4 - Bushfire Response
Proposed Fire Fighting Infrastructure The proposed buildings are to always have a minimum dedicated firefighting water reserve of 50001. This reserve can be in the form of a Tank and must be in place at the time of completion of the new Building. 3.5.3. The tank must be located a minimum of 9m from the nearest bullding, have fiat standing area immediately adjacent, and be no further than 20m from the building and be located between the building and the road. 3.5.4. The tank storage can comprise part of a larger tank providing the normal outlet is positioned to reserve 50001 in the bottom for firefighting purposes only. Provide a 50mm male cam lock fitting outlet with isolating valve for fire brigade purposes only. 3.5.5. The tank is to be of non -combustible materials. ELDON BOTTCHER ARCHITECT PTY LTD © §/10/22 21