
                                                                             E6                            0.028                54.9                     PLAN

                                                                                                                                                       PROJECT NO.      DRAWING NO.     STATUS

                                                                                                                                                          21011         C31             OPW
                                                                                                                                                       DRAWN            DESIGNED        SCALE             ISSUE

                                                                                                                                                           BRP            BRP                 1:200        A

Page 33

                                                                                                                                                                           OP WORKS
                                                                                                                                                                                     ISSUE




Unit 3 Parking Space             Unit 7 Parking Space         Unit 5 Parking Space
Representative of Units 1 to 4   Representative of U6 to U7




                                                                                                                                                             08/07/21   ISSUED FOR OPW                 -    BRP
                                                                                                                                                             02/07/21   ISSUED FOR OPW                 -    MVP
                                                                                                                                                              DATE              REVISION              MARK CHK
                                                                                                                                                             PROJECT ENGINEER



                                                                                     TURNING PATH NOTES
                                                                                     1.   TURNING CIRCLES SHOWN USING A B99 VEHICLE AS DEFINED BY AS2890.1
                                                                                          PARKING FACILITIES - OFF STREET CAR PARKING.
                                                                                     2.   REFER TO ARCHITECTURAL PLANS FOR FULL DETAILS OF DRIVEWAY AISLE
                                                                                          AND PARKING AREA DIMENSIONS.
                                                                                     3.   REFER TO ARCHITECTURAL PLANS FOR WHEEL STOP AND BOLLARD DETAILS     E [email protected]
                                                                                          WHERE NECESSARY
                                                                                                                                                              A 37 MARY ST NOOSAVILLE, QLD
                                                                                                                                                              P +61 7 5211 1003
                                                                                                                                                             CLIENT

                                                                                                  5.20
                                                                                                                                                               VIVIDO
                                                                                                                                                             PROJECT

                                                                                                                                                                THE BELVEDERE ON PEARL
                                                                                                    3.05   0.95
                                                                                                                                                                5 PEARL STREET, COOROY
                                                                                                B99 Vehicle (Realistic min radius) (2004)
                                                                                                Overall Length                              5.200m
                                                                                                Overall Width                               1.940m
                                                                                                Overall Body Height                         1.878m           TITLE
                                                                                                Min Body Ground Clearance                   0.272m
                                                                                                Track Width                                 1.840m
                                                                                                Lock-to-lock time
                                                                                                Curb to Curb Turning Radius
                                                                                                                                            4.00s
                                                                                                                                            6.250m
                                                                                                                                                               TURNING PATH ANALYSIS


                                                                                                                                                             PROJECT NO.      DRAWING NO.    STATUS

Unit 11 Parking Space            Visitor 1 Parking Space                                                                                                        21011          C40           OPW
Representative of U8 to U11
                                                                                                                                                             DRAWN            DESIGNED       SCALE         ISSUE

                                                                                                                                                                 MVP            BRP             NTS         B

Page 34

                                                        Stormwater HGL Analysis




                                                                                                      Page 23 of 33
P +61 7 5211 1003   A 37 Mary St, Noosaville Qld 4566          E [email protected]   recorconsulting.com

Page 35

Page 24 of 33


[OCR of page images]
REC

107.6
1074
107.2

107
106.8
108.6
106.4

108.2

104.8
104.6
104.4
104.2

104
103.8

103.6

Node ID:

Rim (mn:

Invert (m}

Min Pipe Cover (m}
Max HGL (m)
Link ID:
Lenath {m):
Dia {m}:

Slope (m/m
Up Invert (m:
Dn Invert (rn:
Max Q [lps}:
Max Vel (n/s}:
Max Depth {mn}:

WV,
= =
av

Invert 105.12 a

 

 

  

“Link 1D Link-27"

 

   
    
    

Node! ID 2/A
Bim 105.90 m|

104.93.

 

 

 

   
 
   
 
 

Slope 0.0051 mén

Length 33.56 mm

023m

  
  
 
 
  

 

    

2 Link 1D Link B3——

Lenath 8.93 m
Dia 0.23 mi

Slope 0.0101 min
Up invert 10483 m

 

 

 

 

 

| Mode ID 3/&
T Rit 105.80; m

Profile Plot
Internal Stormwater Network

    

       

    
   
 
 

Dia 0.30 m

-Slope. 0.0063 min.
Up Invert 104.81 m
~- Dn invert 104.72 m_

 

Node ID 4/h
Pin 108.60) m

es

    

© tank iD Pump-01

  

   

  
    
  
    
    
     

 

Invert lo6.d4 m

 

 

4400

 

1405

1410

15

1420

1425

1430

1435

1440

3A,

1445
Station (m)

4450

1455

1460

1465

1470

1475

1480

1485

1480

1495

Page 24 of 33

Page 36

Page 25 of 33


[OCR of page images]
AY
“1

Profile Plot
Internal Stormwater Network

Invert 104.95 m

   

1o4

 

 

‘Node ID 3/4

Rim 105.80
Invert

 

 

 

 

 

 

 

 

 

 

 

 

1401 1402 1403 1404 1405 1406 1407 1408 1409 110
Station (m}
Node ID:
Rim {m}:
Invert (mt:
Min Pipe Cover (mn):
Max HGL (m)
Link ID: Link-05
Lenath {): 10.41
Dia (m}: 023
Slope (m/m} 0.0067
Up Invert {m}: 104.95
Dn Invert (rn): 104.88
Max Q (ips) 19.51
Max Vel {m/s}: 1.16.
Max Depth {mn}:

