PROJECT NOTES (NOTE  THAT ALL NOTES MAY
STORMWATER DRAINAGE NOTES
                  SEWERAGE SUPPLY NOTES
                                            NOT APPLY)
                                        WATER SUPPLY NOTES
1.   ANY CHANGES SHALL BE APPROVED BY THE           1.   ALL WORK AND MATERIALS SHALL BE IN              1.   ALL WORK AND MATERIALS SHALL BE IN
     ENGINEER IN WRITING PRIOR TO CARRYING OUT           ACCORDANCE WITH CURRENT SOUTH EAST                   ACCORDANCE WITH CURRENT SOUTH EAST
     OF THE WORKS                                        QUEENSLAND SEWERAGE CODE SPECIFICATIONS              QUEENSLAND WATER SUPPLY CODE
                                                         AND STANDARDS.                                       SPECIFICATIONS AND STANDARDS.
                                                                                                                                                                 LINDSAY CONSULTING PTY
                                                                                                                                                                   LINDSAY CONSULTING PTY LTD




2.   ALL LEVELS TO AHD.                                                                                                                                                             LTD
                                                    2.   UNLESS SPECIFIED OTHERWISE ALL MATERIALS        2.   UNLESS SPECIFIED OTHERWISE ALL MATERIALS
3.   ALL DIMENSIONS ARE IN MILLIMETRES UNLESS            AND WORK SHALL COMPLY WITH THE RELEVANT              AND WORK SHALL COMPLY WITH THE RELEVANT                                                            RPEQ 4928
     NOTED OTHERWISE.                                    AUSTRALIAN STANDARDS.                                AUSTRALIAN STANDARDS.
                                                                                                                                                                 OFF. 2C/82 PARKER STREET, MAROOCHYDORE        PH 54 792 118

