                                                                                                                                                                    suitability for recharge is required and must be approved by the local authority.

                                                                                                                                                          7.2.7.2   Groundwater Table

                                                                                                                                                                    A second groundwater related design consideration is to ensure that the base of an infiltration system is
                                                                                                                                                                    always above the groundwater table. It is generally recommended that the base of the infiltration system
                                                                                                                                                                    be a minimum of 1.0 m above the seasonal high water table.

                                                                                                                                                                    If a shallow groundwater table is likely to be encountered, investigation of the seasonal variation of
                                                                                                                                                                    groundwater levels is essential. This should include an assessment of potential groundwater mounding
                                                                                                                                                                    (i.e. localised raising of the water table in the immediate vicinity of the infiltration system) that in shallow
                                                                                                                                                                    groundwater areas could cause problems with nearby structures.

                                                                                                                                                          7.2.8     Building Setbacks (Clearances)
                                                                                                                                                                    Infiltration systems should not be placed near building footings to avoid the influence of continually wet
                                                                                                      Chapter
                                                                                                   Chapter      7 – Infiltration
                                                                                                           7 – Infiltration      Measures
                                                                                                                            Measures                                sub-surface or greatly varying soil moisture content on the structural integrity. Australian Runoff Quality
  Calculation of Infiltration Area                                                                                                   INPUT                                           Project
                                                                                                                                                                    (Engineers Australia      Number:
                                                                                                                                                                                          2006)          2014019
                                                                                                                                                                                                recommends     minimum distances from structures and property boundaries (to
  Methodology following WSUD Guidelines for SEQ                                                                                      calculated                     protect possible   future buildings
                                                                                                                                                                                     Project:           in neighbouring
                                                                                                                                                                                              Elanda Street              properties) for different soil types. These values are
                                                                                                                                                                                                               Infiltration
                                                                                                                                                                    shown in Table 7-5.
                                                                                                                                     Goal Seek to Zero
   Permeability
    7.3.6.2Design
7.3.6.2       DesignEstimates
                     Storm
                  Storm        provided by Geotechnical Investigations
                           Approach
                        Approach
                                                                              m/s                         mm/s              mm/hr                                                    Table 7-5: Minimum Setback Distances (adapted from Engineers Australia 2006)
           Where     the design    objective
                                          for afor a particular  infiltration system   is peak  discharge attenuation  orcapture
                                                                                                                          the capture
  UpperWhere
        Limit  the  design
                 Permeability objective         particular infiltration  system   is peak  discharge
                                                                                            1.00E-01  attenuation or the
                                                                                                              1.00E+02             360000                                                                Saturated Hydraulic Conductivity                                          Minimum distance from structures
       and and   infiltration
           infiltration   of a ofparticular
                                   a particular  design
                                            design   stormstorm
                                                             event,event,
                                                                       thenthen  the design
                                                                             the design   stormstorm  approach
                                                                                                  approach may may    be adopted
                                                                                                                 be adopted   for for                                           Soil Type
  Lower Limit                                                                                                                                                                                                        (mm/hr)                                                           and property boundaries
           sizing the infiltration system. Use of the design storm approach must be approved by the local authority 9216
                 Permeability                                                               2.56E-03          2.56E+00
          sizing the infiltration system. Use of the design storm approach must be approved by the local authority                                                   Sands                                            >180                                                                      1.0 m
               for sizing
          for sizing        infiltration
                      infiltration       systems.
                                    systems.                                                                                                                         Sandy Loam                                     36 to 180                                                                   2.0 m
             Design
          Design     Storm
                 Storm           (Qdes(Q
                           Selection
                       Selection       ) des)                                                                                                                        Sandy Clay                                     3.6 to 36                                                                   4.0 m
                                                                                                                                                                     Medium to Heavy Clay                           0.0 to 3.6                                                                  5.0 m
        The The
              first first
                     stepstep  in design
                          in the   the design    storm
                                             storm     approach
                                                   approach        to sizing
                                                              to sizing      the infiltration
                                                                        the infiltration      system
                                                                                         system        is selecting
                                                                                                  is selecting      the design
                                                                                                               the design  storm storm