 

Page 25 of 33

Page 37

Page 26 of 33


[OCR of page images]
 

 

Invert 105.02 m

 

 

 

 

Profile Plot
Internal Stormwater Network

 

 

 

 

 

  

Node ID 2/A

 

Tim 108.90 m
Invert {104.99 m

    

 

 

 

 

 

 

 

 

Node ID:
Rim {m}:

Invert (mt

Min Pipe Cover {m}
Max HGL (m)
Link ID:

Lenath {):

Dia (m}:

Slope (m/m}

Up Invert (mn:

Dn Invert (rn)

Max Q {ips}

Max Vel (m/s)
Max Depth (rn)

4400

4401

4402

+07
Station (m}

Link-10

1408

14

115

 

Page 26 of 33

Page 38

Page 27 of 33


[OCR of page images]
1086
1085
108.4
1083
108.2
4106.1

106
1058
1058
4057
1056
1055
1054

31053

£1052

21054

105

1049

1048

1087

1046

1045

1048

1043

1042

1044

108

1038

1038

1037

1036

tion

Elev

Node ID:

Rim {m}:

Invert (m}

Min Pipe Cover (m}
Max HGL (m)
Link ID:
Length {m):
Dia {m}:

Slope (m/m
Up Invert (m:
Dn Invert (rn:
Max Q [lps}:
Max Vel (n/s}:
Max Depth {mn}:

 

Profile Plot
Internal Stormwater Network

 

 

 

 

 

 

 

 

 

 

 

 

0499

 

4400

4401

1402, 1403

1404 1405 1406

1407 1408

1403

110

11
200

105.97

105.22

105.34

1412

1413

1414 1415 14168

17

18

191420. 1421
Station (m)

1422

1423

1424 1425 1428

1427

1428

1429

1430, 1431

1432, 1433

1434

1435

1436

1437

14381439

5A

Page 27 of 33

Page 39

Page 28 of 33


[OCR of page images]
Profle Plot
a Internal Stormwater Network
gak : :
ERS
ac”
ae y
alae
else
88

     

 

   

Dia 0.30m
~ Slope 0.0225 min
-Upjlnvert 106.93 m,
__Drilnvert 106.36 m

 

4
Invert! 106.34 m

Bim, 106.

Link 1D Link-29
Length 3.21 m

 

 

 

 

 

140114021403 140414051408) 140714081409 HD THT 1412113114 1S HIB MIT 141814191420 142114221423 142414251428 142714281429

Station (m}

Node ID:

Rim {m}:
Invert (mt
Min Pipe Cover {m}
Max HGL (m)
Link ID:
Length (0)
Dia (rm)
Slope (m/m]
Up Invert (rn

VE
106.74
106.34

106.52

Dn Invert (m)
Max Q {ips}
Max Vel (mn/s]
Max Depth (rm)

 

Page 28 of 33

Page 40

                                          Example ESC Defect Documentation
                                                 Template




                                                                                               Page 29 of 33
P +61 7 5211 1003   A 37 Mary St, Noosaville Qld 4566   E [email protected]   recorconsulting.com

Page 41

  Date defect       Defect description           Cause of defect        Proposal to              Defect              Repair implemented
   identified                                                          mitigate cause          repair date




                                                                                                                                          Page 30 of 33

P +61 7 5211 1003                  A 37 Mary St, Noosaville Qld 4566                    E [email protected]                        recorconsulting.com

Page 42

                    Ecosol Litter Basket Technical Specification




                                                                                      Page 31 of 33
P +61 7 5211 1003   A 37 Mary St, Noosaville Qld 4566   E [email protected]   recorconsulting.com

Page 43

                      Ecosol™ Litter Basket
                      Technical Specification




                  environmentally engineered
                           for a better future




  URBAN       ®

ASSET SOLUTIONS

Page 44

                  CONTENTS
                  1.0 Introduction
                  1.1 How and Why the Ecosol™ Litter Basket Works

                  2.0 Ecosol™ Litter Basket Credentials

                  3.0 Warranty And Life Expectancy

                  4.0 Key Features And Benefits

                  4.0 Key Dimensions

                  6.0 Collection And Removal Efficiencies

                   6.1 Particle Size Distribution Collection Efficiency
                   6.2 Laboratory Testing Collection Efficiency Sigmoidal Regression Lines
                   6.3 Field Testing Particle Size Distribution Data
                   6.4 Summary Product Collection Efficiency Data
                   6.5 Product Options

                  7.0 MUSIC Modelling Guidelines

                  8.0 Monitoring

                  9.0 Cleaning And Maintenance Procedures

                  10.0 Applications And Configurations

                  11.0 Turnkey Service

                  12.0 Accreditation

                  13.0 Supplier Technical Product Contact Details

                  Appendix 1 – Ecosol™ Litter Basket Essential Information Form

                  Appendix 2 - References




  URBAN       ®

ASSET SOLUTIONS
    Page 1

Page 45

1.0 Introduction
Increasingly stringent environmental best management practice requires planners
and developers to apply a fit-for-purpose treatment train approach to stormwater
treatment to achieve today’s water quality objectives (WQOs). An integral element
to any good WSUD design is primary treatment or pre-screening of stormwater
flows to remove coarse sediment and gross pollutants prior to downstream
secondary or tertiary treatment systems such as bio retention filters or wetlands.

