Original PDF page 6, section 1. The text section number identifies this passage in the reader.

                                                                                                                  REINFORCED CONCRETE NOTES:                                                                                                                                        TESTING:
                                                                                                                  GENERALLY, CONCRETE SHALL BE IN ACCORDANCE WITH AUSTRALIAN STANDARD                                                                                               ALL CONCRETE TESTING IS TO BE CARRIED OUT BY A NATA REGISTERED LABORATORY,                                CONCRETE ACCESS DRIVEWAY DETAILS
                                                                                                                  SPECIFICATIONS                                                                                                                                                    IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF AS 1012.
                                                                                                                  AS 3600-1994            "SAA CONCRETE STRUCTURES CODE".                                                                                                           THE FOLLOWING TESTING SCHEDULE IS TO BE ADOPTED IN ADDITION TO THE REQUIREMENTS
                                                                                                                                                                                                                                                                                                                                                                                                180mm CONCRETE SLAB (Fc=32MPa)
            CONCRETE FOOTPATH DETAILS                                                                             IN ADDITION TO THE ABOVE CODE THE FOLLOWING AUSTRALIAN STANDARD                                                                                                   OF THE MANUFACTURER'S QUALITY ASSURANCE PROGRAM :
                                                                                                                                                                                                                                                                                                                                                                                                (SL82 MESH WITH 50 TOP COVER) on 150mm CEMENT TREATED SUB
                                                                                                                  SPECIFICATIONS AND CODES OR THEIR LATEST REVISION SHALL APPLY:                                                                                                ·   A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH ELEMENT CAST ON ANY
                                                                                                                                                                                                                                                                                                                                                                                                BASE on COMPACTED SUBGRADE (100% STANDARD COMPACTION)
                                                                                                                  AS 1012 PTS 1-19        METHODS FOR THE TESTING OF CONCRETE (METRIC UNITS)                                                                                        GIVEN DAY (EG. COLUMNS, FOOTINGS, ETC)
                                                                                                                                                                                                                                                                                                                                                                                                EXACT PAVEMENT DEPTHS TO BE DETERMINED BY GEOTECHNICAL
             100mm CONCRETE SLAB (Fc=25MPa), SL72 MESH WITH 50 TOP                                                AS 3583.1,2,3,8         METHODS OF TEST FOR SUPPLEMENTARY CEMENTITIOUS                                                                                        ·   A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH CONCRETE STRENGTH                                 ENGINEER.
             & SIDE COVER COMPACTED SUBGRADE (100% STANDARD                                                                               MATERIALS FOR USE WITH PORTLAND CEMENT                                                                                                    GRADE CAST ON ANY GIVEN DAY.
             COMPACTION)                                                                                          AS 3582.1               SUPPLEMENTARY CEMENTITIOUS MATERIALS FOR USE                                                                                          ·   A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH 5OM³ OR PART
             EXACT PAVEMENT DEPTHS TO BE DETERMINED BY THE                                                                                        WITH PORTLAND CEMENT- FLY ASH                                                                                                     THEREOF CAST ON A GIVEN DAY FOR EACH STRENGTH GRADE.
             SUPERVISING ENGINEER.                                                                                AS 1141                 METHODS FOR SAMPLING AND TESTING AGGREGATES                                                                                               ALL SAMPLES ARE TO BE TAKEN FROM THE AGITATOR, ON SITE.                                                                               NOTE:
             BOLSTER JOINTS AT 2m cts, DOWEL JOINTS AT 8m cts (MAX)                                               AS 1302                 STEEL REINFORCING BARS FOR CONCRETE                                                                                                       IF WATER IS ADDED ON SITE, WITH THE ENGINEER'S PERMISSION, SAMPLES FOR TESTING                                REFER TO LANDSCAPE ARCHITECT'S PLANS FOR CONCRETE FINISH
                                                                                                                  AS 1303                 HARD DRAWN STEEL REINFORCING WIRE FOR CONCRETE                                                                                            SHALL BE TAKEN AFTER THE ADDITION OF WATER.                                                                   / COLOURS. IF EXPOSED AGGREGATE IS SPECIFIED THEN THE
                                                                                                                  AS 1304                 HARD DRAWN STEEL WIRE REINFORCING FABRIC FOR                                                                                                                                                                                                            CONTRACTOR MUST SUPPLY SAMPLES OF AGGREGATE SIZE AND
                                                                                                                                          CONCRETE                                                                                                                                                                                                                                                COLOUR FOR APPROVAL PRIOR TO PLACEMENT OF ANY
                                                                                                                  AS 3972                 PORTLAND AND BLENDED CEMENTS                                                                                                                                                                                                                            CONCRETE PAVEMENT.