             for capture
        for capture     and and   infiltration.
                            infiltration.  ThisThis
                                                 mustmust
                                                      occuroccur  in consultation
                                                             in consultation  withwith   the local
                                                                                    the local      authority
                                                                                              authority      and generally
                                                                                                         and will will generally
                                                                                                                           relaterelate
  Designto Event
           3 to
              month    Method
                 3 monthARI ARI
                            and and
                                  1 year1 year
                                           ARI ARI  design
                                                design      storms.
                                                       storms.                                                                                                                                                            Hydrologic Effectiveness Method
                                                                                                                                                          7.2.9     Flow Management
  Vin (Rational   Method
           Detention
        Detention     VolumeQ100 x tc)
                  Volume
                                                                                                   11.44942 m3
                                                                                                                                                                                                                Adopted
                                                                                                                                                                    The following issues should be considered when         Hydrological
                                                                                                                                                                                                                   designing              Effectiveness
                                                                                                                                                                                                                             the flow control             = 100%
                                                                                                                                                                                                                                              structures within       (i.e 100% of the mean annual runoff is inflitrated)
                                                                                                                                                                                                                                                                infiltration
       The The  required
            required        ‘detention
                       ‘detention        volume’
                                    volume’   of anof infiltration
                                                       an infiltration   system
                                                                    system       is defined
                                                                             is defined     by difference
                                                                                        by the the difference  in inflow
                                                                                                          in inflow  and and                                        systems:
  Q100 outflow
       Volume
           outflowfrom      WBNM
                    (or infiltrated)
               (or infiltrated)      volumes
                                volumes        for duration
                                          for the  the duration
                                                              of a of a storm.
                                                                   storm.
                                                                                              11 m3                                                                                                                       From Figure 7-7
  Porosity of fill in trench (0.35 for gravel, 1.0 empty,0.95 for Atlantis
          The The  inflow
              inflow   volume   (V ) is(Vdetermined,
                            volume       ) is determined,
                                                                       0.95Flo-Trench)
                                                            in accordance
                                                       in accordance   withwith Section
                                                                            Section     6 (Detention
                                                                                    6 (Detention     Basins)
                                                                                                 Basins)     of QUDM,
                                                                                                         of QUDM,      as the
                                                                                                                  as the
                                                                                                                                                                    ƒ For large scale systems (i.e. infiltration basins),
                                                                                                                                                                                                                     % Catchment      Area
                                                                                                                                                                                                                          the surface of     Required area’
                                                                                                                                                                                                                                         the ‘infiltration = must be flat or as                                                                                          1.50%
                                           i   i                                                                                                                       close to this as possible to ensure uniform distribution of flow and to prevent hydraulic overloading on
              product
          product       of design
                   of the  the design
                                   storm  storm
                                             flowflow
                                                  and and  the storm
                                                      the storm       duration:
                                                                  duration:                                                                                            a small portion of the ‘infiltration area’.
  W=                                                                                     0.80 m                  2x Double Flo-Tanks (side by side)                                             Catchment                                           Area (ha)                                                                           Infiltration Volume (m3)
  L=                                                                                     8.03 m                  calculated from Ainf         ƒ For gravel filled infiltration systems, flow should
                                                                                                                                                                                                Yard
                                                                                                                                                                                                      be delivered to the ‘detention volume’ via a perforated
                                                                                                                                                                                                                                                      0.025                                                                                         3.75
                  D ˜D
      Vi VQi desQ˜des                                                                                    Equation
                                                                                                     Equation 7.1 7.1                            pipe(s) network that is located and sized to convey the design flow into the infiltration systems and
  d=                                                                                      0.9 m                  Double Flo-Tank                                                                Lot (lessarea.
                                                                                                                                                 allow distribution of flows across the entire infiltration  to street)                              0.0416                                                                                         6.24 7 – Infiltration Measures
                                                                                                                                                                                                                                                                                                                                                   Chapter