The Ecosol™ Litter Basket provides effective primary treatment of stormwater
flows at point of source. For many years the Ecosol™ Litter Basket has been seen
as the industry standard for at-source filtration with its effectiveness proven over
time both in the field and under strict laboratory conditions.



                                                                                       The system has been designed to
                                                                                       provided robust and durable cost
                                                                                       effective at-source primary treatment
                                                                                       system that captures and retains solid
                                                                                       pollutants at drainage entry points.

                                                                                       In developing this innovative stormwater
                                                                                       treatment system careful consideration
                                                                                       has been given to durability, longevity,
                                                                                       cost and maintainability. Key
                                                                                       commercial technical features include:

                                                                                         • low visual impact and energy
                                                                                           footprint;
                                                                                         • designed hydraulics with proven
                                                                                           performance and longevity;
                                                                                         • scalable design; and
                                                                                         • cost effective maintenance regime.

                                                                                       This technical manual describes the
                                                                                       operation and performance characteristics
                                                                                       of the system.




                                                                                                     URBAN             ®

                                                                                                  ASSET SOLUTIONS
                                                                                                        Page 2

Page 46

                                             1.1 How And Why The Ecosol™
                                             Litter Basket Works
                                             The Ecosol™ Litter Basket captures
                                             pollutants at drainage entry points and
                                             consists of a capture basket and an
                                             overflow by-pass flap(s). The basket is
                                             fitted below the invert of the gutter and
                                             inside the drainage inlet pit and
                                             importantly does not obstruct flow in
                                             the outlet pipe. Solid pollutants enter
                                             the Ecosol™ Litter Basket with the
                                             stormwater from roadside or other
                                             run-off areas, such as car parks. The
                                             incoming flow and the pollutants
                                             aquaplane across the flap(s) into the
                                             capture basket. The filtered stormwater
                                             then passes into the drainage network
                                             without any head/hydraulic loss through
                                             the unit.




As the basket approaches 90% full, the
by-pass flap(s) begins to open in
response to the incoming flow. Once
the basket is 100% full the pressure of
the incoming flow forces open the by-
pass flap(s), allowing the excess flow, to
enter the drainage system through the
by-pass openings. This effectively
eliminates the likelihood of flooding, a
common fault with other at-source
systems. Even when in by-pass, the
captured pollutants are not remobilised
and are retained in the capture basket.




            URBAN            ®

        ASSET SOLUTIONS
               Page 3

Page 47

2.0 Ecosol™ Litter Basket Credentials

Ecosol has commissioned a range of tests to confirm not only product performance
but also to help with further research and development work. In 1996, the
University of South Australia, a National Australian Testing Authority (NATA)-approved
testing body, tested the Ecosol™ Litter Basket. Its full-size Roadway Surface
Drainage Rig was used to carry out a series of tests in two stages on the Ecosol™
Litter Basket. These tests measured the capture performance of the unit in both
on-grade and sag situations for a range of flows containing full-size, real-life solid
pollutants. The testing confirmed the unit’s ability to capture 97% of pollutants
greater than the filtration mesh size.

The testing also focused on determining whether the unit had any hydraulic impact
on the flows entering the pit. It found that the Ecosol™ Litter Basket did not
reduce the pit’s inlet capacity, a key benefit, especially as the unit is often installed
in road side entry pits where any level of flooding would be unacceptable. The
Ecosol™ Litter Basket also has a by-pass overflow that effectively eliminates the
risk of flooding.

In 2012 Ecosol engaged the University of Adelaide (ENGTEST The school of civil,
environmental and mining engineering) to undertake further independently laboratory
hydraulic and capture efficiency testing on the improved Ecosol™ Litter Basket design.
Additional they also undertook a comprehensive peer review of all prior and current
Ecosol™ Litter Basket field and laboratory testing reports to comprehensively
determine its performance specification. Reference – “Performance Review of
the Ecosol™ Litter Basket at- source solid pollutant filter (report dated 9 May 2013).




                                              3.0 Warranty And Life Expectancy

                                              The Ecosol™ Litter Basket has a one- year warranty covering all components and
                                              workmanship. Urban Asset Solutions Pty Ltd will rectify any defects that fall within
                                              the warranty period. The warranty does not cover damage caused by vandalism
                                              and may be invalidated by inappropriate cleaning procedures or where the unit is
                                              not cleaned within the recommended frequency. The Ecosol™ Litter Basket is
                                              designed to meet strict engineering guidelines and manufacturers guarantees and is
                                              one of the most durable at-source treatment systems available. The stainless steel
                                              components have a life expectancy of 15 years while the filtration bag has a life
                                              expectancy of 5 years providing appropriate maintenance practices are employed.




                                                                                                        URBAN            ®

                                                                                                    ASSET SOLUTIONS
                                                                                                          Page 4

Page 48

                                          4.0 Key Features And Benefits
                                          The Ecosol™ Litter Basket captures and retains a range of pollutants at entry points
                                          to the drainage network. Easily installed into most types of side entry pits, also
                                          known as gully pits or catch-pits, it retains more than 97% of pollutants greater than
                                          600µm and in the field it has been found to collect much smaller particles, including
                                          fine sediments.

