Test 3: H1 and H2 Combined Performance and Street Supply Test
Water Mains Flow and Pressure Testing | Hydrant Commissioning | Fire System Maintenance
Page 5 of 5
[OCR of page images]
o
w_ HTCGroup.com.au
[email protected]
m 0423 383 329
[ | | C croup
abn 96610617055
—® H3 Water Main Residual Pressure
400 4
300 4
200 4
Pressure (kPa)
100 +
0 T T T T T T T ¥
0 5 10 15 20 25 30 35
Total Flow (L/s)
Test 3: H1 and H2 Combined Performance and Street Supply Test
Water Mains Flow and Pressure Testing | Hydrant Commissioning | Fire System Maintenance
Page 5 of 5