  P=                                                                                     17.7 m                  calculated from dimensions
         Where        Vi Vi = inflow
                                   = inflow  volume    (for storm       D) (mD3)) (m3)
                                                                    duration
                                                                                                                                              ƒ  Where possible, ‘above design’ flows will bypass the infiltration systems. This can be achieved in a
  U = Where                             volume    (for storm   duration                   0.5                    from Table 7-6                  number of ways. For smaller applications, an overflow pipe or pit, which is connected to the
                      QdesQdes = design                                                                                                          downstream drainage system, can be used. For larger applications, a discharge control pit can be
  D=                               = design  storm
                                         storm  flowflow    for sizing
                                                       for sizing      as outlined
                                                                  as outlined       in Section
                                                                               in Section    5 7.3.5
                                                                                          7.3.5 mins              0.08333333 hr
                                                                                                                                                                       located upstream of the infiltration system. This will function much like the inlet zone of a constructed
                                                       (Rational
                                                   (Rational       , Q=, CIA/360
                                                                 Method
                                                             Method      Q= CIA/360  (m3/s)
                                                                                 (m3/s)                                                                                wetland to regulate flows (1 year ARI) into the infiltration systems and bypass above design flows (> 1
                                                                                                                                                                                                                                              Infiltration Hydrologic Effectiveness (Depth = 1m, Porosity = 1.0) - Nambour
  Vo =                  D D = storm          duration
                                       = storm           (hrs (hrs
                                                   duration    x 3600  s/hr)s/hr)
                                                                    x 3600                        5.52                       from Eqn 7.2                              year ARI).
  Substituting  Eqnin 7.2
       As outlined
           As outlined   in into
                       Section    Eqn
                            Section     7.3
                                 7.3.5.2,  if the
                                     7.3.5.2,       infiltration
                                                 if the            system
                                                          infiltration      is toisform
                                                                       system              part part
                                                                                      to form    of a ofdetention basinbasin
                                                                                                          a detention   or if ortheif the                                                                                                                             100

  Vd = catchment  areaarea
           catchment    to the
                             to system   is large
                                the system          (> 50(>ha)
                                               is large       50 then  a fulla flood
                                                                  ha) then             routing
                                                                                full flood        5.77
                                                                                               computation
                                                                                            routing computationmethod  should
                                                                                                                   method    Atlantis
                                                                                                                                 be be Flo-Tank (double) =
                                                                                                                            should                                             25
                                                                                                                                                                       WSUD Technical Design Guidelines for South East Queensland90
                                                                                                                                                                                                                                  – Version 1 June 2006                                                                  7-8
          usedused
               to estimate design
                   to estimate    flows.
                               design flows.
                                                                                                                                                                                                                                                                       80
  Ainf =Outflow from
           Outflow    the Goal
                  Solve
                    from  infiltration
                                  Seek system
                                         for
                          the infiltration     is viais the
                                             Area
                                           system        via base and and
                                                             the base sidessides
                                                                             of the
                                                                                  of infiltration
                                                                                             6.42media
                                                                                                     m2
                                                                                      the infiltration  and is
                                                                                                       media   dependent
                                                                                                             and     Atlantis Flo-Tank (double) =
                                                                                                                 is dependent                                                  23
        on the   areaarea
             on the    and and
                            depth of the
                                depth       structure.
                                        of the          In computing
                                                 structure.            the infiltration
                                                            In computing                  fromfrom
                                                                           the infiltration      the walls    of anofinfiltration
                                                                                                       the walls      an infiltration




                                                                                                                                                                                                                                       Hydrologic Effectiveness (%)
                                                                                                                                                                                                                                                                       70
        system,    Australian
             system,          Runoff
                       Australian     Quality
                                  Runoff        (Engineers
                                           Quality           Australia
                                                     (Engineers        2006)
                                                                 Australia   suggests
                                                                           2006)   suggeststhat that
                                                                                                 pressure    is hydrostatically
                                                                                                       pressure   is hydrostatically
  Goal Seek
        distributed  and and
             distributed thusthus
                               equalequal
                                     to half the depth
                                          to half        of water
                                                  the depth       overover
                                                             of water  the bed   of the
                                                                           the bed        the 0.00
                                                                                      of infiltration  system:
                                                                                               infiltration system:                                   ADOPT                    25                                                                                      60