                                          For many years the Ecosol™ Litter Basket has been seen as the industry standard
                                          for at-source filtration with its effectiveness proven over time both in the field and
                                          under strict laboratory conditions. Consisting of a capture basket, reusable liner,
                                          and overflow bypass flap(s) the Ecosol™ Litter Basket is fitted below the invert of
                                          the gutter inside the drainage pit and, importantly, does not obstruct flow into the
                                          outlet pipe. The liner is easily removed and emptied during maintenance and
                                          comes in a range of filtration fabric sizes from 100µm to 3000µm, depending on the
                                          site requirements.


Key Features                      Benefits

                                  • Minimal head/hydraulic loss
Hydraulics                        • Does not affect stormwater inlet capacity
                                  • Treats 100% of incoming flow

                                  • Unique by-pass overflow eliminates flooding risk
                                  • More than 97% of solid pollutants > 600μm
Pollutant Capture and Retention
                                  • Significant amounts of sediment and more than 40% TSS
                                  • No remobilisation of captured pollutants

                                  • Different sizes of filter media available for targeted pollutant capture
Design                            • Able to be retro-fitted into existing pits or supplied in its own pit
                                  • Easily installed
                                  • Dry storage of pollution thereby reducing risk of toxic fermentation
Cleaning and Maintenance
                                  • Pollutants not handled during cleaning
                                  • Re-usable filter liner is easily removed for manual cleaning
Environmental Impact              • Reduces sedimentation build-up
                                  • Visually unobtrusive




         URBAN              ®

      ASSET SOLUTIONS
               Page 5

Page 49

5.0 Key Dimensions

The Ecosol™ Litter Basket can be fitted to new and existing side entry pits (whether
single, double, or triple in size), including those with non-standard inlets, outlets,
and junctions. The table below shows the approximate dimensions and holding
capacities for the most typical Ecosol™ Litter Basket applications. Holding
capacities, treatable flow rates and by-pass capacities vary dependent on the
site-specifics.


                                                                              Holding Capacity                                        Static
   Stormwater Inlet Pit                       Dimensions                                              Treatable Flow      By- pass
                                                                            (typical basket depth                                    Head in
       Description                         (Length x Width)3                                            Rate (L/s)2       Capacity
                                                                                  450mm)1                                            By-pass

                                                                                                    200µm       1.5mm
                                 Pit                       Litter Basket            (m3)
                                                                                                     mesh        mesh
                                                                                                                            L/s          mm

         Drainway             600 x 595                        600 x 445            0.120            53           106       110          150
                              600 x 600                        600 x 450            0.121            53           106       110          150
  Single Grated Kerb Inlet
                              900 x 750                        900 x 450            0.182            83           167       215          150
        (with Lintel)
                              900 x 900                        900 x 600            0.243            83           167       215          150
                              1200 x 600                   2 x 600 x 450            0.243            103          212       220          150
 Double Grated Kerb Inlet     1200 x 900                   2 x 600 x 600            0.324            103          212       430          150
      (with Lintel)           1800 x 600                   2 x 900 x 450            0.364            106          220       230          150
                              1800 x 900                   2 x 900 x 600            0.496            106          220       440          150
                              600 x 660                        600 x 450            0.121            53           106       110          150
   Single Side Kerb Inlet
                              900 x 750                        900 x 450            0.182            83           167       215          150
  (with Lintel - no grate)
                              900 x 900                        900 x 600            0.243            83           167       215          150
                              1200 x 600                   2 x 600 x 450            0.243            103          212       220          150
   Double Side Kerb Inlet     1200 x 900                   2 x 600 x 600            0.324            106          220       430          150
   (with Lintel - no grate)   1800 x 600                   2 x 900 x 450            0.364            106          220       230          150
                              1800 x 900                   2 x 900 x 600            0.486            106          220       440          150
                              600 x 600                        600 x 450            0.121            53           106       110          150
     Grated Field Inlet
                              900 x 750                        900 x 450            0.182            83           167       215          150
     (no Kerb or Lintel)
                              900 x 900                        900 x 600            0.243            83           167       215          150
                                600                            437 x 437            0.085            54           108       120          150
                                 750                           558 x 558            0.140            92           184       172          150
       Circular Inlet
                                 900                           680 x 680            0.208            103          212       225          150
                                1050                           801 x 801            0.228            103          212       225          150




                                                    ¹Holding capacities are largely determined by the existing inlet pit dimensions and
                                                    the outlet pipe diameter but typically ranges from 120 - 364Kg at 100% full.

                                                    2The TFR varies dependent on the size of the Litter Basket , mesh appetures and
                                                    percentage of fill for the individual baskets. For the purpose of providing indicative
                                                    TFR’s we have assumed a minimum 375mm diameter outlet and empty litter baskets.

                                                    3All Ecosol™ Litter Baskets installed in pits larger than 600mm in width are fitted with
                                                    flow plates, removable capture baskets, optional hydrocarbon socks and include
                                                    by-pass openings to cater for peak flow conditions.




