Stormwater Management Plan
Original PDF page 12, section 1. The text section number identifies this passage in the reader.
This document appears to be plans or drawings. Its page text below holds only the words printed on the drawings, without the drawings themselves, so it may be jumbled or hard to follow. To see the plans as drawn, choose Original above or download the file (both need you to log in).
Log in to see the plans as drawn65-67 Elanda Street, Sunshine Beach
Site Based Stormwater Management Plan
_____________________________________________________________________________________________
Table 3.3 Flow comparison between Pre- and Post- development
Storm Event Peak Flow Pre- Peak Flow Post- Difference Difference
development development (m3/s) (L/s)
3 3
(m /s) (m /s)
63% AEP, 25min 0.017 0.031 0.014 14
39% AEP, 25min 0.022 0.036 0.014 14
20% AEP, 25min 0.035 0.051 0.016 16
10% AEP, 25min 0.046 0.061 0.015 15
5% AEP, 25min 0.054 0.070 0.016 16
2% AEP, 25min 0.059 0.074 0.015 15
1% AEP, 25min 0.069 0.082 0.013 13
It can be observed that the proposed development shall produce a maximum of 16L/s
increase in flow discharge from storm events up to 1% AEP, which may cause actionable
nuisances to the vicinity of the development site. Hence, on-site stormwater detention
devices are necessary for the proposed development, so that the peak flow from the Post-
development scenario can be no greater than the Pre-development scenario.
To validate the modelling results above, Rational Method is also applied to estimate the
discharge, detailed calculation is presented in Appendix E. Table 3.4 summarises the peak
flows of various storm events.
File Name: WCD-22936 – 65-67 Elanda_SWMP.docx
Revision: C 12