                                                                                                                                                                                                                                                                       50
                  ª ª § d ·º dUº˜ KU ˜ K˜ D ˜ D
                                                                                                               2.73 modules/m3
             Vo Vo«A inf«Ainf¨ P˜ §¨ P¸»˜ ˜ ·¸» ˜ sat sat                                                        Equation
                                                                                                                      15.76 7.2 7.2
                                                                                                                       Equation                                                                                                                                        40
                  ¬ ¬ © ©2 ¹¼ 2 ¹¼10001000                                                                                                                                                                                                                                                                                                                3.6mm/hr hydraulic conductivity
                                                                                                      Chapter 7 – Infiltration Measures                                                                                                                                                                                                                   10mm/hr hydraulic conductivity
                                                                                                                                                                                                                                                                       30
                                                                                                                                                                                                                                                                                                                                                          36mm/hr hydraulic conductivity
                                                                                                                                                                                                                                                                                                                                                          100mm/hr hydraulic conductivity
          Where Vo Vo
            Where                 = outflow volume
                                      = outflow     (for storm
                                                volume          duration
                                                         (for storm      D) (mD)3) (m3)
                                                                    duration                                                                                                                                                                                           20                                                                                 360mm/hr hydraulic conductivity
                                                                                                                                                                                                                                                                                                                                                          1800mm/hr hydraulic conductivity
                       Ksat Ksat = saturated hydraulic
                                     = saturated       conductivity
                                                 hydraulic          (mm/hr)
                                                           conductivity     as provided
                                                                        (mm/hr)         in Step
                                                                                as provided      1. 1.
                                                                                             in Step                                                                                                                                                                                                                                                      3600mm/hr hydraulic conductivity
                                                                                                                                                                                                                                                                       10
                                                            2
                       Ainf Ainf = infiltration areaarea
                                     = infiltration  (m ) (m )   2

                                                                                                                                                                                                                                                                        0
                       P
                      P = perimeter         length
                                  = perimeter        of the
                                                  length  of infiltration    area area
                                                              the infiltration      (m) (m)                                                                                                                                                                                 0             0.5                 1                  1.5                   2                        2.5                  3
       Where              Vd           = required detention volume (m3)
                                                                                                                                                                                                                                                                                                     Size of 'Infiltration Area' (as a % of Total Catchment Area)
                 d d = depth           of the
                                            of infiltration  system      (m) (m)
                          Vi = depth            the infiltration
                                       = inflow volume (m3)
                                                                    system
                 U U = soil          hydraulic conductivity       moderating       factor (see Table 7.5)
                          Vo = soil= hydraulic        conductivity
                                          outflow volume          (m3)moderating factor (see Table 7.5)
                                                                                                                                                                                                                              Figure 7-7: Hydrologic Effectiveness of ‘Detention Storage’ for Infiltration Systems for the North Coast (Depth = 1 m and Porosity = 1.0)
                 D D = storm           duration
                                  = storm          (hrs)(hrs)
                                             duration
                          p            = porosity     (void = 1, gravel = 0.35)
         Thus,  the required    detention   volume     (Vd) of  an   infiltration   system   can be Chapter 7 as
                                                                                                               – Infiltration Measures
              Thus, the  required    detention    volume
       Computation of the required storage will need        (V d ) of  an  infiltration
                                                                         to be carried  system   cancomputed
                                                                                            out for  be computed
                                                                                                    the
                                                                                                                  follows:
                                                                                                        full range as
                                                                                                                    of follows:
                                                                                                                        probabilistic storm                                                                                                                                         Infiltration Hydrologic Effectiveness (Depth = 1m, Porosity = 0.35) - Nambour
       durations, ranging from 6 minutes to 72 hours. The critical storm event is that which results in the
       highest required storage. A spreadsheet application (using equations 7.1 to 7.3) is the most convenient                                                                                                                                                        100
                Vi VVo V
       wayVdofVdoing  ithis. oIt is important to note that some storm events result in double peaks                  Equation
                                                                                                                         in the7.3
                                                                                                                                hyetograph
                                                                                                                          Equation 7.3
                d p
                        p storm and these may affect the size of detention storage required.
       for the particular
                                                                                                                                                                                                                                                                       90


