 JOB NUMBER              22-0439 SITE CLASSIFICATION REPORT
 CLIENT                  KMC Superannuation
 SITE LOCATION           PROPOSED DWELLING
                         39-41 Picture Point Crescent, Noosa Heads QLD, Australia
 REPORT DATE             12/04/2022


1. INTRODUCTION
The purpose of this report is to classify the subject allotment in accordance with Australian Standard
2870 - 2011 'Residential Slabs and Footings'. From this classification, a footing system can be recom-
mended for the structure so as to allow adequate performance of the footings under the soil conditions
determined at the site.
Trees: There are small (<5m), medium (5-10m), and large (>10m) trees at this site. Global Testing
recommends an experienced arborist be commissioned to quantify the existing size, location, pre-
dicted maximum height and type of these trees to aid in the design process. It is the responsibility of
the designing engineer to apply the principals of AS2870-2011 Appendix H 'Guide to Design of Foot-
ings for Trees'. The classification herein excludes the effect of trees on the site.


2. SITE DESCRIPTION
 Type of Allotment                                                     Residential
 Vegetation                                                   Scattered Undergrowth/Trees
 Slope                                                                50% to North
 Surface Water will Drain Towards                                        North
 Will Surface Water from adjoining                                        Yes
 allotments traverse this site?
 Surrounding Allotments
                                 Left                                 Dwelling
                                Right                                 Dwelling
                                Rear                                    Road
 Depth to Weathered Rock                                         BH1 (N/a), BH2 (N/a)
 Depth to Water Table                                            BH1 (N/a), BH2 (N/a)


3. SITE CLASSIFICATION AND TARGET STRATA
Based on the findings of the site investigation, the classification of the site is considered to conform to:

  CLASS “P” – (Due to Uncontrolled Fill, the Presence of Trees, and Poor
                Bearing Capacity - See Target Stratum)
    PLEASE NOTE: If not for the above reasons, this site would have the characteristics of a Class M Site.

in accordance with Australian Standard 2870 - 2011, 'Residential Slabs and Footings, Construction'.

The target stratum for the foundation of the structure located at BH1 is to be determined by the
designing engineer.
The target stratum for the foundation of the structure located at BH2 is to be determined by the
designing engineer.

       Page | 1 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             22-0439
Full text of the other 8 pages

Page 2

                                                                                         QBCC #:15288478
                                                                                         PH: 07 54 740 900
                                                                       3/53 Gateway Drive, Noosaville 4566
                                                                            [email protected]


PLEASE NOTE: This report does not address slope stability. If a slope stability analysis is re-
quired, the services of a suitably qualified geotechnical engineer should be sought. We can rec-
ommend one or organise this service on your behalf.
It is the designing engineer’s responsibility to address the potential influence of any trees present
on or around the proposed building site.

If any fill is placed over the existing ground, the structure shall be piered through the fill into the
existing material. Further note that the placement of reactive material as fill, or cutting of the
site may change the site’s classification.


4. SOIL PROFILE
Refer to Soil Profile Report for borelog information.
Whilst every effort has been made to ensure that the borelogs carried out at the subject allotment are
indicative of the soil profile over the site any discrepancy between the profile detailed in the borelogs
and that observed during construction shall be referred to Global Testing for immediate attention.


5. MATERIALS LABORATORY TEST RESULTS
Soil Laboratory testing carried out on samples of the soil taken from the site gave the following results:
                    BOREHOLE                                                  BH1
                    DEPTH RANGE OF SAMPLE                                     N/a
                    LIQUID LIMIT (%)                                          N/a
                    PLASTIC LIMIT (%)                                         N/a
                    PLASTIC INDEX (%)                                         N/a
                    LINEAR SHRINKAGE (%)                                      N/a
                    INSTABILITY INDEX (%)                                     N/a
                    SHRINK SWELL INDEX, Iss (%)                              <1.0*
                    PREDICTED SURFACE MOVEMENT                             20-25 mm
                 *Inferred value to undertake calculation in accordance with AS2870

Please note that the Plasticity Index (PI) determined by the Atterberg Test may be correlated to an
Instability Index (Ips)with reference to the results of extensive testing carried out by others, notably, Dr
P Mitchell, ‘Footings for Small Scale Domestic Structures,’ March 1990.
 Yours Sincerely,




 (on Behalf of Global Testing - B.Eng(Civ)(Hons), CPEng, RPEQ, NER, MIEAust)




       Page | 2 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             22-0439

Page 3

                                                                                         QBCC #:15288478
                                                                                         PH: 07 54 740 900
                                                                       3/53 Gateway Drive, Noosaville 4566
                                                                            [email protected]


                                               LIMITATIONS

Recommendations given in this report are based on the information supplied by the client regarding the
proposed building construction in conjunction with the findings of the investigation. Any change in
construction type, building location or omission in the client supplied information, may require addi-
tional testing and/or make the recommendations invalid.


