The Calile Noosa - Peer Review Rev. B 17.08.22

of 31

Page text shows just the words. Original shows the document exactly as it was published.

               PO22        “Development, including mechanical plant, vehicle maneuvering, commercial
                           kitchens, and communal outdoor recreation uses:
                           (a)   do not have an adverse effect on the amenity enjoyed by users of adjacent
                                 or nearby premises through emission of noise, light, fumes or smoke
                           (b)   do not cause unreasonable disturbance to local fauna through light or
                                 smoke emissions.”
                           Proposal complies.

                           AO22.1 “Communal outdoor recreational facilities including swimming pools,
                                  spas and sports courts are:
                                  (b)   located internally to the arrangement of buildings on the site; and
                                  (c)   not used between the hours of 9:00pm and 6:30am the following
                                        day.”
                                  Proposal complies. Communal outdoor recreational facilities including
                                  swimming pools, spas and sports courts are located internally to the
                                  arrangement of buildings on the site and hotel rules will be established
                                  in due course.

                           AO22.2 “For a lit sports court:
                                  (a)    the court is located at least 60 metres from the external wall of an
                                         existing or approved dwelling on adjoining or nearby premises (as
                                         measured from the centre line of the court); and
                                  (b)    the vertical illumination resulting from direct, reflected or other
                                         incidental light emanating from the site does not exceed 8 lux
                                         when measured at any point 1.5 metres outside the boundary and
                                         at any level from ground level upward; and
                                  (c)    any floodlighting is restricted to the types that give no upward
                                         component of light where mounted horizontally (i.e. a full cut off
                                         luminaire).”
                                  Proposal complies. The centre line of the Tennis Court is 27.6 metres
                                  from the Site Boundary and the closest existing buildings across the
                                  road from the Site Boundary are approximately 65 metres to the
                                  apartment building at 8 Serenity Close and 65 metres to the apartment
                                  building at 10 Serenity Close. The lighting design will ensure that items
                                  (b) and (c) are complied with in due course.

                           AO22.3 “Outdoor or semi-enclosed common areas used for serving or drinking
                                  alcohol, or designated outdoor smoking areas are:
                                  (b)   located internally to the arrangement of buildings on the site.”
                                  Proposal complies.

                           AO22.4 “Mechanical plant is:
                                  (a)  located at least 2 metres from side or rear property boundaries;
                                  (b)  where located at ground level, screened by fencing 1.5 metres in
                                       height or dense vegetation of at least 1.5 metres in width
                                       incorporating grouped trees and shrubs with a maximum
                                       separation distance of 1 metre measured from the centre of the
                                       plant;
                                  (c)  where located above ground level, enclosed or screened such
                                       that it is not visible from the street frontage nor adjoining
                                       properties; and
                                  (d)  visually integrated into the line and plane of the building and roof
                                       design and does not project beyond the height or width of the
                                       building when viewed from the street and adjoining properties.”
                                  Proposal will comply in due course.




Peer Review of the Architectural Design for The Calile Noosa                Revision B   17 August 2022   Page 15
Log in to download the original file

The Calile Noosa - Peer Review Rev. B 17.08.22.pdf · 391 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.