       Soil Hydraulic Conductivity Moderating Factor                                                                                                                                                                                                                   80
                Where              Vd          = required detention volume (m3)
       Soil is inherently non-homogeneous and field tests can often misrepresent the areal hydraulic
                                                                                                                                                                                                                                  Hydrologic Effectiveness (%)




                                                                                                                                                                                                                                                                       70
                                                                       3
              WSUD
       conductivity    Technical
                    WSUD           Vinto
                            a soilDesign
                         of Technical          =Guidelines
                                           which
                                     i Design    inflow
                                           Guidelines  forvolume
                                                           South
                                                   stormwater       (m
                                                                  East
                                                             for South   ) be
                                                                     isQueensland
                                                                        to
                                                                       East          – Version
                                                                                 infiltrated.
                                                                              Queensland       1Field
                                                                                                  June
                                                                                           – Version   2006 2006
                                                                                                     1 experience
                                                                                                       June          suggests that field 7-16
                                                                                                                                             tests
                                                                                                                                              7-16
       of ‘point’ soil hydraulic   Vo   conductivity
                                               = outflow(asvolume
                                                               defined(m3)by Step 1) can often under estimate the areal hydraulic
                                                                                                                                                                                                                                                                       60

       conductivity of clay soils and over estimate in sandy soils. As a result, Australian Runoff Quality
       (Engineers Australia 2005)  p           = porosity (void
                                             recommends            = 1,moderation
                                                                 that     gravel = 0.35)factors for hydraulic conductivities determined                                                                                                                                50

       from field test be applied as shown in Table 7-6.
                Computation of the required storage will need to be carried out for the full range of probabilistic storm                                                                                                                                              40
           Tabledurations,   rangingFactors
                  7-6: Moderation      from to 6 Convert
                                                 minutes Pointto 72tohours.     The critical storm
                                                                       Areal Conductivities            event is that
                                                                                                (after Engineers      which2005)
                                                                                                                   Australia   results in the
                                                                                                                                                                                                                                                                                                                                                                3.6mm/hr hydraulic conductivity
                highest required storage. A spreadsheet application (using equations 7.1 to 7.3) is the most convenient                                                                                                                                                30
                                                                                   Moderation Factor (U)                                                                                                                                                                                                                                                        10mm/hr hydraulic conductivity
                way of doing this.    It is important to note that some storm events result in double peaks in the hyetograph
                                 Soil Type                                                                                                                                                                                                                                                                                                                      36mm/hr hydraulic conductivity
                                                                          (to convert “point” Ksat to areal Ksat)                                                                                                                                                      20
                for the particular storm and these may affect the size of detention storage required.                                                                                                                                                                                                                                                           100mm/hr hydraulic conductivity
                  Sandy soil                                                                    0.5                                                                                                                                                                                                                                                             360mm/hr hydraulic conductivity
                  Sandy
                Soil      clay Conductivity Moderating Factor
                      Hydraulic                                                                 1.0                                                                                                                                                                    10                                                                                       1800mm/hr hydraulic conductivity
                                                                                                                                                                                                                                                                                                                                                                3600mm/hr hydraulic conductivity
                  Medium and Heavy Clay                                                         2.0
                Soil is inherently non-homogeneous and field tests can often misrepresent the areal hydraulic                                                                                                                                                           0
       Emptying       Time of a soil into which stormwater is to be infiltrated. Field experience suggests that field tests
                conductivity                                                                                                                                                                                                                                                0             0.5                1                   1.5                  2                         2.5                  3
                                                                                                                                                                                                                                                                                                     Size of 'Infiltration Area' (as a % of Total Catchment Area)
       Emptying time is defined as the time taken to fully empty aoften
                of  ‘point’ soil hydraulic    conductivity    (as defined     by Step   1) can          under estimate
                                                                                                    detention    volumethe    areal hydraulic
                                                                                                                           associated    with an
                conductivity
       infiltration    systemoffollowing
                                    clay soilstheandcessation
                                                        over estimate        in sandy
                                                                    of rainfall.   Thissoils.
                                                                                           is anAsimportant      Australian
                                                                                                      a result, design       Runoff Quality
                                                                                                                          consideration    as the
                (Engineers
       computation            Australia associated
                          procedure       2005) recommends         that moderation
                                                         with Equation                   factors that
                                                                               7.3 assumes         for hydraulic  conductivities
                                                                                                         the storage    is empty determined
                                                                                                                                     prior to the                                                                              Figure 7-8: Hydrologic Effectiveness of ‘Detention Storage’ for Infiltration Systems the North Coast (Depth = 1 m and Porosity = 0.35)
                from field testofbethe
       commencement                  applied   as shown
                                           design     storm in Table
                                                                 event.7-6.Australian Runoff Quality (Engineers Australia 2006)
       suggestsTable
                  an 7-6:
                     emptying     time
                          Moderation     of the
                                     Factors     detention
                                             to Convert       storage
                                                        Point to         of infiltration
                                                                 Areal Conductivities (aftersystems
                                                                                             Engineers to vary 2005)
                                                                                                       Australia from 12 hours to 84
       hours. For detention basins (surface systems) the emptying time must be limited to 72 hours to reduce
       the risk of mosquito breeding.                                     Moderation Factor (U)
                                  Soil Type
                                                                   (to convert “point” Ksat to areal Ksat)
       Emptying time     is computed
                     Sandy   soil        simply as the ratio of the volume of         0.5water in temporary storage (dimension
       of storage x porosity)
                     Sandy clayto the infiltration rate (hydraulic conductivity1.0x infiltration area):
                             Medium and Heavy Clay                                           2.0

