Technical Note in response to action notice

of 8

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

                                                               Ref No 20648-R1 – Rev 2
DRIVEWAY

A second access to the lot was constructed to facilitate the installation of the new
prefabricated dwelling. We have undertaken an inspection of this access and it
generally complies with Council standard drawing RS-056 for rural access
crossovers with a few minor exceptions -copy of the standard drawing is attached to
the back of this report. We have been informed that the access was constructed
approximately 2 years ago.

The access is approx. 5.3m wide at the narrowest point and is constructed over a
375mm diameter PVC Stormpro pipe – set back approx. 3m back from the road
edge. There is 500mm of cover over the pipe. The headwalls are constructed from
grouted rock. The access pavement is unsealed gravel more than 125mm thick. The
inlet and outlet to the culvert contains some un-grouted rock but there is no evidence
of scouring, indicating the scour protection unnecessary in this case which is
understandable as the road drain is on a very flat grade. Refer photos below:




                                     Page 4 of 8
Log in to download the original file

Technical Note in response to action notice.pdf · 1.1 MB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.