Reference Document - Storm Water Management Plan 132001.210327.1

of 14

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn
  -
    REFERENCE DOCUMENT
       NOOSA COUNCIL
  132001.210327.1 4 DEC 2024




              Stormwater Management Plan
              2/27 Ross Crescent,
              QLD, 4567

              Arcos Project: 240572




Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024
Full text of the other 13 pages

Page 2

            Attention: Peter Flavel                                                        28 August 2024
            C/- David Teeland – Sealand Architect                                    Arcos Project: 240572
                                                                                                  Report 01
            By Email                                                                 AG-240572-RPT-C-01


            Stormwater Management Plan
            2/27 Ross Crescent, Sunshine Beach,
            QLD, 4567


            Document Control
              Version         Date       Details                     Prepared   Checked      Approved
              0               28/08/24   For Approval                JH         GM           LS




            Principal Civil Engineer




            Lachlan Swann B.Eng (Civ) (Hons), CPEng, RPEQ, NER, MIEAust
            [email protected]
            Arcos Group




              E    [email protected]
              W    arcosgroup.com.au
              A    177C Brisbane Road, Mooloolaba, QLD, 4557




Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 3

                                                                                                                                                       ABN 51 640 311 842
                                                                                                                                                                  CONTACT
                                                                                                                                                          arcosgroup.com.au
                                                                                                                                                                   OFFICES
                                                                                                                                     Sunshine Coast | Brisbane | Gold Coast




                 Contents
                 1.0         Introduction ................................................................................................................................ 4
                 2.0         Proposed Development.............................................................................................................. 4
                 3.0         Existing Drainage ....................................................................................................................... 5
                 4.0         External Catchments .................................................................................................................. 6
                 5.0         Flooding ..................................................................................................................................... 7
                 6.0         Lawful Point of Discharge .......................................................................................................... 7
                 7.0         Developed Case ......................................................................................................................... 7
                    7.1      Proposed System ....................................................................................................................... 7
                    7.2      Stormwater Quality Management .............................................................................................. 7
                    7.3      Stormwater Quantity Management ............................................................................................ 7
                 8.0         Conclusion ................................................................................................................................. 8
                 LIMITATIONS .......................................................................................................................................... 9
                 Appendix A – Stormwater Drawings & Calculations ............................................................................. 10




                  28 August 2024


Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 4

                                                                                                                 ABN 51 640 311 842
                                                                                                                            CONTACT
                                                                                                                    arcosgroup.com.au
                                                                                                                             OFFICES
                                                                                               Sunshine Coast | Brisbane | Gold Coast




                 1         Introduction
                 Arcos Unit Group Pty Ltd (Arcos) has been commissioned by Peter Flavel to prepare this Stormwater
                 Management Plan as part of a development application with Noosa Shire Council (NSC). The subject
                 site is described as Lot 2 on GTP100987 and has an area of 1,105m2. A site locality plan is presented
                 in Figure 1. The existing dwelling is located at 2 The Beach Houses - 2/27 Ross Crescent, Sunshine
                 Beach, Queensland.




                 FIGURE 1: SITE LOCALITY (SOURCE: NSC)
                 The subject site includes a large existing dwelling with a highset a garage. The site falls east towards
                 Sunshine Beach.
                 The property is located within the “Coastal area – erosion prone area” as noted in the SARA DA
                 mapping.



                 2         Proposed Development
                 It is proposed to renovate the existing dwelling. This renovation consists of the removal of the existing
                 garage, guest pavilion, entry decking and dilapidated roof section, and the construction of a new home
                 office, new garage, family room and new roof section. These proposed renovations are shown below in
                 Figure 2 and Figure 3.




                 28 August 2024


Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 5

                                                                                                                  ABN 51 640 311 842
                                                                                                                             CONTACT
                                                                                                                     arcosgroup.com.au
                                                                                                                              OFFICES
                                                                                                Sunshine Coast | Brisbane | Gold Coast




                 FIGURE 2: SITE PLAN (SOURCE: SEALAND ARCHITECTS)




                 FIGURE 3: EXISTING SITE PLAN (SOURCE: SEALAND ARCHITECTS)



                 3         Existing Drainage
                 There is no existing public stormwater network near the subject lot. Instead, the existing dwellings roof
                 runoff is captured and discharged to a rubble pit. This rubble pit is located downhill of the dwelling near
                 the lot’s eastern boundary, see Figure 4. The rubble pit sheet flows to the east towards Sunshine Beach
                 Park before reaching the beach itself.