                                                                                                                       URBAN         ®

                                                                                                               ASSET SOLUTIONS
                                                                                                                        Page 6

Page 50

                                            6.0 Collection And Removal Efficiencies

                                            Stormwater treatment is best when distributed across the catchment treating
                                            stormwater pollutants as close as possible to their point of source. The Ecosol™
                                            Litter Basket provides a cost effective and efficient solution at point of source
                                            and has the highest treatable flow rate of any comparable system. In order to
                                            determine a meaningful characterisation of the Ecosol™ Litter Basket collection
                                            efficiency, an extensive verification phase was undertaken by Avocet Consulting
                                            Pty Ltd, Ecosol and EngTest (The University of Adelaide). To best summarise
                                            the capture efficiency results of extensive product testing a regression of the data
                                            points using a sigmoidal regression curve was selected as it provided a conservative
                                            fit to the wide scatter of data collected. Refer to figures 1 & 2 for testing results.
                                            Table 1 summarises these results

6.1 Particle Size Distribution Collection Efficiency


                    Pollutant Capture Efficiency PSD

                                Capture                    Capture
      Sieve Size
                                Efficiency                 Efficiency
       (micron)
                            (200μm Filter Bag)        (1500μm Filter Bag)

      2000 - 6000                    97%                        97%

      600 - 2000                     97%                        77%

       200 - 600                     86%                        37%

        60 - 200                     35%                        8%

         20 - 60                      4%                        1%




Table 1 – Ecosol™ Litter Basket typical particle size distribution
results at designed Treatable Flow Rates.




            URBAN            ®

        ASSET SOLUTIONS
               Page 7

Page 51

6.2 Laboratory Testing Collection Efficiency Sigmoidal
Regression Lines

In 1996, the University of South Australia tested the Ecosol™ Litter Basket. These
tests measured the capture efficiencies of the unit in both on-grade and sag situations
for a range of flows containing full-size, real-life solid pollutants. In 2012 the
University of Adelaide (Engtest Civil, Environmental and Mining) completed further
measurements of the products capture efficiency at varying flow rates and compiled
comprehensive product performance report (Performance Review of the Ecosol™
Litter Basket) reviewing both past and present field and laboratory testing data.
The below graphs summarise this data.


                                                        100%


                                                        80%
                            Collection efficiency (%)




                                                        60%


                                                        40%


                                                        20%


                                                        0%
                                                               2      4       8       16      32       64       128      256     512     1024   2048   4096

                                                                                                   Particle size (microns)



                                                                   Figure 1 - Sigmoidal regression line for the Ecosol™ Litter Basket, with a 200 micron
                                                                   filtration bag indicating high capture efficiencies for a range of particle sizes.




                                                                                                                                 URBAN            ®

                                                                                                                               ASSET SOLUTIONS
                                                                                                                                       Page 8

Page 52

                                                                                                   6.2 Laboratory Testing Collection Efficiency Sigmoidal
                                                                                                   Regression Lines continued


                                                                                    100%


                                                                                     80%
                                                       Collection efficiency (%)




                                                                                     60%


                                                                                     40%


                                                                                     20%


                                                                                      0%
                                                                                              2             4           8        16              32           64       128      256    512   1024      2048        4096   8192   16384

                                                                                                                                                                   Particle size (microns)




                                                                                                   Figure 2 - Sigmoidal regression line for the Ecosol™ Litter Basket, with a 1500 micron
                                                                                                   filtration bag indicating high capture efficiencies for a range of particle sizes.

6.3 Field Testing Particle Size Distribution Data

                                                 Ecosol Litter Basket Particle Size Distribution
                  100
                  90
                  80
                  70
                                                                                                                                                                                             Parafield Gardens
      Passing %




                  60                                                                                                                                                                         (Residential) 1.5mm

                  50                                                                                                                                                                         Pooraka Pre Cast Factory
                                                                                                                                                                                             (Industrial) 0.200mm
                  40
                                                                                                                                                                                             Techport (Commercial)
                  30                                                                                                                                                                         0.200mm

                  20
                  10
                  0
                                                                                                                                        13.200




                                                                                                                                                                       26.500
                                                                                                                                                               19000
                                                                                                                                                      16000
                                                                                                    2.360
                                         0.300



                                                                                   0.600




                                                                                                                        6.700
                         0.075

                                 0.150



                                                     0.425



                                                                                           1.180



                                                                                                                4.750



                                                                                                                                9.500




                                                                                                   Sieve Size


Figure 3 - Field testing Particle size distribution data for three separate
product installations.




                  URBAN                          ®

            ASSET SOLUTIONS
                        Page 9

Page 53

6.4 Summary Product Collection Efficiency Data
In recent years modern Water Sensitive Urban Design (WSUD) objectives and
principles now applied to most urban development’s require more onerous water
quality objectives (WQOs) specifically targeting the removal of suspended solids,
nitrogen, phosphorus and heavy metals. The Ecosol™ Litter Basket is an integral
part of the treatment train providing essential pre-screening of stormwater flows,
and when used in conjunction with other treatment measures such as swales or
sand filters will achieve target water quality objectives.


                                                       Capture Efficiency (Up to)   Capture Efficiency (Up to)
     Performance Criteria1
                                                          (200µm Filter Bag)          (1500µm Filter Bag)

     Gross Pollutants (>600μm)                                   97%                          77%

     Total Suspended Solids (TSS) (20 - 600µm)                   41%                          15%

     Total Phosphorous (TP)                                      39%                          15%

     Total Nitrogen (TN)                                         11%                           4%

     Heavy Metals                                                6%                           2%

     Total Petroleum/Hydrocarbon                                 20%                           7%



1 Figures quoted are mean collection efficiency statistics based on available
product testing data. It is important to note that the water quality CE values are
indicative of potential field CEs given that Ecosol™ Litter Basket provides physical
screening and the removal of chemical constituents is therefore largely dependent
on the chemical composition of the particles and the bonding of these chemical
constituents to the surface of the particles.

                                                 6.5 Products Options
                                                 To enhance the product capture efficiencies other filter medias can be incorporated
                                                 into the design.

