WATER SUPPLY MAIN

 

 

 

 

 

1 CONNECTION METHOD USING Ic ECS THAN 400MM,

 

 

 

 

 

TYPICAL UNDER PRESSURE warn PIPE DIAMETER.

 

 

 

‘SS FULL WRAP FLANGED DOME:
OFFTAKE. FOR THIS METHOD STIC SERVICE
PIPE MATERIAL
ONLY, THRUST BLOCKS ARE be) ow GROUND IS
NOT REQUIRED FOR PARENT pea INCLUDING
MAINS LESS THAN DN300 F
BEND FITTINGS.

    
 

DUAL CV FOR
LOW HAZARD ONLY,

 

CONTAINMENT PROTECTION - VALVE PRODUCT SPECIFICATION (OR UNITYWATER APPROVED EQUIVALENT PER SEQ CODE CIVIL IPAM LIST )

 

 

 

 

 

HAZARD | SIZE PRODUCT DESCRIPTION VALVE CHEQ;) APPLICATION ITEM
RATING PART No. No.
LOW 150mm| TESTABLE SINGLE CHECK SDCTO3 (50kPa) VALVE 20663308FG0
Low 100mm| TESTABLE SINGLE CHECK SDCTO3 (SOkPa) VALVE 2066164arGO | FIRE HYDRANT SERVICE §
Low 40mm | TESTABLE SINGLE CHECK SCTO3 (16kPa) CO FS BYPASS VALVE 2234355FSBV YDRANT SERV VALV
Low 25mm | TESTABLE SINGLE CHECK SCTO3 (16kPa) CO FS BYPASS VALVE 7234353FSBV | FIREHYORANT SERVICE BYPASS VALVE | 10
LOW 0mm) TESTABLE SINGLE CHECK SDCTO3 (i6kPal VALVE 7206072
Low 400mm| TESTABLE SINGLE CHECK SDCTO3 (16kPa) VALVE 2206070 FIRE SPRINKLER SERVICE 5
LOW 1S0mm| NON TESTABLE DuCV DUAL CHECK DCO3U C/W GEAR-OPERATED BUTTERFLY VALVES & BOLT KIT (vekPal | 2024586BFGO
Low 100mm| NON TESTABLE DuCV DUAL CHECK DCO3U C/W GEAR-OPERATED BUTTERFLY VALVES & BOLT KIT (16kPa) | 2027167BFGO
LOW 80mm | NON TESTABLE DuCV DUAL CHECK DCO3U C/W GEAR-OPERATED BUTTERFLY VALVES & BOLT KIT (16kPa) | 20265668FGO | WATER (POTABLE) SERVICE 16
Low 65mm | NON TESTABLE DuCV DUAL CHECK DCO3U C/W GEAR-OPERATED BUTTERFLY VALVES & BOLT KIT (16kPa) | 22373578FGO | Y - TYPE STRAINER REQUIRED
LOW 50mm | NON TESTABLE DuCV DUAL CHECK DCO3U C/W BALL VALVES & UNIONS (16kPa} 2025906FSBV

 

 

 

 

 

 

 

 

 

 

NOTES:

4. THIS METER ASSEMBLY ARRANGEMENT IS ONLY APPLICABLE FOR ABOVE GROUND INSTALLATIONS WITHIN PRIVATE
PROPERTY OF LARGE DIAMETER FIRE SERVICES (SPRINKLER & HYDRANT, 2100MM-9150MM) AND WATER SERVICES
(DOMESTIC, 250MM-2150MM) FOR RESIDENTIAL (MULTI-UNIT), COMMERCIAL, AND INDUSTRIAL DEVELOPMENTS. FOR
OTHER ARRANGEMENTS, INCLUDING BASEMENT INSTALLATIONS, CONTACT UNITYWATER DEVELOPMENT SERVICES.

»

FOR ARRANGEMENT OF METERED WATER SERVICES OF SIZES 820MM TO 625MM, REFER TO SEQ CODE STANDARD
DRAWING SERIES SEQ-WAT~-1108-1 TO SEQ-WAT~-1108-3.