The recommendations herein identify a target soil stratum into which the footings are to be founded.
The target stratum has been located by the depth in mm of the target stratum's upper horizon boundary
below the existing ground surface level at the time of the site investigation. Any cutting or filling works
and any surface erosion or deposits subsequent to the site investigation, will alter the measured location
of the stratum relative to the surface. Where required, the author should be notified in such cases to
confirm the location of the target stratum.


The description of the soil given in the Soil Profile section of this report is intended as a brief overview
of the soil's primary constituents. For a detailed classification of the soil, the reader should refer to the
Soil Profile Reports and/or Borehole Reports attached to this report.

Every reasonable effort has been made to locate the test sites so that the borehole profiles are repre-
sentative of the soil conditions within the area investigated. The client should be made aware however,
that exploration is limited by time available and economic restraints. In some cases, soil conditions can
change dramatically over short distances, therefore, even careful exploration programs may not locate
all the variations.

If soil conditions different from those shown in this report are encountered or are inferred from other
sources, then the author must be notified immediately.

This report may not be reproduced except in full. The information and drawings provided with this
report shall only be used and will only be applicable for the development shown on the client supplied
information provided for this site.

Any dimensions, contours, slope directions and magnitudes shown on the Test Locality Plan shall not
be used for any building construction or costing calculations. The purpose of the plan is to show ap-
proximate location of field tests only.

Any changes made to these recommendations by persons unauthorised by the author will legally be
interpreted as that person assuming the responsibility for the long-term performance of the footing sys-
tem.

The recommendations contained in this report have not taken into consideration the long-term effects
of any previous, current or potential subsurface work by mining companies or potential slope instability
problems. At the time of writing this report neither our client (nor his agent) nor the local authority had
made the author aware that these problems may be affecting this allotment. If a mining subsidence or
slope stability assessment is required for this allotment, the recommendations of a suitably qualified
geotechnical engineer should be sought.



       Page | 3 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             22-0439

Page 4

                                                                               QBCC #:15288478
                                                                               PH: 07 54 740 900
                                                             3/53 Gateway Drive, Noosaville 4566
                                                                  [email protected]


SOIL PROFILE REPORT
CLIENT:      KMC Superannuation              AUTHORISED            KMC Superannuation
                                             BY:
PROJECT:     39-41 Picture Point Crescent,   DATE TESTED:          11/04/2022
             Noosa Heads QLD, Australia      JOB NO:               22-0439


               Drilling Method: Hand Auger 100mm.                                     Borehole
                                                                                        No.1
  Depth       Description                                         PENET.             Est. Bearing
                                                             (blows per 100mm)
  (mm)                                                                                Capacity
                                                              1      2    3      4       (kPa)
    0         (FILL) SAND (SP)-fine to medium sand,
              grey, moist, very loose
   100                                                        1                          30
   200                                                        1
   300                                                        1
   400        SAND (SP)-fine to medium sand, grey,            1
              moist, very loose
   500                                                        1                          30
   600                                                        1
   700                                                        1
   800                                                        1
   900                                                        1                          30
   1000                                                       1
   1100                                                       1
   1200                                                       1
   1300                                                       1                          30
   1400                                                       1
   1500       Borehole Terminated                             1
   1600                                                       1
   1700                                                       1                          30
   1800                                                       1
   1900                                                       1
   2000                                                       2                          50
   2100                                                       2
   2200                                                       2
   2300                                                       2
   2400                                                       2                          50
   2500                                                       1
   2600                                                       2
   2700                                                       2
   2800                                                       3                          100
   2900                                                       4
   3000                                                       4
   3100                                                       4
   3200                                                       4
   3300                                                       4                          125
   3400                                                       5
   3500                                                       5

    Page | 4 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                          22-0439

Page 5

 

QBCC #:15288478

 

 

 

 

 

 

 

 

 

 

 

 