                                                                                                                  AS 1379                 READY-MIXED CONCRETE (METRIC UNITS)                                                                                                       CURING:
                                                           TOOL FINISH CONCRETE                                   AS 2758                 CONCRETE AGGREGATES
                    CUT EVERY SECOND                       BREAK SLAB FULL DEPTH                                                                                                                                                                                                    ALL CONCRETE IS TO BE CURED BY AN APPROVED METHOD FOR A MINIMUM OF 28 DAYS AFTER
                                                           WHILE STILL "GREEN"
                                                                                                                  AS 1478, 1479           CODE OF PRACTICE FOR USE OF CHEMICAL ADMIXTURES IN                                                                                        FINISHING.
                                                                                                                                          CONCRETE
                                                                                                                                                                                                                                                                                    CURING METHOD IS TO BE APPROVED BY THE ENGINEER PRIOR TO CONCRETE PLACEMENT AND
                                                                                                                  AS 3610                 FORMWORK FOR CONCRETE                                                                                                                     SHALL GENERALLY CONSIST OF ONE OR A COMBINATION OF THE FOLLOWING METHODS :
                                                                                                                       SUPPLY:                                                                                                                                                  ·   CONTINUOUS WATER PONDING.
                                                                                                              ·        ALL CONCRETE IS TO BE SUPPLIED BY A LICENSED READY MIXED CONCRETE MANUFACTURER.                                                                          ·   COMPLETE ENCASEMENT IN A WATERPROOF FILM (EG. POLYTHENE).
                                                                                                              ·        NO ON SITE BATCHING IS ACCEPTABLE.                                                                                                                       ·   APPLICATION OF AN APPROVED CURING COMPOUND.
                                                                                                              ·        MANUFACTURERS MUST HAVE AN APPROVED AND CERTIFIED QUALITY ASSURANCE PROGRAM
                                                                   200 UM VISQUEEN                                     IN PLACE AND BE APPROVED BY THE ENGINEER PRIOR TO SUPPLY OF ANY CONCRETE.
                                                                                                              ·        ALL MATERIALS, STORAGE, BATCHING, ETC TO CONFORM TO THE REQUIREMENTS
                                                                                                                       OF THE RELEVANT AUSTRALIAN STANDARDS.
                                       BOLSTER JOINT                                                          ·        ALL CONCRETE TO BE NORMAL-CLASS IN ACCORDANCE WITH AS 3600 UNLESS NOTED OTHERWISE.
                                                    N.T.S.                                                    ·        ALL CONCRETE SHALL HAVE A SHRINKAGE STRAIN NOT EXCEEDING 600 MICROSTRAIN.
                                                                                                              ·        ALL CONCRETE IS SPECIFIED BY 28 DAY COMPRESSIVE STRENGTH UNLESS NOTED OTHERWISE.
                                                                                                              ·        ALL REINFORCEMENT TO BE SUPPLIED BY A REGISTERED MANUFACTURER WITH AN APPROVED AND
                        DOWEL SOCKETS TO                                                                               CERTIFIED QUALITY ASSURANCE PROGRAM IN PLACE. ALL REINFORCEMENT IS TO COMPLY WITH THE                                                                                                                                                       TOOL FINISH CONCRETE
                                                                                                                                                                                                                                                                                                                                  CUT EVERY SECOND                 BREAK SLAB FULL DEPTH
                        MANUFACTURERS SPEC.                R12 GALVANISED DOWELS                                       REQUIREMENTS OF AS 1302, AS 1303 AND AS 1304 AS APPLICABLE.                                                                                                                                                WIRE OF MESH
                                                           (600 LONG) AT 450 CTS                              ·        ALL REINFORCEMENT IS TO BE DELIVERED TO SITE FREE FROM OIL, GREASE OR OTHER SURFACE                                                                                                                                                         WHILE STILL "GREEN"
                        OR EQUAL
                                                                                                                       COATINGS WHICH MAY IMPAIR BOND TO CONCRETE.