                 28 August 2024


Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 6

                                                                                                                  ABN 51 640 311 842
                                                                                                                             CONTACT
                                                                                                                     arcosgroup.com.au
                                                                                                                              OFFICES
                                                                                                Sunshine Coast | Brisbane | Gold Coast




                                 Existing rubble pit




                 FIGURE 4:EXISTING STORMWATER LAYOUT PLAN (SOURCE: SEALAND ARCHITECTS)



                 4         External Catchments
                 There is a small external catchment that flows through the existing site, refer contours in Figure 5
                 below. It is noted that the existing driveway would intersect majority of the external catchment and direct
                 flows to Ross Crescent.




                 FIGURE 5: CONTOURS (SOURCE: NSC)




                 28 August 2024


Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 7

                                                                                                                    ABN 51 640 311 842
                                                                                                                               CONTACT
                                                                                                                       arcosgroup.com.au
                                                                                                                                OFFICES
                                                                                                  Sunshine Coast | Brisbane | Gold Coast




                 5         Flooding
                 The site is not identified as being impacted by flooding as per NSC Flood Hazard Mapping.



                 6         Lawful Point of Discharge
                 The lawful Point of Discharge (LPD) for the subject lot is the downslope eastern boundary of the site.
                 This lawful point of discharge is compliant with Section 3.9.1 requirements of QUDM.



                 7         Developed Case
                 7.1       Proposed System
                 It is proposed to reuse the existing rubble pit which had been sized for the existing dwelling and to install
                 a new second rubble pit for the new garage and new home office, refer to attached drawings in the
                 Appendix.
                 The roof area of the existing garage, guest pavilion and dilapidated roof section which are being
                 removed is of similar size to the proposed family room and new roof section (within 10m2). Therefore,
                 it is proposed to connect the roof area of the proposed family room to the existing stormwater downpipe
                 outlet and existing rubble pit.
                 The new garage and new home office are proposed to discharge to a new 2.4m long ‘Evertrench Large’
                 (or approved equivalent) stormwater disposal system. This rubble pit system has been sized in
                 accordance with the Moreton Bay Regional Council Stormwater for domestic buildings fact sheet. The
                 rubble pit has been positioned to avoid sheet flow being directed towards any buildings or structures.
                 Further, sizing was checked using additional industry adopted soak well design guidance.

                 7.2       Stormwater Quality Management
                 Stormwater quality measures do not apply for this development approval.
                 The State Planning Policy states that stormwater management design objectives do not apply for
                 premises smaller than 2500m2. This lot has an area of 1,105m2.

                 7.3       Stormwater Quantity Management
                 The minor increase of 56m2 in impervious area for this renovation does not require any stormwater
                 mitigation. The site is also located within 100m from Sunshine Beach. Detention is not required this
                 close to the ocean as it will not coincide with the peak flows in a storm event.




                 28 August 2024


Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 8

                                                                                                                   ABN 51 640 311 842
                                                                                                                              CONTACT
                                                                                                                      arcosgroup.com.au
                                                                                                                               OFFICES
                                                                                                 Sunshine Coast | Brisbane | Gold Coast




                 8         Conclusion
                 This SWMP has been prepared to support the application on the proposed renovation at 2/27 Ross
                 Crescent.
                 Arcos confirms the following:
                     •    The existing dwelling has a fully functional and operating rubble pit;
                     •    The portion of the proposed renovation which is replacing the existing will reuse the existing
                          rubble pit;
                     •    To manage roof runoff effectively, alleviating any scour potential to the sensitive coastal erosion
                          area the new garage and new office will discharge to a secondary rubble pit which has been
                          adequately sized and located;
                     •    No stormwater quality or quantity measures are required for this renovation.
                 In summary, this report shows that the stormwater can be adequately managed for this renovation in
                 accordance with Council's code requirements.




