                              PROPOSED UNIT DEVELOPMENT
                              3 HENDERSON STREET, SUNSHINE BEACH

6.3       Building Foundations
6.3.1       Indicative Site Classification
Site classifications for footing design are determined in accordance with AS 2870-2011 Residential Slabs and
Footings and depend on the depth of cut / fill undertaken at a site, variations in the natural soil/rock depths,
and the reactivity of the in situ soil / rock and any imported fill materials. It should be noted that the proposed
works are outside of the scope of AS2870.

Based on the results of the investigation, the site is classified as Class P in accordance with AS 2870-2011
Residential Slabs and Footings, due to the presence of uncontrolled fill and the poor bearing capacity of soils
at shallow depths. However, if not for these factors, the site would have the characteristics of Class S, with
the estimated characteristic surface movements (‘ys’) ranging up to about 20 mm. Due to the potential
variability in subgrade density, a site classification of Class M is recommended in relation to assessment of
flexibility requirements for ground slab, footing and plumbing design.

6.3.2       Footing Design
No design loadings were available at the time of reporting. Footings for the proposed development and any
ancillary structures (e.g. retaining walls, etc.) must penetrate through any fill materials and unsuitable natural
soils (i.e. very loose to loose sands) to found at least 0.5 m into medium dense (or denser) natural sands.
Such materials were encountered in the boreholes below depths of about 1 m in the eastern part of the site to
2.8 m BGL (existing ground levels) in the rear western part of the site. High level footings may be adopted
where such materials are exposed at or near the foundation subgrade level. However, piled footings will be
required in areas where loose or very loose sands are present at depth below subgrade level.

Piles founded in medium dense sands or better may be designed using an allowable end bearing pressure
(EBP) of 500 kPa. Piles founded in dense sand may adopt an allowable EBP of 1 MPa. High level footings,
where achievable in deeper cut areas, may be designed using an allowable bearing pressure of 150 kPa
provided that they are founded in the natural medium dense (or denser) sands. Settlement under such loads
is expected to be in the order of up to 20 mm or 1% of footing width.

Given the sandy soil profile and depths of footings required, steel screw piles are considered to be an
appropriate foundation type for the proposed unit development generally. However, in areas of cut exposing
medium dense (or denser) sands at the subgrade level, conventional high-level footings may be adopted. It
should be noted that excavation for concrete strip footings (or similar) may loosen the base. Therefore, the
use of a vibrating plate and ample water would be required to densify any high-level footing bases prior to
the placement of reinforcing steel. Additional DCP testing should be conducted during construction to
confirm the density of the subgrade materials where high-level footings are proposed.

Due to the presence of loose sands, open bored piers or driven piles are not considered to be appropriate for
this site. Steel reinforced concrete bored piles may be possible; however, the use of sacrificial liners (e.g.
formatube etc.) would be required. The advice of a specialist piling contractor must be sought regarding
feasibility, design and installation of the piling system for this site, including an assessment of potential
vibration effects on nearby structures, and monitoring requirements.

If steel screw piles are adopted, it will be important to ensure close supervision of installation, as piling may
not encounter sufficient drilling resistance (from torque measurement) in sands at the suggested founding
depth, and piles could extend to much greater depth than necessary.
It is therefore recommended that site specific static load testing be conducted from screw piles, if adopted, at
a minimum. Where tension or compression capacity developed in the footings is critical for the future
structure (e.g. resistance to uplift forces from high winds), then cyclic load tests (including measurement of
deflections under tension and compression cycles) should also be undertaken prior to construction.
Kentledge for static testing, or simulated cyclic loads, should prove the piles to a minimum of two times the
expected working load within tolerable deflections.

Footing design should also account for potential soil reactivity to be equivalent to Class M. It should be noted
that placement of reactive clay (which is not recommended) may result in a more severe equivalent site
classification, such as H1 or greater.



29 June 2022
Report No. 22227-001-Rev0                               12

Used in these records

About this file

File size
5.1 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

geotech and slope stability.pdf · 5.1 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.