Work Order EB0918529
Client DUKE ENVIRONMENTAL
Protect DE0923 ALS
Method Blank (MB) and Laboratory Control Spike (LCS) Report
The quality control term Method Laboratory Blank refers to an anatvte free matrix to vihich all reagents are added in the same volumes or proportions as used in standard sample preparation The purpose of lhns CC
parameter is to monitor potential laboratory contamination The quality control term Laboratory Control Sample (LCS) refers to a certified reference rrmterial, or a known interference free matrix spiked with target
analytes. The purpose of this QC parameter is to monitor method precision and accuracy independent of sample matrix. Dynamic Recovery Limits are based on statistical evaluation of processed LCS.
Sub-Matrix: WATER Method Blank (MB) Laboratory Control Spike (LCS) Report
Report Spike Spike Recovery (%) Recovery Limits (%)
I
Method: Compound Numb
CAS LOR Unit Result Concentration LCS I Low High
EA025: Suspended Solids (QCLOt: 1179437)
EA025H: Suspended Solids (SS) mg/L <5 j 150 mg/L 107 86 108
ED093F: Dissolved Major Catlons(QCLat:_ 1174688)
EG02OF: Dissolved Metals by ICP-MS (QCLot:1174815)
EG020A-F: Aluminium 7429-90-5 0.01 ng/L <0.01 0.500 mg/L 101 76 130
EG020A-F: Arsenic 7440-38-2 0.001 mg/L <0.001 0.100 mg/L 98.2 80 124
EG020A-F: Cadmium 7440-43-9 0.0001 mg/L <0.0001 0.100 mg/L 106 89 117
EG02OA-F: Chromium 7440.47-3 0.001 mg/L <0.001 0.100 mg/L 106 85 127
EG020A-F: Copper 7440-50-8 0.001 mg/L <0.001 0.200 mg/L 95.8 85 119
EG020A-F: Lead 7439-92-1 0.001 mg/L <0.001 0.100 mg/L 106 88 116
EG020A-F: Nickel 7440-02-0 0001 mg/L <0.001 0.100 mg/L 96.8 85 119
EG020A-F: Zinc 7440-66-6 0.005 mg/L <0.005 0.200 mg/L 103 86 130
EG020A-F: Iron 7439-89-6 0.05 mg/L <0.05 0.50 mg/L 104 79 128
EG02OF: Dissolved Metals by ICP-MS (QCLot:1174628)
EG020A-F: Aluminium 7429-90-5 0.500 mg/L 90.9 76 130
EG020A-F: Arsenic 7440-38-2 0.100 mg/L 99.2 80 124
EG02OA-F: Cadmium 7440-43-9 0.100 mg/L 103 89 117
EG020A-F: Chromium 7440-47-3 0.100 mg/L 106 85 127
EG020A-F: Copper 7440-50-8 0.200 mg/L 103 85 119
EG020A-F: Lead 7439-92-1 0.100 mg/L 98.9 88 116
EG02OA-F: Nickel 7440-02-0 0,100 mg/L 105 85 119
EG02OA-F: Zinc 7440-66-6 0.200 mg/L 100 86 130
EG02OA-F: Iron 7439-89-6 0.50 mg/L 106 79 128
EK086O: Ammonia as N by Discrete Analyser (QCLot:1178355)
EKO55G,Ammon aasN 7664-41-7 0 01 mg/L 129
EK0670: Nitrite as N by Discrete Analyser (QCLot:1174886)
EK057G 0 01 103 74 128
T
EK0690: NOX as N by Discrete Analyser (QCLot:1176354)
EK059G Nitrite + Nitrate as N 90.4 70 130
EK061: Total Kjeldahl Nitrogen (TKN) (QCLot:1175188)
EK061G: Total Kjeldahl Nitrogen as N 0 1 <0.1 85.8 70 115
iEK067O: Total Phosphorus as P by Discrete Analyser (QCLCt: 1176187)
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Water Quality Monitoring Report - Noosa Civic - November 2009-2010 - Eenie Creek Rd NOOSAVILLERelated documentApplication case desk ↗
About this file
- File size
- 34.4 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.