                 28 August 2024


Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 9

                                                                                                                  ABN 51 640 311 842
                                                                                                                             CONTACT
                                                                                                                     arcosgroup.com.au
                                                                                                                              OFFICES
                                                                                                Sunshine Coast | Brisbane | Gold Coast




                 LIMITATIONS
                 Arcos Unit Group Pty Ltd (Arcos) has prepared this document for the project described on the title page
                 for the client's exclusive use. The document is specific to this particular project and for the purposes as
                 described within the document. The document cannot be used for any other project on the same site or
                 other sites or relied upon by a third party. Any party relying upon this document beyond its exclusive
                 use and purpose as stated above, and without the express written consent of Arcos, does so entirely
                 at its own risk and without recourse to Arcos for any loss or damage. Arcos has necessarily relied upon
                 information provided by the client and/or their agents.
                 The required detailed design for the service infrastructure will be subject to the conditions (if any),
                 attached to the Development Approval provided by Council and any nominated referral agencies.
                 The advice given in this document is based upon the assumed conditions and data outlined herein. The
                 relevance and accuracy of advice given are directly affected by variations in the information supplied
                 and open source information relied upon.
                 This document must be kept in its entirety, read in full and understood. Interpretations or conclusions
                 made by others unless supported by an expressed written statement, interpretation, outcome or stated
                 within this document cannot be the responsibility of Arcos.
                 This document or parts of it should not be used as part of a specification or design for a project without
                 prior review and agreement by Arcos.




                 28 August 2024


Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 10

                                                                   ABN 51 640 311 842
                                                                              CONTACT
                                                                      arcosgroup.com.au
                                                                               OFFICES
                                                 Sunshine Coast | Brisbane | Gold Coast




            Appendix A – Stormwater Drawings &
            Calculations




             28 August 2024


Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 11

           RUBBLE PIT CALCULATIONS
           Arcos Group

                                           Address: 2/27 Ross Crescent, Sunshine Beach
                                       Job Number: 240572
                                              Date: 14/08/2024
                                          Engineer: JH

           Calculations based off Moreton Bay Regional Council

           Catchments:
           Office                                                  71.9 m2
           New Garage                                              46.5 m2

           Catchment Total                                       118.4 m2

           Depth                                                    0.5 m
           Width                                                      1m
           Length                                                     1 m per 50m2
           Required length                                          2.4 m

           Detail in link




Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Page 12

     Stormwater for domestic buildings
                 The roof of every domestic building shall be provided with a complete and effective
                  drainage system to the satisfaction of the building certifier, which must ultimately comply
                  with the requirements of the Building Code of Australia.

                 The stormwater drainage must discharge to the kerb and channel (road frontage) where
                  a kerb adaptor has been provided by the developer at the time of the original subdivision;
                  or if the minimum pipe grade of 1:100 is achievable and adequate cover over that pipe
                  can be obtained. In this instance, the pipe shall be connected to the kerbing with an
                  approved galvanized mild steel kerb adaptor. The kerbing shall be “neatly” cut so the
                  kerb adaptor can be grouted into position and once in position it does not change the
                  profile of the kerbing.

                 Where there is an inter-allotment drainage network provided with an approved
                  connection point to receive the property’s stormwater drainage system then it must
                  discharge to that drainage network.

                 If there is no inter-allotment drainage network and the private stormwater drainage
                  system falls away from the street it must be discharged to an on-site stormwater
                  dispersion system.

                 An on-site dispersion system (rubble pit) must be placed so that it does not cause
                  stormwater to pond under the floor of any building; or to flood around the foundations of
                  any building; or cause nuisance to neighbouring properties.




Document Set ID: 23245585                              Page 1 of 2                                    October 09
Version: 1, Version Date: 16/09/2024

Page 13

        Important:

        There is no specific criteria relating to the placement of an on-site dispersion system (rubble
        pit), however, it is suggested that it be placed a minimum of three (3) metres from any
        boundary, building or structure. Where the land slopes toward the boundary this distance should
        be increased accordingly.