                               SL72 MESH                                                                      ·        ALL REINFORCEMENT TO BE 500 MPA MINIMUM YIELD UNLESS NOTED OTHERWISE.
                               50 COVER                       10mm ABELFEX OR EQUIV.




                                                                                                                                                                                                                                                                                                                                180
                                                                                                                       FORMWORK:
                                                                                                              ·        ALL CONCRETE OTHER THAN CAST AGAINST GROUND, SHALL BE PLACED AGAINST TIMBER, PLYWOOD
                                                                                                                                                                                                                                                                                                                                                                                                        200mm CBR 15
                                                                                                                       OR STEEL FORMS.
                                                                                                              ·        ALL FORMWORK SHALL COMPLY WITH THE REQUIREMENTS OF AS 15O9 AND AS 151O.                                                                                                                                                                               200 UM VISQUEEN
                                                                                                              ·        REFER ARCHITECT'S DRAWINGS FOR REQUIRED FORMWORK CLASS WHERE APPLICABLE. CLASS B
                                            300              300                                                       FORMWORK SHALL BE ADOPTED UNLESS NOTED OTHERWISE.
                                                                            200 UM VISQUEEN
                                                                                                              ·        ALL TEMPORARY FORMWORK, FALSEWORK, PROPPING, BRACING, TO BE DESIGNED AND CERTIFIED                                                                                                                                 BOLSTER JOINT (BJ)
                                 DOWELLED JOINT                                                                        BY A REGISTERED PROFESSIONAL ENGINEER (RPEQ) PRIOR TO ERECTION.
                                                                                                                                                                                                                                                                                                                                                           N.T.S.
                                                    N.T.S.                                                    ·        ALL REINFORCEMENT TO BE SUPPORTED OFF FORMS WITH PLASTIC OR PLASTIC TIPPED WIRE
                                                                                                                       CHAIRS TO PROVIDE THE SPECIFIED COVER. ALL CONCRETE CAST AGAINST GROUND TO BE
                                                                                                                       UNDERLAIN BY WATERPROOF MEMBRANE.
                                                             1.80m U.N.O.
                                                                                                                  TRANSPORT :
                                                                                                                  ALL CONCRETE IS TO BE TRANSPORTED TO SITE IN AGITATOR TRUCKS.                                                                                                                                                        DOWEL SOCKETS TO
                                                                                                                  CONCRETE NOT PLACED WITHIN ONE HOUR AFTER BATCHING MAY BE REJECTED AT THE                                                                                                                                            MANUFACTURERS SPEC.              R16 GALVANISED DOWELS
                                           2.5%                 2.5%                    2.5%                      ENGINEER'S DISCRETION.                                                                                                                                                                                               OR EQUAL                         (600 LONG) AT 450 CTS

                                                             100tk CONCRETE SLAB, SL72 MESH, 50                                                                                                                                                                                                                                           SL92 MESH
                                                                                                                       PLACEMENT, COMPACTION AND FINISHING :                                                                                                                                                                              50 COVER                           10mm ABELFEX OR EQUIV.
                                                             COVER. ALL SLABS CAST WITH 25MPa
                                                                                                              ·        CONCRETE TO BE PLACED IN FORMS BY HORIZONTAL 'CHUTING' NO MORE THAN 3M³, CONCRETE
                                                             CONCRETE. BOLSTER JOINTS @ 2m cts,
                                                             DOWLED JOINTS @ 8m cts                                    PUMPING OR KIBBLING. UNDER NO CIRCUMSTANCES SHALL CONCRETE BE INDUCED TO FLOW
                                                                                                                       HORIZONTALLY BY USE OF VIBRATORS.




                                                                                                                                                                                                                                                                                                                          180
                                                                                                              ·        ALL CONCRETE SHALL BE PLACED CONTINUOUSLY BETWEEN CONSTRUCTION JOINTS AS DETAILED,
                           TYPICAL CROSS SECTION                                                                       IN SUCH A MANNER AS TO AVOID 'COLD JOINTS'. CONSTRUCTION JOINTS SHALL BE LOCATED AS                                                                                                                                                                                              200mm CRB 15
                                                   SCALE 1:25                                                          DETAILED ON DRAWINGS OR AS INSTRUCTED IN WRITING BY THE ENGINEER.
