Figure 2 – Proposed stormwater tank location
Source: BRW Hydraulics




                     PROPOSED HYDRAULIC DESIGN

                               CHARGED DRAINAGE LINES

The maximum potential head on the charged line is 2.600m and measured between the Ground floor roof
and the discharge point at the kerb. With the charged roof water line running full the head loss and flow
rates in the pipe discharging to the kerb are as follows:


    •    23m of 150mm PVC, equivalent length including fittings = 40.5m. Flow rate = 19.3L/s. Therefore the
         Headloss in 150mm PVC pipe (6.5m/1000m) = 0.263m


    •    6.5m of 150mm PVC, equivalent length including fittings = 20.0m. Flow rate = 14.4L/s. Therefore the
         Headloss in 150mm PVC pipe (4.0m/1000m) = 0.08m


    •    26m of 100mm PVC, equivalent length including fittings = 30.5m. Flow rate = 6.2L/s. Therefore the
         Headloss in 100mm PVC pipe (4.3m/1000m) = 0.134m

                                               Page 4 of 6
   2261 david low way, peregian beach, qld 4573      acn: 626 671 092          [email protected]
Log in to download the original file

124-002 Technical Memorandum Revision B.pdf · 4.6 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.