Performance outcomes Acceptable outcomes Response
Bushfire mitigation measures do not adversely impact The site does not contain any areas of biodiversity
on: values, connectivity of ecosystem functioning OR natural
waterways, wetland or areas of native vegetation that
1. biodiversity values, connectivity and ecosystem
could be adversely impacted upon by bushfire mitigation
functioning; and
measures.
2. the long term physical integrity of waterways,
wetland and areas of native vegetation.
Water Supply for Fire Fighting Purposes
PO3 AO3.1 R3.1
Development provides an adequate water supply for Premises are connected to the reticulated water
fire fighting purpose which is reliable, safely located supply. The subject site has access to a reticulated water
and freely accessible. supply/is in a water service area.
Editor's note—For reconfiguring a lot, water supply
needs to provide for a minimum flow and pressure of 10
litres a second at 200kPa at all times for fire fighting
purposes.
OR
AO3.2
Where there is no available reticulated water supply,
the premises has:
1. an accessible dam, swimming pool or water tank
available for fire fighting purposes with an onsite
water volume of not less than 5,000 litres; and
2. a water supply outlet pipe 50 millimetres in
diameter fitted with a standard fire brigade fitting
connected to the water supply (other than where
the water supply is in a swimming pool or dam).
Editor’s Note—Water supply capacity for fire fighting
purposes is in addition to water supply capacity for
other uses and activities on the premises.