4.   ALL DIMENSIONS AND LEVELS ARE TO BE            3.   THE CONSTRUCTION OF THE SEWERAGE WORK           3.   ADOPT LIP OF KERB OR SHOULDER OF ROAD AS          THIS DRAWING REMAINS THE PROPERTY OF
     CHECKED ON-SITE BEFORE WORK COMMENCES.              SHOWN ON THIS DRAWING SHALL BE SUPERVISED            PERMANENT LEVEL.                                  LINDSAY CONSULTING PTY LTD AND IS FOR
                                                         BY AN ENGINEER WHO HAS RPEQ REGISTRATION                                                                 THE SOLE USE OF THE CLIENT. NO PART
5.   DIMENSIONS SHALL NOT BE OBTAINED BY                 AND ENDORCEMENT FROM THE RELEVENT               4.   COVER ON MAINS FROM PERMANENT LEVEL TO            MAY BE USED IN PART OR WHOLE WITHOUT
     SCALING THE DRAWING.                                AUTHOIRITY . SEWERAGEWORKS NOT COMPLYING             BE AS SHOWN IN SEQ-WAT-1200-2.                       PRIOR EXPRESS WRITTEN CONSENT OF
                                                         WITH THIS REQUIREMENT WILL NOT BE
6.   FOR BUILDING SET-OUT REFER ARCHITECTURAL
                                                                                                                                                                      LINDSAY CONSULTING PTY LTD
                                                         PERMITTED TO CONNECT INTO THE SEQ SERVICE       5.   CONDUITS TO BE INSTALLED IN ACCORDANCE
     DRAWINGS                                            PROVIDER SEWERAGE SYSTEM.                            WITH THE STANDARD DRAWINGS.
                                                                                                                                                                CLIENT AND PROJECT DESCRIPTION
7.   THE LOCATION AND DEPTH OF ALL SERVICES
     SHALL BE VERIFIED ON SITE WITH THE
                                                    4.   ALL WORK ASSOCIATED WITH LIVE SEWERS OR
                                                         MAINTENANCE HOLES SHALL BE CARRIED OUT BY
                                                                                                         6.   A WATER METER SUPPLIED AT THE DEVELOPER'S
                                                                                                              COST, IS TO BE INSTALLED AT THE SERVICE POINT
                                                                                                                                                                  GJ GARDNER NOOSA
     REVLEVANT AUTHORITY PRIOR TO THE                    THE SEQ SERVICE PROVIDER AT THE                      OF EACH LOT IN ACCORDANCE WITH THE                  PROPOSED RESIDENTIAL
     COMMENCEMENT OF WORKS                               DEVELOPER'S COST.                                    STANDARD DRAWING FOR THE SEQ-SP.
                                                                                                                                                                  DEVELOPMENT
8.   DURING CONSTRUCTION BARRIERS, LIGHTS &         5.   ALL PIPES AND MATERIALS SHALL COMPLY WITH       7.   ALL MATERIALS USED IN THE WORKS SHALL               4-6 HAY STREET,
     SIGNS SHALL BE MAINTAINED TO ENSURE SAFE            THE REQUIREMENTS OF THE "ACCEPTED                    COMPLY WITH THE SEQ-SP's ACCEPTED
     PASSAGE OF TRAFFIC AND PEDESTRIANS IN               PRODUCTS ANDMATERIALS" LIST.                         PRODUCTS AND MATERIALS LIST OR BE                   TEWANTIN
     ACCORDANCE WITH THE REQUIREMENTS OF THE                                                                  APPROPRIATELY SHOWN, LISTED AND DEFINED IN
     LOCAL AUTHORITY.                               6.   EACH ALLOTMENT SHALL BE SERVED BY A DN110            THE ENGINEERING SUBMISSION SO THAT THE
                                                         PE (OR DN100 PVC) PROPERTY CONNECTION. FOR           ALTERNATIVE PRODUCT OR MATERIAL CAN BE
9.   ALL WORK AND MATERIALS SHALL BE IN                  ALLOTMENTS OTHER THAN SINGLE RESIDENTIAL,            ASSESSED AND IF APPROPRIATE, APPROVED BY
     ACCORDANCE WITH CURRENT LOCAL                       A DN160 PE (OR DN150 PVC) PROPERTY                   THE SEQ-SP.                                       DRAWING TITLE
     AUTHORITIES SPECIFICATIONS AND STANDARDS.           CONNECTION SHALL BE PROVIDED.
                                                                                                         8.   ALL CONCRETE FOOTPATHS TO BE CLEAR OF             STANDARD NOTES
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
    NOTIFYING ALL RELEVANT AUTHORITIES AND
                                                    7.   PROPERTY CONNECTIONS SHALL BE LOCATED
                                                         WITHIN THE PROPERTY AS SHOWN IN THE
                                                                                                              WATER MAINS.
                                                                                                                                                                CONTINUED
    PAYING ALL FEES NECESSARY BEFORE                     DRAWINGS.                                       9.   TEST/CHLORINATION POINTS TO BE INSTALLED IN
    COMMENCING WORK, FOR LOCATING ALL                                                                         ACCORDANCE WITH STANDARD DRAWING
    EXISTING SERVICES AND FOR REPAIR OF ANY         8.   PROPERTY CONNECTION BRANCHES SHALL                   NO.SEQ-WAT-1410-1.
    SERVICES DAMAGED AS A RESULT OF THE                  EXTEND INTO THE PROPERTY A MINIMUM OF 300                                                              SCALES
    FOOTPATHS AND PRIVATE PROPERTY SHALL BE              mm AND A MAXIMUM OF 750 mm. UNITYWATER          10. THE CONSTRUCTION OF THE WATER
    REINSTATED TO THEIR ORIGINAL CONDITION.              REQUIRES MINIMUM EXTENSION OF 500 mm INTO           RETICULATION WORK SHOWN ON THIS DRAWING
                                                         PROPERTY.                                           MUST BE SUPERVISED BY AN ENGINEER WHO HAS
11. ANY OBSOLETE/REDUNANT CIRCUITWAY                                                                         RPEQ REGISTRATION. WORKS NOT COMPLYING
    CROSSINGS AND DRAINAGE OUTLETS FROM THE         9.   WHERE PIPES ARE LAID IN FILL, THE FILLING           WITH THIS REQUIREMENT WILL NOT BE