                                                 Hydrocarbon booms installed within the Ecosol™ Litter Basket will provide
                                                 additional protection against oil or fuel spills in wet conditions.


                                                 Reactive filtration media pillows installed at the base of the basket will provide
                                                 improved capture efficiencies for heavy metals, total nitrogen, total phosphorous,
                                                 turbidity and suspended solids.




                                                                                                                 URBAN     ®

                                                                                                             ASSET SOLUTIONS
                                                                                                                 Page 10

Page 54

                                             7.0 MUSIC Modelling Guidelines
                                             These guidelines provide instruction to the creation and application of a treatment
                                             node for the Ecosol™ Litter Basket for the Model for Urban Stormwater Improvement
                                             Conceptualisation (MUSIC). The Ecosol™ Litter Basket can be modelled in MUSIC
                                             using the Generic Treatment node to represent the results derived from independent
                                             laboratory testing and field testing by the University of South Australia and the
                                             University of Adelaide (ENGTEST The school of civil, environmental and mining
                                             engineering). The guidelines apply to the creation of the treatment node within
                                             MUSIC v6.0.4

                                             Insert a GPT treatment node into your model by selecting “GPT” under the treatment
                                             nodes menu. When the node is created the node properties dialog is displayed.
                                             There are several changes that need to be made in this dialog.

                                             • Adjust the text in the Location box to read "Ecosol™ Litter Basket" plus any other
                                               relevant information (200µm or 1500µm).
                                             • Adjust the low flow bypass to refect any flow (m3/sec) diverted away from the
                                               unit before treatment (usually zero).
                                             • Adjust the high flow bypass to reflect the treatable flow rate (TFR values are
                                               detailed in page 6) (L/Sec) any higher flows will bypass treatment

                                             NOTES: Can be used to describe assumptions or location of reduction values for
                                             authority approvals

Adjust the transfer function for each pollutant selecting the pollutant and editing
(right click on the function point)the input and output values on the graph below
to reflect the capture efficiencies (ce) of the treatment device. Table 2 provides the
input and output values for the Ecosol™ Litter Basket based on the use of a 200µm-
filter liner. Table 6 provides the input and output values for the Ecosol™ Litter Basket
based on the use of a standard 1500µm filter liner


                                                                Removal Rate           Entered Input       Entered Output
     Pollutant
                                                                    (%)                    Value                Value

     Total Suspended Solids (20 - 600μm)                              41                   1000                  590
     Total Phosphorus                                                 39                   1000                  610
     Total Nitrogen                                                   11                   1000                  890
     Gross Pollutants (>600µm)                                       97                    1000                  30
     Heavy Metals                                                     6                     n/a                  n/a
     Total Petroleum/Hydrocarbons                                     20                   n/a                   n/a



Table 2 - Ecosol™ Litter Basket - 200 µm Filter liner, input and output values.




            URBAN            ®

        ASSET SOLUTIONS
              Page 11

Page 55

7.0 MUSIC Modelling Guidelines Continued

                                                                Removal Rate           Entered Input     Entered Output
   Pollutant
                                                                    (%)                    Value              Value

   Total Suspended Solids (20 - 600μm)                                15                   1000                850
   Total Phosphorus                                                   15                   1000                850
   Total Nitrogen                                                     4                    1000                960
   Gross Pollutants (>600μm)                                          77                   1000                 230
   Heavy Metals                                                        2                    n/a                 n/a
   Total Petroleum/Hydrocarbons                                        7                    n/a                 n/a



Table 3 - Ecosol™ Litter Basket -1500 µm Filter liner, input and output values.

Once the transfer functions have been defined for each of the pollutants the node
has been fully defined. When completed the properties window can be closed by
clicking the “Finish” button.

For further assistance in sizing or specifying a system for your next project please
complete the form in Appendix 1 and forward to your local Urban Asset Solutions
Pty Ltd representative



                                             8.0 Monitoring
                                             Under normal weather and operating condition your Ecosol™ Litter Baskets
                                             should be checked a minimum of every two - three months depending on the
                                             quality and quantity of the inflow to the unit and immediately following a major
                                             storm event. Initially, Urban Asset Solutions Pty Ltd recommends that monitoring
                                             is undertaken monthly. Once the unit has been in operation for an extended period
                                             of time (say, 24 months) then the monitoring schedule can be adjusted to
                                             reflect the actual operating conditions specific to the catchment.




                                                                                                       URBAN          ®

                                                                                                  ASSET SOLUTIONS
                                                                                                       Page 12

Page 56

                                     9.0 Cleaning And Maintenance
                                     During the first two years of operation it is important to regularly monitor and
                                     maintain each unit to better determine long-term maintenance regimes. All elements
                                     within the Ecosol™ Litter Basket have been designed for easy safe and cost efficient
                                     cleaning by either manual basket removal or vacuum method. Please refer to the
                                     product maintenance guide for full cleaning and maintenance procedures.

                                     The figures in the table below give a broad guideline about the optimal catchment
                                     size,and the number of cleans required annually based on typical expected
                                     urban pollutant loads.



                                                                   Recommended cleaning frequency based on
                                             Optimal
                                            Catchment           optimal catchment sizes and typical pollutant loads
                                               Size                              (per annum)
                                               (Ha)
                                                                          Typical Developed Urban Catchment
                                             Up to 0.2                                     2
                                             Up to 0.3                                    2-3
                                              Up to 0.5                                   3-4




One of the ke y advantages of the Ecosol™ Litter Basket is that it can
be cleaned by vacuum method using street sweeping vehicles. This is safe
and cost efficient.




