1 - GENERAL NOTES
Standard Heavy DutyAbove ground 23,000L Water Tank Standard Heavy Duty In ground 23,000L Water Tank 1.1 - These drawings shall be read in conjuction with all other consultant
• 1 x 500mm QLD Approved strainer • 1 x 480mm Access with concrete access cover drawings and specifications. Any discrepancies shall be referred to the architect
• 1 x 100mm Overflow @ top of wall • 1 x 100mm Overflow @ top of wall or project manager for a decision before proceeding with the work.
• 1 x 32mm female Brass @ base of wall • 2 x 100mm Inlet @ top of wall Any decision that inputs on Engineering Design shall be referred to the Engineer
• 1 x 32mm female Brass @ top of wall
for confirmation of design integrity.
55 top of wall
1.2 - Dimensions SHALL NOT be obtained by scaling off the drawings.
75
lid thickness
manhole
2 x 100mm Inlet 100mm overflow 1.3 - All dimensions shall be checked by Builder prior to commencement of
1 x 32mm Brass works.
1.4 - Tank Design for exclusive use by Allcast Precast only.
1.5 - Engineering Certification by HR Design. Form is available at time of
2800 overall height
2530 overflow height
Reinforced with purchase.
TM484265R mesh
2 - LOADINGS
2.1 - The structural work as shown in these drawings has been designed for the following cases:
40 MPa high density concrete (i) a lid load of 500kg.
600 x 600 N12
10mm aggregate
corners bars @
600 cnrs
SL82 mesh to floor 3 - FOUNDATIONS
125
floor thickness
3.1 - Foundation material preparation to be in accordance with consulting civil
Refer Bouyancy control
4m x 4m leveled site with 75mm of 5-10mm scredded gravel joint detail below engineer deign and specifications.
100 top of taper
4 x 2.5 Tonne swift lift anchors at
150 at base
base of external wall. 3.2 - Tank backfill material to be free draining and placed in accordance with
3.5m spreader bar required for lifting Allcast Precast backfill specifications.
3.3 - Where suitable foundation bearing capacity is not achieved, contact HR
TANK DESIGN Design Engineers for alternative design solution.
1 : 50
4 - REINFORCED CONCRETE
4.1 - All work shall be in accordance with all current Australian Standards as
SL62 central layer a MINIMUM work standard.
Trimmed to suit manhole
90
4.2 - Concrete shall have a characteristic compressive strength after 28
75
days of not less than : 40 MPa.
3480 Diameter
4.3 - All concrete shall be mechanically vibrated. Vibrator shall not be used
to spread concrete.
Allcast Precast Water Tank 4.4 - All reinforcement shall be supported on plastic chairs, generally at not
greater than 800mm centres in both directions. Bars shall be tied at
alternate intersections.
For Concrete
volumes speak to
Allcast Precast
4.5 - Concrete to have a maximum aggregate size of 10mm and
Engineer water/cement ratio of not greater than 0.65.
R10 links around edge The maximum permissible transport time for concrete between batching
top and bottom and placement on site shall be in accordance with the following table.
AMBIENT AIR MAX. BATCHING TO PLACEMENT
TEMPERATURE TIME
10°-24°C 120 minutes
75mm 5-10mm 25°-27°C 90 minutes
gravel bed 28°-30°C 60 minutes
N12 bar, chem-set 31°-33°C 45 minutes
into 12mm hole 34°-36°C 30 minutes
drilled as shown 37°C+ No placement of concrete unless
3 x 1.3 Tonne chilled water or ice in mix
swift lift anchors
4.6 - All reinforcement shall be supplied by a registered manufacturer with an
Anti-flotation control only required for Tanks in high water table areas or Pump out tanks
approved and certifier quality assurance program in place. All reinforcement is
to comply with the requirements of AS 1302, AS 1303 and AS 1304 as
applicable.
4.7 - All reinforcement is to be placed free from oil, grease or other surface
LID DESIGN BOUYANCY CONTROL JOINT coatings which may impair bond to concrete.
1 : 50 1 : 10 4.8 - All reinforcement to be 500 MPa minimum yield unless noted otherwise.
4.9 - Reinforcement shall not be welded without written approval from the
Engineer.
PHONE :: (07) 5442 2522
HD23,000 LITRE WATER TANK
FAX :: (07) 5442 2479
TOTAL WEIGHT - 9.8 T
POST :: PO Box 100, Woombye Q 4559
FACTORY :: 40 Hill St, Woombye Q 4559
GENERAL ARRANGEMENT SHOWN
WEB :: www.allcastprecast.com.au CUSTOM FITTINGS BY REQUEST
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
15104 - SBSMP - Rev 0.pdfRelated documentApplication case desk ↗
15104 - SBSMP - Rev 0.pdfRelated documentApplication case desk ↗
15104 - SBSMP - Rev 0.pdfRelated documentApplication case desk ↗
15104 - SBSMP - Rev 0.pdfRelated documentApplication case desk ↗
About this file
- File size
- 4.9 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.