RFI - Revised Engineering Plans · MCU24/0153

of 24

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn

Original PDF page 2, section 1. The text section number identifies this passage in the reader.

GENERAL NOTES                                                                                      21. NO WORKS ARE TO BE UNDERTAKEN ON LAND OUTSIDE OF THE SITE BOUNDARY                                                           h.      PAVEMENT REINFORCING
                                                                                                       WITHOUT FORMAL APPROVAL BY THE OWNER/CUSTODIAN OF THAT LAND INCLUDING BUT
1.    ALL DIMENSIONS SHOWN ARE IN METERS UNLESS OTHERWISE SHOWN.                                                                                                                                                                    i.      PAVEMENT PRIOR TO SEALING (PRESEAL)
                                                                                                       NOT LIMITED TO PRIVATE PROPERTY, ROAD RESERVE, PARKS/OPENSPACE, EASEMENTS.
2.    ALL SETOUT ON SITE IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR                                                                                                                                                   j.      RETAINING WALL FOOTING REINFORCING
                                                                                                   22. THE CONTRACTOR SHALL HAVE AN APPROVED SET OF CONSTRUCTION DRAWINGS AND
      TO ALLOW FOR ALL MEANS NECESSARY TO ACCURATELY SETOUT THE WORKS.                                 APPROVALS ON SITE AT ALL TIMES.                                                                                              k.      RETAINING WALL BLOCKWORK PRIOR TO CORE FILL
3.    ALL WORKS TO BE CONSTRUCTED IN ACCORDANCE WITH PROJECT SPECIFICATIONS AND                    23. ALL WATER AND SEWER RETICULATION WORKS TO BE CONSTRUCTED IN ACCORDANCE                                                       l.      STEEL REINFORCEMENT OF CONCRETE STRUCTURES
      WHERE FURTHER DETAILS ARE REQUIRED THE CONTRACTOR SHALL REFER TO NOOSA                           WITH THE SEQ WATER SUPPLY AND SEWERAGE DESIGN AND CONSTRUCTION CODE                                                          m.      PRACTICAL COMPLETION
      SHIRE COUNCIL DEVELOPMENT GUIDELINES, LOCAL WATER AUTHORITY GUIDELINES,                          (2013).
      ASSOCIATED STANDARD DRAWINGS AND SPECIFICATIONS U.N.O.                                                                                                                                                                        n.      ON MAINTENANCE
3.    SHOULD ANY OF THE CONSTRUCTED WORKS BE CONSTRUCTED OUTSIDE OF THE                                                                                                                                                             o.      OFF MAINTENANCE
      TOLERANCES SPECIFIED WITHIN THE PROJECT SPECIFICATION AND LOCAL AUTHORITY
                                                                                                   STANDARD SIGNS AND LINE MARKING NOTES
                                                                                                                                                                                                                                    p.      ANY OTHER INSPECTION AS SPECIFIED BY LOCAL COUNCIL (REFER DEVELOPMENT
      REQUIREMENTS, THE CONTRACTOR WILL RECTIFY AT THEIR COST INCLUSIVE OF ANY                     1.      GENERAL
                                                                                                                                                                                                                                            APPROVAL)
      ADDITIONAL COSTS INCURRED BY RECOR.                                                            1.1.     ALL SIGNS AND PAVEMENT MARKING IS TO BE IN ACCORDANCE WITH THE
 4.   EXISTING SERVICES HAVE BEEN PLOTTED FROM SUPPLIED DATA AND AS SUCH THEIR                                QUEENSLAND TRANSPORT MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES
      ACCURACY CANNOT BE GUARANTEED. NO RESPONSIBILITY IS TAKEN BY RECOR OR THE                               (CURRENT EDITION).
      PRINCIPAL FOR THE ACCURACY AND COMPLETENESS OF THIS INFORMATION. IT IS THE                   2. SIGNS
      RESPONSIBILITY OF THE CONTRACTOR TO ACCURATELY ESTABLISH THE LOCATION AND                       2.1.    ALL SIGNS TO BE REFLECTORISED CLASS 1 TO AS1906.1:2007 UNLESS NOTED
      LEVEL OF ALL EXISTING SERVICES PRIOR THE COMMENCEMENT OF ANY WORKS. ANY                                 OTHERWISE.
      DISCREPANCIES SHALL BE REPORTED TO THE SUPERINTENDENT. CONTRACTOR TO                            2.2.    SIGNS ARE TO BE INSTALLED WITH THE FOLLOWING CLEARANCES TO EDGE OF SIGN:
      LOCATE AND PROTECT SERVICES AS REQUIRED DURING PROPOSED WORKS.                                          LOCATION CLEARANCE NO KERB 600 BEHIND GUIDE POSTS BARRIER KERB 300 FROM