    KERB AND CHANNEL INCLUDING ASSOCIATED                SHALL BE CARRIED OUT IN LAYERS NOT                  PERMITTED TO CONNECT TO THE RETICULATION
    PIPES ACROSS THE FOOTPATH SHALL BE                   EXCEEDING 300 mm (LOOSE) IN DEPTH AND SHALL         SYSTEM.
    REMOVED AND THE KERB AND CHANNEL AND                 BE COMPACTED UNTIL THE COMPACTION IS NOT
    FOOTPATH REINSTATED TO THE LOCAL                     LESS THAN 95% OF THE MATERIALS MAXIMUM
    AUTHORITIES CURRENT SPECIFICATIONS AND OR            COMPACTION WHEN TESTED IN ACCORDANCE
    STANDARDS                                            WITH A.S. 1289 (MODIFIED COMPACTION). TESTING
                                                         SHALL BE CARRIED OUT AFTER EACH ALTERNATE
12. THE CONTRACTOR'S ATTENTION IS DRAWN TO               LAYER. IN ALL SUCH CASES APPROVAL OF
    THE REQUIREMENTS OF THE WORKPLACE HEALTH             CONSTRUCTED SEWERS WILL NOT BE ISSUED BY
    AND SAFETY ACT 1995. ALL WORK IS TO BE               THE SEQ SERVICE PROVIDER UNLESS
                                                                                                                                                                SURVEY DATUM
    CARRIED OUT IN ACCORDANCE WITH THIS ACT              CERTIFICATES ARE PRODUCED CERTIFYING THAT
    AND IN PARTICULAR THE CONTRACTOR TO                  THE REQUIRED COMPACTION HAS BEEN                                                                        .
    ENSURE THE REQUIREMENTS OF THIS                      ACHIEVED.
    SPECIFICATION WITH REGARD TO 'NOTIFICATION
    IN RELATION TO A NOTIFIABLE PROJECT ARE         10. WHERE SEWERS HAVE A GRADE OF 1 IN 20 OR
    FULFILLED.                                          STEEPER,BULKHEADS SHALL BE CONSTRUCTED                                                                  ASSOCIATED CONSULTANTS
                                                        IN ACCORDANCE WITH THE SEQ SEWER CODE.
13. BENCHING OF PIT STRUCTURES SHALL HAVE A
    SMOOTH FINISHED SURFACE, AND PIPES SHALL        11. THE CONTRACTOR SHALL VERIFY THE LOCATION                                                                  REPRODUCED AND
    NOT PROJECT INSIDE THE SHAFT OF THE PIT.            AND DEPTH OF EXISTING SERVICES WITH
                                                        RELEVANT AUTHORITIES BEFORE COMMENCING                                                                    UPDATED FROM
14. STORMWATER DRAINAGE PIPES SHALL BE UPVC
    PIPE (MINIMUM SEWER CLASS SN8) TO AS 14. 1260
                                                        WORKS.
                                                                                                                                                                  CONTOUR CONSULTING
    OR APPROVED EQUIVALENT. MINIMUM COVER TO
    ROOFWATER PIPES SHALL BE 50mm EXCEPT
                                                    12. SEWERS SHALL BE DISUSED /ABANDONED IN
                                                        ACCORDANCE WITH PROCEDURES SET OUT IN
                                                                                                                                                                  ENGINEERS APPROVED
    WHERE REDUCED COVER IS REQUIRED TO
    DISCHARGE TO THE KERB AND CHANNEL.
                                                        THE SEQ SEWER CODE.
                                                                                                                                                                  OPW DRAWINGS FOR
15. MINIMUM PIPE GRADES FOR STORMWATER AS
                                                    13. BENCH MARK AND LEVELS TO AHD.
                                                                                                                                                                  PROJECT 3045 FOR OPW
    3500 PART 3: PIPES SHALL COMPLY WITH - 1.0%
    (MIN) GRADE FOR PIPES < 150 DIA. - 0.5% (MIN)
                                                    14. EXISTING ALLOTMENTS REQUIRING A PROPERTY
                                                        CONNECTION FROM EXISTING SEWERS SHALL BE
                                                                                                                                                                  22/0218 APPROVED 31
    GRADE FOR PIPES > 150 BUT < 375 DIA.                PROVIDED BY THE SEQ SERVICE PROVIDER AT
                                                        THE DEVELOPERS COST.
                                                                                                                                                                  OCT 2022
16. CONCRETE CIRCUITWAY AND PARKING AREAS
    SHALL BE CONSTRUCTED WITH 32 MPa

17. REFER HYDRAULIC DRAWINGS FOR SANITARY
    DRAINAGE LAYOUTS.
                                                                                                                                                               REVISION LIST
18. COMPACTION OF MATERIAL UNDER CONCRETE                                                                                                                      A ORIGINAL ISSUE                                     15/10/24
    CIRCUITWWAYS AND PARKING AREAS SHALL BE (i)                                                                                                                B OVERLAND FLOW PATHS ADDED                          18/12/24
    75% MINIMUM DENSITY FOR COHESIONLESS
    MATERIAL (AS 1289 E5.1) AND (ii) 90% RELATIVE
    DRY DENSITY (STD COMP.) FOR MATERIAL OTHER
    THAN (i)




                                                                                                                                                              Computer File
                                                                                                                                                                                                240608OW.DWG
                                                                                                                                                              DRAWING NUMBER                                     SHEET   REV.

                                                                                                                                                                                                 24-0608-C2       2      B
Log in to download the original file

240608OPW-B.pdf · 2.9 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.