 

ry = PH: 07 54 740 900
; Fe Global Testing 3/53 Gateway Drive, Noosaville 4566
THE ONLY NAME IN SOILS [email protected]
3600 5
3700 6 150
3800 7
3900 8
4000 8
4100 8 150
4200 10
4300 10
4400 10
4500 10 150
4600 10
4700 10
4800 11

 

 

 

 

 

 

 

Page | 5 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
22-0439

Page 6

                                                                               QBCC #:15288478
                                                                               PH: 07 54 740 900
                                                             3/53 Gateway Drive, Noosaville 4566
                                                                  [email protected]




SOIL PROFILE REPORT
CLIENT:      KMC Superannuation             AUTHORISED          KMC Superannuation
                                            BY:
PROJECT:     39-41 Picture Point Cres-      DATE TESTED:        11/04/2022
             cent, Noosa Heads QLD,         JOB NO:             22-0439
             Australia


               Drilling Method: Hand Auger 100mm.                                     Borehole
                                                                                        No.2
  Depth       Description                                       PENET.               Est. Bearing
                                                             (blows per 100mm)
  (mm)                                                                                Capacity
                                                            1      2      3      4       (kPa)
    0         (FILL) SAND (SP)-fine to medium sand,
              grey, moist, very loose
   100                                                             1                     30
   200                                                             1
   300        SAND (SP)-fine to medium sand, grey,                 1
              moist, very loose
   400                                                             1                     30
   500                                                             1
   600                                                             1
   700                                                             1
   800                                                             1                     30
   900                                                             1
   1000                                                            1
   1100                                                            1
   1200                                                            1                     30
   1300                                                            1
   1400                                                            1
   1500       Borehole Terminated                                  1
   1600                                                            1                     30
   1700                                                            1
   1800                                                            1
   1900                                                            1
   2000                                                            1
   2100                                                            2                     50
   2200                                                            2
   2300                                                            2
   2400                                                            1
   2500                                                            2
   2600                                                            2
   2700                                                            3                     100
   2800                                                            3
   2900                                                            2
   3000                                                            2
   310                                                             2                     50
   3200                                                            2

    Page | 6 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                          22-0439

Page 7

 

QBCC #:15288478

Ca = PH: 07 54 740 900
Az Global Testing 3/53 Gateway Drive, Noosaville 4566
X I

THE ONLY NAME IN SOILS [email protected]

 

3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300

 

 

100

 

 

 

 

100

 

 

 

 

150

 

 

 

 

 

00] CO] JNM MN} ny) BY] BY] Go] G2] G2 fb} Go] bo] bo

150

 

me
o

 

me
o

 

me
o

 

me
o

150

 

 

 

 

 

 

 

e
ane

 

Page | 7 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
22-0439

 

Page 8

                                                                           QBCC #:15288478
                                                                           PH: 07 54 740 900
                                                         3/53 Gateway Drive, Noosaville 4566
                                                              [email protected]




Site- 39-41 Picture Point Crescent, Noosa Heads QLD, Australia




Page | 8 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                      22-0439

Page 9

                                                                                                                                                        N
                                                                                                                                                             SATELLITE IMAGERY
                                    ING
                               EXIST L
                                 PO O
                                                                                                                                                              LEGEND

                                                                                                                                                                   BHx = BOREHOLE LOCATION


                                                                                                                                                                   PNx = DYNAMIC CONE PENETROMETER
                                                                                                                                                                   LOCATION

                                                                                                                                                                    TREES
                                                        EXISTING
     PIC




                                                       RESIDENCE
         TUR




                                                                                    BH1
             E




                                                                                    PN1
            POI




                                                                              BH2
                NT




                                                                              PN2
                 CRE
                    S




SITE PLAN
SCALE: 1 : 250


                                                             CLIENT DETAILS               PROJECT DETAILS                    DRAWING TITLE                                        JOB No.    22/0439
                        SITE CLASSIFICATION
                        EFFLUENT DESIGN
                        SOUTH EAST QLD                       KMC SUPERANNUATION           LOT 2, 39-41 PICTURE POINT CRES,   TEST LOCATION PLAN                                   DRG No.     301
                        [email protected]
                                                                                          NOOSA HEADS, QLD                                                                                     1
                                                                                                                             DRAWN: CA   DATE: 12/04/2022   SCALE:As indicated@A3 REVISION

Used in these records

About this file

File size
1.2 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Soil Report.pdf · 1.2 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.