5.    THE CONTRACTOR IS TO CHECK THROUGH LOCATING, POTHOLING AND SURVEY ALL                                   FACE MOUNTABLE KERB 500 FROM FACE OF KERB.
      CRITICAL CONNECTION POINTS FOR ALL CIVIL WORKS SHOWN ON THE DRAWINGS                            2.3.    PARKING CONTROL SIGNS TO BE MOUNTED TO FACE APPROACHING TRAFFIC AT 45°
      INCLUDING ANY POTENTIAL EXISTING SERVICES CLASHES PRIOR TO COMMENCEMENT OF                              TO KERB OR CARRIAGEWAY EDGE. ALL OTHER SIGNS TO BE TURNED AWAY BY 5°
      CIVIL WORKS. CONTRACTOR TO IMMEDIATELY REPORT ANY DISCREPANCIES TO RECOR                                FROM THE NORMAL TO APPROACHING HEADLIGHT.
      AND AWAIT FORMAL DIRECTION PRIOR TO COMMENCING CIVIL WORKS.                                  3. SIGN SUPPORTS
6.    ON COMPLETION OF SERVICES INSTALLATION, ALL DISTURBED AREAS SHALL BE                            3.1.     SLEEVED SIGNS SUPPORTS ARE TO BE PROVIDED IN ALL AREAS WHERE THEY ARE
      RESTORED TO ORIGINAL LEVEL, INCLUDING KERBS, FOOTPATHS, CONCRETE AREAS,                                 IN A PAVED SURFACE.
      GRAVEL AREAS, GRASSED AREAS AND ROAD PAVEMENTS.                                              4. LINEMARKING
                                                                                                      4.1.    REDUNDANT LINEMARKING IS TO BE GROUND OFF.
7.    CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY DAMAGE TO
                                                                                                      4.2.    THERMOPLASTIC LINEMARKING TO BE USED FOR ALL CONCRETE.
      AUTHORITY/COUNCIL'S INFRASTRUCTURE. SUCH REPAIR OR REINSTATEMENT TO BE
      CARRIED OUT IMMEDIATELY TO THE SATISFACTION OF INFRASTRUCTURE
      OWNER/MANAGER / AUTHORITY/COUNCIL.                                                           JOINTING NOTES
8.    CONTRACTOR TO UNDERTAKE ALL WORKS IN ACCORDANCE WITH ALL WORKPLACE
      HEALTH AND SAFETY REQUIREMENTS.                                                              1.     ALL JOINTING AND CONCRETE TO BE IN ACCORDANCE WITH THE REQUIREMENTS OF
                                                                                                          AS3727.1:2016.
9.    WHERE ANY EXCAVATION OR CONSTRUCTION WORKS ARE TO BE IN CLOSE PROXIMITY                      2.     SAW CUT JOINTS MUST BE:
      TO NEIGHBOURING LOT BOUNDARIES OR INFRASTRUCTURE, CONTRACTOR TO ALLOW IN
      SCOPE OF WORKS TO PROVIDE ALL MEASURES NECESSARY TO ENSURE THE INTEGRITY                       2.1.      BETWEEN 41 AND 31 OF CONCRETE PAVEMENT DEPTHS.
      OF EXISTING BOUNDARIES AND INFRASTRUCTURE. THIS MAY INCLUDE THE USE OF LOW                     2.2.     CLEARED OF ANY DEBRIS FROM THE CUTTING METHOD.
      VIBRATION EQUIPMENT, TRENCH SHORING ETC AS REQUIRED.                                           2.3.     PERFORMED WITHIN 6 TO 12 HOURS OF FINISHING CONCRETE POURS.
10. PRIOR TO THE CONTRACTOR COMMENCING ANY WORKS DETAILED ON THESE DRAWINGS,                       3. DOWELL BARS MUST BE INSTALLED EXACTLY 90° TO THE FACE OF JOINT TO ALLOW
    THE CONTRACTOR IS TO NOTIFY RECOR AND RECEIVE WRITTEN CONFIRMATION THAT                              EXPANSION AND CONTRACTION MOVEMENTS.
    WORKS CAN COMMENCE.                                                                            4. JOINTING LAYOUT TO BE CONFIRMED BY SUPERINTENDANT PRIOR TO CONSTRUCTION
                                                                                                         COMMENCING. LAYOUT SHOULD AVOID ACUTE ANGLES IN THE CONCRETE SLAB AND
11. CONTRACTOR TO PROVIDE AS CONSTRUCTED DRAWINGS FOR ALL CONSTRUCTED                                     AVOID MISMATCHED JOINTS.
    WORKS IN ACCORDANCE WITH LOCAL GOVERNMENT REQUIREMENTS. UNLESS
                                                                                                   5. JOINT SEALANTS WHERE USED MUST ADHERE TO SIDE OF JOINT FACES ONLY AND SHALL
    OTHERWISE ADVISED BY RECOR CONTRACTOR TO NOTE COUNCILS ADAC
                                                                                                         NOT EXTEND ABOVE SIDES OF JOINTS ONTO THE SLAB SURFACE.
    REQUIREMENTS.
                                                                                                   6. DOWEL BARS ARE TO BE
12. CONTRACTOR TO UNDERTAKE ALL WORKS IN ACCORDANCE WITH RELEVANT                                    6.1.     FOR 100MM THICK SLAB, 12MM Ø OF LENGTH 300MM AND SPACED AT 400MM
    APPROVALS.                                                                                                CENTRES
13. CONTRACTOR TO ALLOW TO LIASE/CO-ORDINATE WITH ELECTRICAL, LANDSCAPE AND                          6.2.     FOR 125MM THICK SLAB, 16MM Ø OF LENGTH 350MM AND SPACED AT 300MM
    OTHER SERVICE CONTRACTORS THROUGHOUT CIVIL CONSTRUCTION.                                                  CENTRES
14. CONTRACTOR TO ORGANISE ALL DEMOLITION PERMITS PRIOR DEMOLITION WORKS                             6.3.     FOR 150MM THICK SLAB, 20MM Ø OF LENGTH 400MM AND SPACED AT 300MM
    COMMENCING ON SITE.                                                                                       CENTRES

