Slope Stability Analysis
QBCC #:15288478
PH: 07 54 740 900
3/53 Gateway Drive, Noosaville 4566
[email protected]
JOB NUMBER 25-0664 SITE CLASSIFICATION REPORT
CLIENT MACKY GROUP
SITE LOCATION PROPOSED DWELLING
15 & 17 MYALL STREET, COOROY
REPORT DATE 26/05/2025
1. INTRODUCTION
The purpose of this report is to classify the subject allotment in accordance with Australian Standard
2870 - 2011 'Residential Slabs and Footings'. From this classification, a footing system can be recom-
mended for the structure so as to allow adequate performance of the footings under the soil conditions
determined at the site.
Trees: There are small (<5m), medium (5-10m), and large (>10m) trees at this site. Global Testing
recommends an experienced arborist be commissioned to quantify the existing size, location, pre-
dicted maximum height and type of these trees to aid in the design process. It is the responsibility of
the designing engineer to apply the principals of AS2870-2011 Appendix H 'Guide to Design of Foot-
ings for Trees'. The classification herein excludes the effect of trees on the site.
2. SITE DESCRIPTION
Type of Allotment Residential
Vegetation Grassed/Scattered Undergrowth
Slope 6% to 8% to East
Surface Water will Drain Towards East
Will Surface Water from adjoining No
allotments traverse this site?
Surrounding Allotments
Left Dwelling
Right Dwelling
Rear Dwelling
Depth to Weathered Rock BH1 (2.0m)
Depth to Water Table BH5 (4.0m)
3. SITE CLASSIFICATION AND TARGET STRATA
Based on the findings of the site investigation, the classification of the site is considered to conform to:
CLASS “M” – (Due to Fill, Trees, and Poor Bearing Capacity - See Target
Stratum)
NOTE: If not for the above reasons, the site would have Class H1 characteristics.
in accordance with Australian Standard 2870 - 2011, 'Residential Slabs and Footings, Construction'.
The target stratum for the foundation of the structure located at BH1 is the SANDY CLAY en-
countered at 400 mm below existing ground level.
The target stratum for the foundation of the structure located at BH2 is the SANDY CLAY en-
countered at 500 mm below existing ground level.
Page | 1 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations