I -9-
testing be utilised to determine if further investigation is required, or if this was an
isolated event.
Refer to Table B6 in Appendix B for summary of results.
3.4 Total Petroleum Hydrocarbons
All results were below laboratory limits of reporting. Refer to Table B7 included in
Appendix B for summary of results.
1 4.0 BIORETENTION SYSTEM MONITORING
In accordance with commissioning, the bioretention basins were tested once only,
following a significant rainfall event. Sampling was undertaken at the following locations,
based on information contained within MBT WBM OSWMP - Addendum Report, which
indicated that only these locations provide access and unmixed water:
• BR1/2A;
• BR 1 /213; and
• BR1/3A;
I Sampling was not undertaken at BR1/3B, due to water flow not observed from the outlet.
The issue was reported to Noosa Civic Management and we understand that
maintenance was undertaken. Refer to Table B8 in Appendix B for summary of results.
Permeability testing and soil contamination testing are not required until the end of year
5. Photographic survey was not within the scope of this commissioning.
Fil
5.0 ROOF WATER REUSE SYSTEM
The roof water collection tanks were inspected on a quarterly basis. Refer to Drawing
DE0923/03 for location of inspection points.
Observations are summarised in Table B9 in Appendix B.
The presence of mosquito and cane toad larvae was not detected during inspections. Sludge
within the tanks was immeasurable. A small quantity of floating litter was observed during the
inspection in November 2009 and February 2010. Advice received from Noosa Civic
I Management indicated that the tanks had been leaned out prior to the inspection in
September 2010. The concrete bottom of the tank was clearty visible during this inspection,
with only a very minor amount of leaf litter observed within the tank.
6.0 DISCUSSION
As a result of the significant increase of developed land in the vicinity of the Noosa Civic,
we consider that the monitoring points specified under the OSMP may no longer be
indicative of runoff quality independent to the complex.
As such, we consider a review of monitoring locations and WQOs should be undertaken.
The area surrounding the site is now largely developed with additional roads, and
several of the monitoring locations have catchments which are no longer exclusive to
Noosa Civic.
In addition we consider dissolved oxygen parameters designed for flowing waters are
generally not applicable in this instance and should be amended in line with median
values obtained over the last 12 months of monitoring.
AE0923WQM
March 2011
SHfjs
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Water Quality Monitoring Report - Noosa Civic - November 2009-2010 - Eenie Creek Rd NOOSAVILLERelated documentApplication case desk ↗