When is a fire separating or fire resisting wall required in Class 1a building? External walls if: * the wall is less than 900mm from an allotment boundary other than the boundary adjoining a road alignment or other public space, or * 1.8m from another building on the same allotment other than an associated Class 10 building. External walls - allowable encroachments Encroachments allowed within 900mm of an allotment boundary or within 1800mm of another building on the same allotment include: * fascias, gutters and downpipes _* eaves with non-combustible roof cladding and eaves lining * flues, chimneys, pipes, cooling, heating or other services. These encroachments however must not be built within 450mm of an allotment boundary or 900mm of another building on the same allotment.