RFI - Revised Engineering Plans · MCU24/0153
Plans and drawings: the text below has words only, no drawings.
Original PDF page 2, section 1. The text section number identifies this passage in the reader.
GENERAL NOTES 21. NO WORKS ARE TO BE UNDERTAKEN ON LAND OUTSIDE OF THE SITE BOUNDARY h. PAVEMENT REINFORCING
WITHOUT FORMAL APPROVAL BY THE OWNER/CUSTODIAN OF THAT LAND INCLUDING BUT
1. ALL DIMENSIONS SHOWN ARE IN METERS UNLESS OTHERWISE SHOWN. i. PAVEMENT PRIOR TO SEALING (PRESEAL)
NOT LIMITED TO PRIVATE PROPERTY, ROAD RESERVE, PARKS/OPENSPACE, EASEMENTS.
2. ALL SETOUT ON SITE IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR j. RETAINING WALL FOOTING REINFORCING
22. THE CONTRACTOR SHALL HAVE AN APPROVED SET OF CONSTRUCTION DRAWINGS AND
TO ALLOW FOR ALL MEANS NECESSARY TO ACCURATELY SETOUT THE WORKS. APPROVALS ON SITE AT ALL TIMES. k. RETAINING WALL BLOCKWORK PRIOR TO CORE FILL
3. ALL WORKS TO BE CONSTRUCTED IN ACCORDANCE WITH PROJECT SPECIFICATIONS AND 23. ALL WATER AND SEWER RETICULATION WORKS TO BE CONSTRUCTED IN ACCORDANCE l. STEEL REINFORCEMENT OF CONCRETE STRUCTURES
WHERE FURTHER DETAILS ARE REQUIRED THE CONTRACTOR SHALL REFER TO NOOSA WITH THE SEQ WATER SUPPLY AND SEWERAGE DESIGN AND CONSTRUCTION CODE m. PRACTICAL COMPLETION
SHIRE COUNCIL DEVELOPMENT GUIDELINES, LOCAL WATER AUTHORITY GUIDELINES, (2013).
ASSOCIATED STANDARD DRAWINGS AND SPECIFICATIONS U.N.O. n. ON MAINTENANCE
3. SHOULD ANY OF THE CONSTRUCTED WORKS BE CONSTRUCTED OUTSIDE OF THE o. OFF MAINTENANCE
TOLERANCES SPECIFIED WITHIN THE PROJECT SPECIFICATION AND LOCAL AUTHORITY
STANDARD SIGNS AND LINE MARKING NOTES
p. ANY OTHER INSPECTION AS SPECIFIED BY LOCAL COUNCIL (REFER DEVELOPMENT
REQUIREMENTS, THE CONTRACTOR WILL RECTIFY AT THEIR COST INCLUSIVE OF ANY 1. GENERAL
APPROVAL)
ADDITIONAL COSTS INCURRED BY RECOR. 1.1. ALL SIGNS AND PAVEMENT MARKING IS TO BE IN ACCORDANCE WITH THE
4. EXISTING SERVICES HAVE BEEN PLOTTED FROM SUPPLIED DATA AND AS SUCH THEIR QUEENSLAND TRANSPORT MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES
ACCURACY CANNOT BE GUARANTEED. NO RESPONSIBILITY IS TAKEN BY RECOR OR THE (CURRENT EDITION).
PRINCIPAL FOR THE ACCURACY AND COMPLETENESS OF THIS INFORMATION. IT IS THE 2. SIGNS
RESPONSIBILITY OF THE CONTRACTOR TO ACCURATELY ESTABLISH THE LOCATION AND 2.1. ALL SIGNS TO BE REFLECTORISED CLASS 1 TO AS1906.1:2007 UNLESS NOTED
LEVEL OF ALL EXISTING SERVICES PRIOR THE COMMENCEMENT OF ANY WORKS. ANY OTHERWISE.
DISCREPANCIES SHALL BE REPORTED TO THE SUPERINTENDENT. CONTRACTOR TO 2.2. SIGNS ARE TO BE INSTALLED WITH THE FOLLOWING CLEARANCES TO EDGE OF SIGN:
LOCATE AND PROTECT SERVICES AS REQUIRED DURING PROPOSED WORKS. LOCATION CLEARANCE NO KERB 600 BEHIND GUIDE POSTS BARRIER KERB 300 FROM
5. THE CONTRACTOR IS TO CHECK THROUGH LOCATING, POTHOLING AND SURVEY ALL FACE MOUNTABLE KERB 500 FROM FACE OF KERB.
CRITICAL CONNECTION POINTS FOR ALL CIVIL WORKS SHOWN ON THE DRAWINGS 2.3. PARKING CONTROL SIGNS TO BE MOUNTED TO FACE APPROACHING TRAFFIC AT 45°
INCLUDING ANY POTENTIAL EXISTING SERVICES CLASHES PRIOR TO COMMENCEMENT OF TO KERB OR CARRIAGEWAY EDGE. ALL OTHER SIGNS TO BE TURNED AWAY BY 5°
CIVIL WORKS. CONTRACTOR TO IMMEDIATELY REPORT ANY DISCREPANCIES TO RECOR FROM THE NORMAL TO APPROACHING HEADLIGHT.