        The objective is to ensure there is no risk to the structural integrity of buildings and structures
        and to achieve “sheet flow” at the property boundary. “Sheet flow” is the flow across a property
        boundary that would have occurred naturally had there not been any building work at the
        property.




Document Set ID: 23245585                            Page 2 of 2                                    October 09
Version: 1, Version Date: 16/09/2024

Page 14

                                                                                                                           18                                                                                                                                                                                                   16


      ENGINEERS MARK UP
      SWMP
      23/08/2024                                                                                                  19
                                                                                                                                                                                                                                                                                                                                     WALL LEGEND
      ARCOS GROUP                                                                                                                                                                                                                                                                                                                                EXISTING WALL
      JH                                                                                                                                                                                                                                                                                                                                         NEW WALL
                                                                                                                                                                                                                 APPROX LOCATION OF
                                                                                                                                                                                                                 10.5m LONG EXISTING
                                                                                                         20                                                                                                      RUBBLE PIT TO REMAIN                                                                                                PLAN LEGEND
                                                                                                                                                                           180°
                                                                                                                                                                                   25'                                                                                                                                               CB          STRAMIT SHARPLINE
                                                                                                                                                                                                                                                                                                                                                 290w 38 rib MagnaFlow
                                                                                                                                                                                                                                                                                                                          17         DP          SS DOWN PIPE
                                                                                                                                                            Existing Rock Retaining Wall                 32.99
                                                                                                                                                                                                                      SITE                                                                                                           EX          EXISTING
                                                                                                                                                                                                                             BOU                                                                                                     MB          METER BOX
                                                                                                                           EXISTING                                                                                               NDA
                                                                                                                                                                                                                                          RY                                                                                         SL          VELUX SKY LIGHT
                                                                                                                            P O O L                                                                                                                                                                    18                            SS          316 STAINLESS STEEL
                                                                                                                                                                                                                                                                                                                                     ST          STONE TILE
                                                                                                                                            NEW                                                                                                                                                                                      RL          RELATIVE LEVEL
                                                                                                                                            POOL                                                                 CB
                                                                                                21
                                                                                                                                            DECK                                                                                                         CB                                       19



                                                                                                                                              CB                                                                                                                                                             INSTALL NEW 2.4m LONG X 1m WIDE X
                                                                                                                                                                                  EXISTING HOUSE                 CB
                                                                                                                                                                                                                                                                                             20              0.5m DEEP RUBBLE PIT. ENSURE NO
                                                                                                                                                                                                                                          CB
                                                                                                                                                                                                                                                                                                             STRUCTURES DOWNHILL. CONSTRUCT
                                                                                                                                              CB                                                                                                                                                             'EVERTRENCH LARGE' OR APPROVED
                                                                                                                                                                                                                                                               SL
                                                                                                                                                                                                    CB                                    CB                                        21
                                                                                                                                                                                                                                                                                                             EQUIVALENT RUBBLE PIT SYSTEM IN
                                                                                                                                                                                                                      SL
                                                                                                                                               EXISTING HOUSE                     CB                                                                                                                         ACCORDANCE WITH THEIR STANDARD
                                          NEIGHBOURING HOUSE                                                 SL             SL                                                                                                                                                                               DETAILS.
                                                                                       NDAR
                                                                                           Y                                      SL                                                                                                                                                22


                           CONNECT FAMILY ROOM ROOF




                                                                                                                                                                                                                                                                           RY
                                                                                                                                                                                                                                                                                     23
                                                                                22




                                                                                                                                                                                                                                                                         NDA
                                                                                       BOU




                           DOWNPIPES TO EXISTING                                                                                                                                                                                       Wall
                                                                                                                                                                                                                       ock   Retaining
                                                                                                                                                                                                          Existing R




                                                                                                                                                                                                                                                                     BOU
                                                                                                                                                                                                                                                                                24
                           RUBBLE PIT DRAINAGE. THIS
                                                                                  SITE




                                                                                                       NDER




                                                                                                                                                                                                                                                                    SITE
                           AREA IS A SIMILAR SIZE TO WHAT
                                                                                                     ALL U
                                                                                 35.26




