Inputs Outputs
Heat of 18,600 Minimum distance to < 19 23 m
combustion kJ/kg kW/m²
Flame temperature 1,090 K Minimum distance to < 32.4 m
12.5 kW/m²
Minimum distance to < 10 38.4 m
kW/m²
Rate of Spread - Mcarthur, 1973 & Noble et al., 1980
Flame length - NSW Rural Fire Service, 2001 & Noble et al., 1980
Elevation of receiver - Douglas & Tan, 2005
Flame angle - Douglas & Tan, 2005
Radiant heat flux - Drysdale, 1999, Sullivan et al., 2003, Douglas & Tan, 2005
The setback distance required to achieve a radiant heat flux of less than 29kW/m2 is 15.7m from the
potentially hazardous vegetation to the north. Figure 4 below designates the setback edge of
hazardous vegetation where the distance to the proposed building is 21.9m from the north-eastern
most corner, and 24.4m from the north-western most corner. This will achieve a Radiant Heat Flux
within 19-29kW/m2 which is within the sates acceptable level of risk. Compliance with AS3959-2018
for a Class 3 Structure will be required.
Figure 4: Proposed development location opposite potentially hazardous vegetation. A setback
distance from the nominal ‘Hazardous Vegetation Effective Edge Line’ of 15.7m will achieve a Radiant
Bushfire Hazard Assessment | Noosa Springs RFA17-040 22 April 2021
Rob Friend & Associates Pty Ltd