AND AWAIT FORMAL DIRECTION PRIOR TO COMMENCING CIVIL WORKS. 3. SIGN SUPPORTS
6. ON COMPLETION OF SERVICES INSTALLATION, ALL DISTURBED AREAS SHALL BE 3.1. SLEEVED SIGNS SUPPORTS ARE TO BE PROVIDED IN ALL AREAS WHERE THEY ARE
RESTORED TO ORIGINAL LEVEL, INCLUDING KERBS, FOOTPATHS, CONCRETE AREAS, IN A PAVED SURFACE.
GRAVEL AREAS, GRASSED AREAS AND ROAD PAVEMENTS. 4. LINEMARKING
4.1. REDUNDANT LINEMARKING IS TO BE GROUND OFF.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY DAMAGE TO
4.2. THERMOPLASTIC LINEMARKING TO BE USED FOR ALL CONCRETE.
AUTHORITY/COUNCIL'S INFRASTRUCTURE. SUCH REPAIR OR REINSTATEMENT TO BE
CARRIED OUT IMMEDIATELY TO THE SATISFACTION OF INFRASTRUCTURE
OWNER/MANAGER / AUTHORITY/COUNCIL. JOINTING NOTES
8. CONTRACTOR TO UNDERTAKE ALL WORKS IN ACCORDANCE WITH ALL WORKPLACE
HEALTH AND SAFETY REQUIREMENTS. 1. ALL JOINTING AND CONCRETE TO BE IN ACCORDANCE WITH THE REQUIREMENTS OF
AS3727.1:2016.
9. WHERE ANY EXCAVATION OR CONSTRUCTION WORKS ARE TO BE IN CLOSE PROXIMITY 2. SAW CUT JOINTS MUST BE:
TO NEIGHBOURING LOT BOUNDARIES OR INFRASTRUCTURE, CONTRACTOR TO ALLOW IN
SCOPE OF WORKS TO PROVIDE ALL MEASURES NECESSARY TO ENSURE THE INTEGRITY 2.1. BETWEEN 41 AND 31 OF CONCRETE PAVEMENT DEPTHS.
OF EXISTING BOUNDARIES AND INFRASTRUCTURE. THIS MAY INCLUDE THE USE OF LOW 2.2. CLEARED OF ANY DEBRIS FROM THE CUTTING METHOD.
VIBRATION EQUIPMENT, TRENCH SHORING ETC AS REQUIRED. 2.3. PERFORMED WITHIN 6 TO 12 HOURS OF FINISHING CONCRETE POURS.
10. PRIOR TO THE CONTRACTOR COMMENCING ANY WORKS DETAILED ON THESE DRAWINGS, 3. DOWELL BARS MUST BE INSTALLED EXACTLY 90° TO THE FACE OF JOINT TO ALLOW
THE CONTRACTOR IS TO NOTIFY RECOR AND RECEIVE WRITTEN CONFIRMATION THAT EXPANSION AND CONTRACTION MOVEMENTS.
WORKS CAN COMMENCE. 4. JOINTING LAYOUT TO BE CONFIRMED BY SUPERINTENDANT PRIOR TO CONSTRUCTION
COMMENCING. LAYOUT SHOULD AVOID ACUTE ANGLES IN THE CONCRETE SLAB AND
11. CONTRACTOR TO PROVIDE AS CONSTRUCTED DRAWINGS FOR ALL CONSTRUCTED AVOID MISMATCHED JOINTS.
WORKS IN ACCORDANCE WITH LOCAL GOVERNMENT REQUIREMENTS. UNLESS
5. JOINT SEALANTS WHERE USED MUST ADHERE TO SIDE OF JOINT FACES ONLY AND SHALL
OTHERWISE ADVISED BY RECOR CONTRACTOR TO NOTE COUNCILS ADAC
NOT EXTEND ABOVE SIDES OF JOINTS ONTO THE SLAB SURFACE.
REQUIREMENTS.