          URBAN         ®

       ASSET SOLUTIONS
           Page 13

Page 57

10.0 Applications And Configurations
The Ecosol™ Litter Basket is an at-source filtration system that is ideal for capturing
solid pollutants in a variety of locations but is especially effective in built-up areas,
so-called “hot spots” such as shopping precincts and restaurant strips.

The ability to retro-fit the Ecosol™ Litter Basket into existing pits means that
drainage lines serving pollutant-generating catchments, such as schools, shopping
precincts, and central business districts, can be targeted for treatment cost efficiently.




Shopping Centre                                                            Residential Development

                                               Treatment-train Approach

                                               As no one measure can treat all of the pollutants generated from a typical
                                               development a treatment-train approach to stormwater management is always
                                               preferable. This involves using a range of treatment measures, working together, to
                                               achieve improved water quality. The Ecosol™ Litter Basket operating as a
                                               pre-screening system in a treatment train provides essential primary treatment
                                               thereby enhancing the operating life of secondary and tertiary treatment systems.




                                                                                                        URBAN           ®

                                                                                                     ASSET SOLUTIONS
                                                                                                         Page 14

Page 58

                                            11.0 Turnkey Services

                                             Urban Asset Solutions Pty Ltd design and estimating staff provide a dedicated
                                             management approach towards your project. In addition all staff are capable of
                                             liaising with the client, the consulting engineer, the contractor, and all other interested
                                             third parties to achieve a successful outcome.

                                             Given the wide range of pit types, sizes, and configurations, Urban Asset Solutions Pty
                                             Ltd provide a complete turnkey service inclusive of site measure, manufacture and
                                             installation on-site to suit each individual stormwater inlet pit. This flexibility,
                                             when compared to other off-the-shelf, supply-only products, means the client can
                                             be assured of a unit that not only has proven performance but also one that is
                                             ideally suited to the particular needs of the site. The unit’s unique design enables
                                             it to maximise holding capacities for the many different types of pits without
                                             impeding on the hydraulic design characteristics of the inlet pit.

                                             Urban Asset Solutions Pty Ltd has a very competitive cleaning service. After each
                                             clean we provide a report detailing the volume and type of pollutants removed.
                                             We believe that it is in your best interests for Urban Asset Solutions Pty Ltd staff to
                                             clean and maintain the unit, not only because we are specialists, but also because
                                             proper monitoring and maintenance enhances the unit life significantly.

                                             Should you use another company to clean the unit, or undertake this work yourself,
                                             we request that it be conducted according to Urban Asset Solutions Pty Ltd
                                             specifications. Otherwise, you may invalidate your warranty, as damage caused by
                                             inappropriate cleaning procedures is not covered. The advantages of using Urban
                                             Asset Solutions Pty Ltd to clean and maintain your unit are that you get:

                                             • regular inspections of your unit;
                                             • a comprehensive cleaning service with removal and disposal of all captured pollutants;
                                             • a detailed report provided on completion of each clean;
                                             • trained and experienced staff; and remedial work completed, if required.
12.0 Accreditation

Urban Asset Solutions Pty Ltd is accredited to AS/NZS ISO 1400 (Environment)
and AS/NZS 9001 (Quality). Our commitment to continuously improving our
products and services is demonstrated by our ongoing accreditation for Quality and
Environmental Management. Urban Asset Solutions Pty Ltd is also committed to a
safe environment for its employees. We are fully third-party accredited to AS/NZS 4801.


13.0 Suppiler And Technical Product Contact Details

For any maintenance or technical product enquiries please contact:
Urban Asset Solutions Pty Ltd
Tel: 1300 706 624
Fax: 1300 706 634
Email: [email protected]



            URBAN            ®

        ASSET SOLUTIONS
              Page 15

Page 59

Appendix 1

Ecosol™ Litter Basket Essential Information Form
To ensure your system is appropriately designed for its intended application and meets local water
quality objectives it is essential that the following minimum information is provided:


                                                            Customer Details
 Asset Owner:                                                                    Asset ID:
 Unit Location :                                                                 UAS Ref:
 Date:                                   Time:                                   Product Code: Ecosol™ Litter Basket
 Inspected By:




                                                       Project and Site Information
 Project Name:
 Project Address:
 Type of Development/Catchment Type
 Pollutant Removal Targets (%):                               Gross Pollutants (>2000μm)
 Site Water Quality Objectives (WQO’s)                        Total Suspended Solids (20 – 2000μm)
                                                              Total Phosphorus
                                                              Total Nitrogen
                                                              Heavy Metals
                                                              Total Petroleum/ Hydrocarbon
                                                              Other
 Local Authority:
 Proposed Number of Ecosol™ Litter Baskets required:
 Inlet pit type & typical dimensions
 (e.g. Grated side entry pit 900 x 600mm)



 Other essential design or site relevant information




                                                  Please forward the above information for your next project to your local Urban
                                                  Asset Solutions Pty Ltd representative. On receipt Urban Asset Solutions Pty Ltd
                                                  will model and design the most appropriately sized system to suit your application
                                                  to assist you achieve the project Water Sensitive Urban design objectives.
                                                  Email: [email protected]
                                                  Fax: 1300 706 634




                                                                                                                  URBAN      ®

                                                                                                              ASSET SOLUTIONS
                                                                                                                   Page 16

Page 60

                  Appendix 2

                  References

                  Dr. F.P Nejad, Dr.A. Zecchin, Dr.M Lambert (2013) - Performance Review of the Ecosol
                  Litter Basket at-source solid pollutant filter - School of Civil Environmental and
                  Mining Engineering. The University of Adelaide.