                                                                                                              ·        ALL CONCRETE IS TO BE COMPACTED UPON PLACEMENT USING 5OMM DIAMETER VIBRATORS.                                                                                                                                                 300                   300
                                                                                                                                                                                                                                                                                                                                                                                              200 UM VISQUEEN
                                                                                                              ·        SLABS AND BEAMS ARE TO HAVE A FILM OF APPROVED ALPHATIC ALCOHOL APPLIED TO THE SURFACE,
                       CONCRETE FOOTPATHS                                                                              DIRECTLY AFTER SCREEDING, PRIOR TO FLOATING, REGARDLESS OF WEATHER CONDITIONS.                                                                                                                                      DOWEL JOINT (DJ)
                                                                                                              ·        ADDITIONAL PROTECTIVE MEASURES SUCH AS CHILLED MIX WATER, SHADING PLACEMENT AREAS,
                                                                                                                                                                                                                                                                                                                                                            N.T.S
                                                                                                                       WIND BREAKS, ETC MAY BE REQUIRED BY THE ENGINEER IF PLACING CONCRETE DURING
                                                                                                                       UNUSUALLY HOT, DRY OR WINDY CONDITIONS.
                                                                                                              ·        ALL CONCRETE SLABS SHALL BE STEEL TROWEL FINISHED UNLESS NOTED OTHERWISE.
                                                                                                              ·        BROOM FINISHING, WHERE SPECIFIED, SHALL BE CARRIED OUT AFTER STEEL TROWEL FINISHING.
                                                                                                              ·        ALL CONCRETE TO BE ORDERED AND PLACED AT 8OMM SLUMP UNLESS NOTED OTHERWISE.                                                                                                                         CONCRETE ACCESS DRIVEWAYS
                                                                                                              ·        NO WATER TO BE ADDED ON SITE UNLESS APPROVED BY THE ENGINEER.




NOTE: ONLY DRAWINGS MARKED "FOR CONSTRUCTION" AND BEARING AN ORIGINAL SIGNATURE SHALL BE USED FOR CONSTRUCTION Design:
                                                                                                               PURPOSES.
                                                                                                                       SWT                                                                                                                                                                         PROJECT:                                                                                           DRAWING TITLE:
                                                                                                                                                                                                                                                                 ALTA PROJECTS
                                                                                                                                    Drawn: SWT
                                                                                                                                                                                                                                                                 A.B.N. 611355330                                                                                                                     CONCRETE DETAILS
                                                                                                      FOR APPROVAL                   Date: DEC 2017                                                                                                              26 Memorial Avenue, Cotton Tree   PROPOSED COMMERCIAL DEVELOPMENT
                                                                                                          NOT FOR CONSTRUCTION                                                                                                                                   PO Box 559, Cotton Tree, QLD, 4558                                                                                                                                           Revision       Sheet
  C    28/01/2021    ISSUE FOR APPROVAL                                          S.T.          S.R.                               Checked:. . . . . . . . . . .
                                                                                                                                                                                                                                                                                                   at 30-32 DOONELLA STREET, TEWANTIN QLD
                                                                                                                                                                                                                                                                 Tel (07) 5475 4125 Fax (07) 5479 1607                                                                                                DRAWING No:
                                                                                                                                                                                                                                                                                                                                                                                                                       A6035/21/R02             C           2 of 3
  B    27/01/2021    ISSUE FOR APPROVAL                                          S.T.          S.R.      STEPHEN ROBERTS
                                                                                                                                                                                                                                                                 Email: [email protected]
  A
  1
       21/01/2021
       18/01/2021
                     ISSUE FOR APPROVAL
                     CO-ORDINATION ISSUE
                                                                                 S.T.
                                                                                 S.T.
                                                                                               S.R.
                                                                                               SR
                                                                                                      .......................
                                                                                                          DIRECTOR APPROVAL            Datum AHD
                                                                                                                                                                                                                                                                 Web: http://www.alta.net.au       for DONNELLA STREET PTY LTD
 REV    DATE                                 DESCRIPTION                         BY        CHKD           RPEQ - 7665                   A1 SHEET SIZE             FILENAME : A6035 - R02 CONCRETE DETAILS.dwg - DATE : 28/1/21 - 4:36pm - XREF's: H-Approved-SR; H-Checked-SR                                                                              Council Ref: ...................

Log in to download the original (Engineering Drawings.pdf)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.