3, STANDARD DRAWINGS SEQ-WAT-1108-4 & SEQ-WAT-1108-5 ARE NOT FOR CONSTRUCTION AND ONLY DEPICT
INDICATIVE ARRANGEMENTS. IT IS THE DESIGNER'S RESPONSIBILITY TO SPECIFY THE MAKE, MODEL AND SIZES OF ALL
PIPES AND FITTINGS REQUIRED FOR INSTALLATION OF THE SERVICE ARRANGEMENT, INCLUDING ISOLATION VALVES,
CONTAINMENT PROTECTION DEVICES AND WATER METERS IN ACCORDANCE WITH THE CURRENT SEO CODE ACCEPTED
CIVIL PRODUCTS AND MATERIALS LIST. REFER TO APPROVED DESIGN DRAWINGS FOR SPECIFIC INSTALLATION
REQUIREMENTS,

4, THESE STANDARD DRAWINGS SEQ-WAT-1108-4 & SEQ-WAT-1108-5 MUST BE READ IN CONJUNCTION WITH THE SEQ
CODE (AMENDED WSA03-2011 WATER SUPPLY CODE OF AUSTRALIA}, AS 2419 FIRE HYDRANT INSTALLATIONS; AS/NZS
3500.1 PLUMBING AND DRAINAGE PART 1: WATER SERVICES AND THE DESIGNER’S HYDRAULIC DRAWINGS WHICH ARE
SUBJECT TO SEPARATE APPROVAL BY THE RELEVANT COUNCIL PLUMBING REGULATORY AUTHORITY.

5. THE MAXIMUM ALLOWABLE OFFTAKE SIZE FOR FIRE SERVICES (SPRINKLER & HYDRANT) AND WATER SERVICES
(DOMESTIC) FROM THE UNITYWATER MAIN IN THIS STANDARD DRAWING IS 150MM.

6, FOR ITEM 1, REFER TO STANDARD DRAWING SEQ-WAT-1105-2 FOR ACCEPTABLE CONNECTOR TYPES, FOR SUPPLY
MAINS IN PVC-0 OR PE MATERIAL, DESIGNER SHALL SPECIFY OFFTAKE USING TRE CUT-IN CONNECTION METHOD. FOR
DETAILS ON UNDER PRESSURE CUT-IN CONNECTION TO PRESSURE PIPES >DN80,

REFER TO WSA 03-2011-3.1 APPENDIX C.

7. CONTAINMENT PROTECTION USING BACKFLOW PREVENTION DEVICES IN ACCORDANCE WITH AS/NZS 2845.1 IS REQUIRED
FOR AT LEAST A LOW HAZARD RATING OF CROSS CONNECTION FOR ALL CONNECTIONS TO THE WATER SUPPLY
NETWORK (REFERENCE AS/NZS 3500.1 CLAUSE 4.4.4). ONLY LOW HAZARD RATED CONTAINMENT PROTECTION VALVES
ARE INCLUDED IN THE TABLE BELOW. CONTAINMENT PROTECTION REQUIREMENTS FOR MEDIUM OR HIGH HAZARD RATED
TYPE PREMISES SHALL BE INDENTIFIED IN THE APPLICATION AND SUITABLE VALVES SPECIFIED BY THE DESIGNER.

8. ALL ABOVE GROUND PIPES AND FITTINGS SHALL BE FLANGED DICL PRESSURE CLASS PN16.
9, PIPES THAT PENETRATE CONCRETE SHALL BE LAGGED WITH 12MM THICK COMPRESSIBLE FOAM FILLER.

10. FOR FIRE HYDRANT SERVICES, ONLY ABOVE GROUND HYDRANT PILLARS AND FIRE HOSE REELS MAY BE
CONNECTED. CONNECTION OF WATER SERVICE TO A SPRINKLER SERVICE OR DOWNSTREAM OF A HYDRANT SERVICE
METER |S NOT PERMITTED. A FIRE SERVICE MUST NOT INTERCONNECT WITH A WATER DOMESTIC SERVICE UNDER ANY
CIRCUMSTANCE,

11. FOR CONNECTION OF UP TO 3 FIRE HOSE REELS TO A FIRE SERVICE, THE FIRE SERVICE BYPASS PIPE AND METER SIZE
SHALL BE 825MM, FOR CONNECTION OF MORE THAN 3 FIRE HOSE REELS TO A FIRE SERVICE, THE BYPASS PIPE AND
METER SIZE SHALL BE SPECIFIED BY THE DESIGNER.

12. FIRE SERVICES (SPRINKLER AND HYDRANT) SIZES OF 100MM AND @150MM SHALL BE INSTALLED WITH ISOLATING
GEAR OPERATED BUTTERFLY VALVES WHICH SHALL BE LOCKED IN THE OPEN POSITION WITH THE USE OF QFES
APPROVED ‘003 TYPE’ LOCKS.