15. CONTRACTOR TO ALLOW TO DEMOLISH ALL EXISTING STRUCTURES, ROADS AND
    SERVICES WITHIN LIMIT OF WORKS AND REMOVE FROM SITE U.N.O.                                     INSPECTIONS:
                                                                                                   THE FOLLOWING INSPECTIONS MUST BE COMPLETED BY RECOR ENGINEERS BEFORE
16. CONTRACTOR TO UNDERTAKE DILAPIDATION REPORT FOR ADJOINING PROPERTIES AND                       ENGINEERING CERTIFICATION WILL BE ISSUED. THE CONTRACTOR IS TO PROVIDE A MINIMUM
    COUNCIL ROADS AND VERGES PRIOR TO COMMENCEMENT OF ANY WORKS ON SITE.                           OF 72 HOURS NOTICE TO RECOR FOR REQUIRED INSPECTIONS. SHOULD THE
17. CONTRACTOR TO CLEAR AND GRUB ALL VEGETATION ON SITE AS IDENTIFIED IN THE                       CONTRACTOR FAIL TO REQUEST AN INSPECTION, THE CONTRACTOR WILL BE RESPONSIBLE
    APPROVED VEGETATION MANAGEMENT PLAN. CONTRACTOR TO ENSURE ALL TREE                             FOR ALL COSTS TO ALLOW FOR THE WORKS TO BE INSPECTED TO THE SATISFACTION OF
    ROOTS AND STUMPS ARE COMPLETELY REMOVED AND BACKFILLED TO LEVEL 1                              RECOR. ANY INSPECTIONS THAT FAIL ARE TO BE RE-INSPECTED WITH ALL REINSPECTION
    SUPERVISION. CONTRACTOR TO ALLOW TO MULCH ALL CLEARED VEGETATION AND                           COSTS TO BE PAID BY THE CONTRACTOR.
    STOCKPILE ON SITE OR REMOVE FROM SITE AS DIRECTED.
                                                                                                   a.     PRESTART
18. DRAWINGS TO BE READ IN CONJUNCTION WITH ARCHITECT, SURVEYOR, HYDRAULICS,
    ETC. CONSULTANT AND CONTRACTOR DRAWINGS.                                                       b.     EARTHWORKS - FINAL STRIPPING OF TOPSOIL, INSTALLATION OF SEDIMENT AND EROSION
                                                                                                          CONTROL MEASURES UNSUITABLE GROUND
19. CONTRACTOR TO PREPARE AND HAVE APPROVED BY RELEVANT AUTHORITY: ROAD
    OPENING PERMIT AND TRAFFIC MANAGEMENT PLAN FOR ALL WORKS WITHIN COUNCIL                        c.     SIDE AND CUT OFF DRAINS
    ROAD RESERVES. CONTRACTOR TO ALLOW FOR ALL COSTS ASSOCIATED WITH                               d.     STORMWATER PIPE LAID ON BEDDING PRIOR TO BACKFILL
    IMPLEMENTATION OF THE TMP.
                                                                                                   e.     STORMWATER TRENCH BACKFILLED PRIOR TO PAVEMENT PLACEMENT
20. ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH ALL LOCAL AUTHORITY
    APPROVALS RECEIVED FOR THE PROJECT AND IN ACCORDANCE WITH OPW APPROVALS                        f.     STORMWATER STRUCTURE BASE SLABS
    BY COUNCIL.                                                                                    g.     PAVEMENT SUBGRADE