                           IS EXISTING                                                                                                                                                                                                                                   25
                                                                                                                                                                                       NEW WORK
                                                                                                 OF W




                                                                                                                                                                                       TO CONNECT




                                                                                                                                                                                                                                                               58'
                                                                                                                                                                                                                                                               75
                                                                                '
                                                                               89°39




                                                                                                                                                                                       INTO EXISTING




                                                                                                                                                                                                                                                          272°
                                                                                                                                                                                                                                                          33.8
                                                                                                             FAMI                                                                                                                                                   26
                                                                                                LINE




                                                                                                                  LYROO                                                                SERVICES
                                                                                                         FALL
                                                                                                              7.5 0     M                                                                                                                                                                                                      NEIGHBOURING HOUSE
                                                                                                        CB
                                                                                                                                                                                                                                                              27


                                                                                                                                               NEW
                                                                               2,000                                                           ENTRY
                                                                         SETB                                                                  STAIR
                                                                                 ACK                                                                                                LINE OF WALL UNDER                                                   28
                                                                                                NEW
                                                                                                             GAR
                                                                                               FALL                 AGE                                                                   NEW HOME OFFICE
                                                                                                    15 0
                                                                                               CB                                                                                                 FALL 250 CB
                                                                                                                                                                                                                                                    29

                                                                    23                                                                                                                            FALL 300
                                                                                                                                                                                                  CB
                                                                                                                                                                                                                                               30
                                                                                                       SETB                                                                                                                   2,500
                                                                                                                  ACK                                                                                                                 .
                                                                                                                                                                                                                           SETB
                                                                                                                                                                                                                                ACK
                                                                                                                                                                              K


                                                                  24                                                                                                                                                                                                                 CONNECT NEW HOME OFFICE
                                                                                                                                                                        BAC



                                                                                               EXISTING
                                                                                                                                                                            .
                                                                                                                  1,400.




                                                                                                                                                                      3,000




                                                                                               DRIVEWAY
                                                                          25                                                                                                                                                              31                                         AND NEW GARAGE ROOF
                                                                                                                                                                    SET




                                                                                               BRICK                       27                357°4
                                                                                                                                                      8'
                                                                                                                                                            31.04
                                                                                                                                                                    3
                                                                                                                                                                                                                                                                                     AREAS TO NEW RUBBLE PIT
                                                                                                                                                                                  SITE
                                                                                         26                                            28                                                BOUN
                                                                                                                                                       29                                    DARY


                                                                                                                                                                             30



   SITE PLAN
   1:200                                                                                                                                                                                                                                                                                          scale
                                                                                                                                                                                                                                                                                                  0    1            5                10m      DESIGN DEVELOPMENT ISSUE
                                                 COMPLIANCE: All works to comply with Australian Standards,Queensland and National           Client                     Project                          Amendment List                                                                                                                                                 Drawing Title




                                                                                                                                                                                                                                                                                         E
                                                 Construction Code requirements.                                                             Flavel                     Alterations & Additions          DD1 Development Application Client Issue 28.06.24                                                                                                         SITE PLAN
                                                 DIMENSIONS: Verify dimensions before commencing any work or making any shop




                                                                                                                                                                                                                                                                                N
                                                                                                                                                                        to 2 Beach Houses                DD2 Development Application Client Issue 19.07.24




                                                                                                                                                                                                                                                                                                  S
                                                 drawings. Figured dimensions take precedent over scale.
                                                 COPYRIGHT: This drawing is copyright and property of the architects and must not be
                                                                                                                                                                        2/27 RossCrescent                DD3 Client Issue                         01.08.24                                                  1:200 @ A3         AUGUST 2024           2308          2001        DD4
                                                                                                                                                                                                         DD4 Client Issue                         09.08.24
                                                 retained, copied or used without their written authority.                                                              Sunshire Beach                                                                                                                            Scale                Date     Project No.   Drawing No.   Revision




                                                                                                                                                                                                                                                                                         W
Document Set ID: 23245585
Version: 1, Version Date: 16/09/2024

Used in these records

About this file

File size
1.3 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Reference Document - Storm Water Management Plan 132001.210327.1.pdf · 1.3 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.