                  Prof J.R. Argue, D Pezzaniti (1996) Evaluation of the RSF 100 and RSF 200 Gross Pollutant
                  Traps - Full scale laboratory testing on the performance of the Ecosol Litter Basket
                  on sag and grade test utilising the road surface drainage test rig – Urban Water
                  Resources Centre, University of South Australia.

                  Prof J.R. Argue, D Pezzaniti (1996) Evaluation of the RSF 100 Gross Pollutant Trap –
                  Stage 2 - Full scale laboratory testing on the performance of the Ecosol Litter Basket
                  on sag and grade test utilising the road surface drainage test rig – Urban Water
                  Resources Centre, University of South Australia.

                  Dr.A Wallace (2003) Hydraulic and Strength review of the RSF 100 pollutant traps
                  (Ecosol Litter Basket) primary stormwater filter -Avocet Consulting Pty Ltd.

                  Dr.A Wallace (2012) Experimental determination of collection efficiency of Ecosol
                  Litter Basket primary stormwater filter - Avocet Consulting Pty Ltd.

                  A Attwood (2011) Physical and Chemical Assessment of Gross Pollutants Captured
                  in Ecosol Stormwater Retention Products, Field sampling and analysis at three
                  active site installations - LabSA Pty Ltd.

                  Upper Parramatta River Catchment Trust (2000) Stormwater Pit Pollutant Trap
                  Monitoring – Maintenance and monitoring of Stormwater Pit Pollutant Traps.
                  www. uprct.nsw.gov.au/cleanstreams.

                  M.Liebman, M.Brown, E. Garraway, C.Jones (2004) Kiama CBD’s stormwater treatment
                  and reuse project – Storm Consulting Pty Ltd “Kiama Municipal Council”.

                  J.Chrispin (2003) Assessing Different At-Source Stormwater Treatment Devices in
                  Hobart – Sullivans Cove and Brooker Highway Performance Trials – Hobart City Council.

                  J. Lewis (2002) Effectiveness of Stormwater Litter Traps for Syringe and Litter
                  Removal for Melbourne Water Corporation – Cooperative Research Centre for
                  Catchment Hydrology.

                  I. Jackson (2002) Stormwater Quality Improvement Project Monitoring report June
                  2001 – January 2002 At-Source RSF 100 Solid Pollutant Filters – Great Lakes Council.

                  A.Macklin (2012) Ecosol Litter Basket Water Quality Testing- Filtration Basket Capture
                  Efficiency, Laboratory testing and analysis of pollutant retention and chemical
                  composition using various filter basket medias - Ecosol Pty Ltd.

                  N.Watson (2005) Performance Report Ecosol RSF 100 Basket Installations Tauranga
                  New Zealand – Cleaning maintenance and monitoring report of litter basket
                  installation in the Tauranga City Council CBD – Ecosol (NZ) Wastewater Filtration
                  Systems Pty Ltd.




  URBAN       ®

ASSET SOLUTIONS
   Page 17

Page 61

                                                                       Urban Asset Solutions Pty Ltd
                                                                                ABN 73 627 354 830
                                                                           Telephone: 1300 706 624
                                                                                  Fax: 1300 706 634
                                                           Website: www.urbanassetsolutions.com.au




©Urban Asset Solutions Pty Ltd ABN 73 627 354 830 - 2020
This document is copyright. No part may be reproduced,
stored in a retrieval system, or transmitted in any form
or by any means, electronic, mechanical photocopying,
recording or otherwise without prior written permission
of Urban Asset Solutions Pty Ltd.




       URBAN                                  ®

ASSET SOLUTIONS

Page 62

                              Bioretention Inspection Checklist




                                                                                      Page 32 of 33
P +61 7 5211 1003   A 37 Mary St, Noosaville Qld 4566   E [email protected]   recorconsulting.com

Page 63

                           BIORETENTION SWALE MAINTENANCE CHECKLIST
                                                      3 to 6      Date of
Inspection Frequency:
                                                      monthly     Visit:
Location:
Description:
Site Visit by:
INSPECTION ITEMS                                             Y       N       ACTION REQUIRED (DETAILS)
Sediment accumulation at inflow points?
Litter within swale?
Erosion at inlet or other key structures?
Traffic damage present?
Vegetation condition satisfactory (density,
weeds etc)?
Replanting required?
Mowing required?
Clogging of drainage points?
Evidence of ponding?
Set down from kerb still present?
Damage/vandalism to structures?
Surface clogging visible?
Drainage system inspected?
Remulching of trees and shrubs required?
Soil additives or amendments required?
Pruning and/ or removal of dead or diseased
vegetation required?
Resetting of system required?
                                                     COMMENTS




                                                                                                          Page 33 of 33
   P +61 7 5211 1003          A 37 Mary St, Noosaville Qld 4566             E [email protected]   recorconsulting.com

Page 64

a

G

STRATEGIC

STRATEGIC SOLUTIONS,
CREATIVE THINKING

rgstrategic.com.au

 

Used in these records

About this file

File size
5.1 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

MCU21.0117 OPW21.0199-Att 5 Stormwater.pdf · 5.1 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.