                                                                                    North Point   Approved                                                                                                                                                                                                           Project Address                        Sheet Title

                                                                                                                                                                                                                                                                                                                                                            GENERAL NOTES
                                                                                                  E WHITMORE                                                                                                                                                                                                          51 ELANDA STREET SUNSHINE BEACH QLD
                                                                                                  RPEQ 31423

                                                                                                  For and on behalf of RECOR Pty Ltd.
                                                                                                  Scale                                                                                                 ENGINEERING + PROJECT MANAGEMENT                                                                             Client Details                         Project Name                         Sheet Size
                                                                                                                                                                                                        SUNSHINE COAST | BRISBANE | SYDNEY
                                                                                                                                                                                                       www.recorconsulting.com | ABN 89 647 469 707                                                                   ARCHEND                               PROPOSED MULTIPLE RESIDENCE            A1
 A    21/03/25   ISSUE FOR APPROVAL                               TVZ     AY                                                                                       COPYRIGHT © This drawing is subject to copyright in accordance with the agreement between RECOR Pty Ltd and RECOR's client. This                                                         Project Number        Sheet Number    Revision

                                                                                                                                                                                                                                                                                                                                                                                  002               A
                                                                                                                                                                   drawing shall only be used for this specific project. This drawing shall not be used for construction until marked as 'Issued For Construction'

Rev    Date               Revision Description                  Drawn Check                                            DO NOT SCALE, IF IN DOUBT ASK                                                                          in the revision description.                                                                                                  20240127

Used in these records

About this file

File size
5.0 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

RFI - Revised Engineering Plans.pdf · 5.0 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.