6. DOWEL BARS ARE TO BE
12. CONTRACTOR TO UNDERTAKE ALL WORKS IN ACCORDANCE WITH RELEVANT 6.1. FOR 100MM THICK SLAB, 12MM Ø OF LENGTH 300MM AND SPACED AT 400MM
APPROVALS. CENTRES
13. CONTRACTOR TO ALLOW TO LIASE/CO-ORDINATE WITH ELECTRICAL, LANDSCAPE AND 6.2. FOR 125MM THICK SLAB, 16MM Ø OF LENGTH 350MM AND SPACED AT 300MM
OTHER SERVICE CONTRACTORS THROUGHOUT CIVIL CONSTRUCTION. CENTRES
14. CONTRACTOR TO ORGANISE ALL DEMOLITION PERMITS PRIOR DEMOLITION WORKS 6.3. FOR 150MM THICK SLAB, 20MM Ø OF LENGTH 400MM AND SPACED AT 300MM
COMMENCING ON SITE. CENTRES
15. CONTRACTOR TO ALLOW TO DEMOLISH ALL EXISTING STRUCTURES, ROADS AND
SERVICES WITHIN LIMIT OF WORKS AND REMOVE FROM SITE U.N.O. INSPECTIONS:
THE FOLLOWING INSPECTIONS MUST BE COMPLETED BY RECOR ENGINEERS BEFORE
16. CONTRACTOR TO UNDERTAKE DILAPIDATION REPORT FOR ADJOINING PROPERTIES AND ENGINEERING CERTIFICATION WILL BE ISSUED. THE CONTRACTOR IS TO PROVIDE A MINIMUM
COUNCIL ROADS AND VERGES PRIOR TO COMMENCEMENT OF ANY WORKS ON SITE. OF 72 HOURS NOTICE TO RECOR FOR REQUIRED INSPECTIONS. SHOULD THE
17. CONTRACTOR TO CLEAR AND GRUB ALL VEGETATION ON SITE AS IDENTIFIED IN THE CONTRACTOR FAIL TO REQUEST AN INSPECTION, THE CONTRACTOR WILL BE RESPONSIBLE
APPROVED VEGETATION MANAGEMENT PLAN. CONTRACTOR TO ENSURE ALL TREE FOR ALL COSTS TO ALLOW FOR THE WORKS TO BE INSPECTED TO THE SATISFACTION OF
ROOTS AND STUMPS ARE COMPLETELY REMOVED AND BACKFILLED TO LEVEL 1 RECOR. ANY INSPECTIONS THAT FAIL ARE TO BE RE-INSPECTED WITH ALL REINSPECTION
SUPERVISION. CONTRACTOR TO ALLOW TO MULCH ALL CLEARED VEGETATION AND COSTS TO BE PAID BY THE CONTRACTOR.
STOCKPILE ON SITE OR REMOVE FROM SITE AS DIRECTED.
a. PRESTART
18. DRAWINGS TO BE READ IN CONJUNCTION WITH ARCHITECT, SURVEYOR, HYDRAULICS,
ETC. CONSULTANT AND CONTRACTOR DRAWINGS. b. EARTHWORKS - FINAL STRIPPING OF TOPSOIL, INSTALLATION OF SEDIMENT AND EROSION
CONTROL MEASURES UNSUITABLE GROUND
19. CONTRACTOR TO PREPARE AND HAVE APPROVED BY RELEVANT AUTHORITY: ROAD
OPENING PERMIT AND TRAFFIC MANAGEMENT PLAN FOR ALL WORKS WITHIN COUNCIL c. SIDE AND CUT OFF DRAINS
ROAD RESERVES. CONTRACTOR TO ALLOW FOR ALL COSTS ASSOCIATED WITH d. STORMWATER PIPE LAID ON BEDDING PRIOR TO BACKFILL
IMPLEMENTATION OF THE TMP.
e. STORMWATER TRENCH BACKFILLED PRIOR TO PAVEMENT PLACEMENT
20. ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH ALL LOCAL AUTHORITY
APPROVALS RECEIVED FOR THE PROJECT AND IN ACCORDANCE WITH OPW APPROVALS f. STORMWATER STRUCTURE BASE SLABS
BY COUNCIL. g. PAVEMENT SUBGRADE
North Point Approved Project Address Sheet Title
GENERAL NOTES
E WHITMORE 51 ELANDA STREET SUNSHINE BEACH QLD
RPEQ 31423
For and on behalf of RECOR Pty Ltd.
Scale ENGINEERING + PROJECT MANAGEMENT Client Details Project Name Sheet Size
SUNSHINE COAST | BRISBANE | SYDNEY
www.recorconsulting.com | ABN 89 647 469 707 ARCHEND PROPOSED MULTIPLE RESIDENCE A1
A 21/03/25 ISSUE FOR APPROVAL TVZ AY COPYRIGHT © This drawing is subject to copyright in accordance with the agreement between RECOR Pty Ltd and RECOR's client. This Project Number Sheet Number Revision
002 A
drawing shall only be used for this specific project. This drawing shall not be used for construction until marked as 'Issued For Construction'
Rev Date Revision Description Drawn Check DO NOT SCALE, IF IN DOUBT ASK in the revision description. 20240127
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
RFI - Revised Engineering Plans.pdfRelated documentApplication case desk ↗
About this file
- File size
- 5.0 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.