                 Emptying
                1000  ˜ Vd Time
                            ˜P ˜ p
        te                                                                                           Equation 7.4                                                                                                                                                       WSUD Technical Design Guidelines for South East Queensland – Version 1 June 2006                                           7-13
                  A inf ˜ K sat
                 Emptying   time is defined as the time taken to fully empty a detention volume associated with an
            infiltration system following the cessation of rainfall. This is an important design consideration as the
            computation procedure associated with Equation 7.3 assumes that the storage is empty prior to the
       Where             te       = emptying time (hours)
            commencement       of the design storm event. Australian Runoff Quality (Engineers Australia 2006)
                                                           3
            suggests anVdemptying = time of thevolume
                                     detention  detention
                                                        (mstorage
                                                             )      of infiltration systems to vary from 12 hours to 84
            hours. For detention basins (surface systems) the emptying time must be limited to 72 hours to reduce
                         P        = perimeter length of the infiltration area (m)
            the risk of mosquito breeding.
                             Ainf       = infiltration area (m2)
                 Emptying time    is computed simply as the ratio of the volume of water in temporary storage (dimension
                 of storage xKporosity)
                              sat       =tosaturated    hydraulic
                                            the infiltration        conductivity
                                                             rate (hydraulic      (mm/hr)
                                                                             conductivity    as provided
                                                                                          x infiltration     in Step 1
                                                                                                         area):
                                 p             = porosity (void = 1, gravel = 0.35)

                           1000 ˜ Vd ˜ P ˜ p
                  te                                                                                                    Equation 7.4
                             A inf ˜ K sat


                 Where                 te           = emptying time (hours)

                                       Vd           = detention volume (m3)
             WSUD Technical Design Guidelines for South East Queensland – Version 1 June 2006                                                  7-17
                                       P            = perimeter length of the infiltration area (m)

                                       Ainf         = infiltration area (m2)

                                       Ksat         = saturated hydraulic conductivity (mm/hr) as provided in Step 1

                                       p            = porosity (void = 1, gravel = 0.35)




                       WSUD Technical Design Guidelines for South East Queensland – Version 1 June 2006                                 7-17

Used in these records

About this file

File size
6.7 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Tod Consulting Stormwater Plans v2.pdf · 6.7 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.