13. INSTALL BUTTERFLY VALVES WITH THE SPINDLE/STEM ALIGNED IN THE HORIZONTAL PLANE TO ENABLE THE
LOWER PART OF THE DISC TO MOVE IN THE FLOW DIRECTION WHEN THE VALVE IS OPENED. ALIGN OPERATING WHEELS
IN THE TOP HORIZONTAL PLANE (REFER UNITYWATER PR9693 SPECIFICATION FOR MECHANICAL INSTALLATIONS,
‘SECTION 8.1.1.23).

Ts. WATER SERVICE SIZES OF 250MM SHALL BE SUPPLIED AND INSTALLED WITH WATERMARKED BALL VALVES AND
UNIONS.

15. ALL WATER METERS SHALL BE SPECIFIED, SUPPLIED AND INSTALLED IN ACCORDANCE WITH UNITYWATER
SPECIFICATION FOR WATER METERS (Pr10068),

16. AT THE LIMIT OF WORKS, THE DEVELOPER'S LICENSED PLUMBER IS RESPONSIBLE FOR REPLACING GASKET(S) AT
ALL VALVE FLANGE FACE(S).

17. TESTING OF ALL CONTAINMENT PROTECTION DEVICES (ITEMS 5, 6, 10 & 17 WHERE APPLICABLE) SHALL BE CARRIED
QUT BY THE PROPERTY OWNER'S BACKFLOW ENDORSED LICENSED PLUMBER AND IN ACCORDANCE WITH THE
REQUIREMENTS OF AS 2845.3.

18. WHERE THE INSTALLATION IS ADJACENT TO A TRAFFICABLE AREA AND NOT SEPARATED BY A STANDARD
RAISED KERB, THE DESIGNER SHALL SPECIFY ADEQUATE BOLLARD PROTECTION OF THE ASSEMBLY ARRANGEMENT.

 

 

 

 

 

  
   
   

 

T
SUPPLY MAIN

$2.0 Meters

FLANGED DICL
PRESSURE CLASS

PN16 NN

ONLY DI PIPE 7
‘ABOVE GROUND

(PROPERTY BOUNDARY]

ROAD RESERVE (TYP.)

 

 

 

 

 

 

 

300 MIN. CLEAR
ABOVE FSL

 

 

(ON 25 SHOWN,

FSL

 

 

 

 

600 Mik cover |

 

 

    

‘WATER (POTABLE) SERVICE
OFFTAKE TEE WHERE REQUIRED

‘THRUST BLOCK FOR ABOVE GROUND PIPE, WHERE PIPE DIAMETER

IS 100MM AND GREATER, MATERIAL TO BE DUCTILE |
IRON (DITBP) & WHERE PIPE DIAMETER IS LESS
THAN 100MM, PIPES TO BE OF RIGID APPROVED
MATERIAL SUCH AS STAINLESS STEEL, SUITABLY

 

 

 

‘METER & PIPE SUPPORT AS REQUIRED
WITH CONNECTION ISOLATED FROM
METER/PIPE

FIRE SERVICE o~
ELEVATION A
SCALENTS. (J

(HYDRANT AND HOSE REELS)

    
    

 

   

 

 

 

 

   

 

    

 

 

   

 

 

 

 

       

  

 

 

 

ABOVE FSL

300 MIN, CLEAR

 

NOTES:
THIS DRAWING MUST BE READ IN CONJUNCTION WITH UW-6885-1108-4 FOR LAYOUT
ARRANGEMENT VIEWS AND NOTES.

NEW: CHECK VALVE TYPE FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘SUPPORTED & THRUST RESTRAINED, N65 SHOWN AND DN80+
=> | LEVER OR GEAR ACTUATED
Se 1
els |
aa
2 Biz Er | + ___ ever &pire support as KEY FITTING LIST (ALL FITTINGS SUBJECT TO UNITYWATER APPROVAL]
2s 33 | TE tron cereyere ITEM QTY| ASPECT DESCRIPTION INSTALLATION
2\= 2 FSL NO. | BY
' | 1/4 ‘APPROVED CONNECTION (SPECIFY UNDER PRESSURE OR CUT-IN METHOD PER NOTE 6) | _UNITYWATER
' MAIN MAIN ISOLATION RESILIENT SEATED GATE VALVE (MIN DNT00 FOR SPRINKLER OR FIRE
' f 2 | 1 | OFFTAKE | HYDRANT SERVICE) PER SEQ-WAT-1301-1, WITH VALVE BOX AND COVER PER UNITYWATER
i 1 SEQ-WAT-1305-1 AND SEQ-WAT-1306-1.
1 | \_ concrete support BLock 31a | FIRE ISOLATION BUTTERFLY VALVE GEAR OPERATED LOCKABLE, CLOCKWISE CLOSING UNITYWATER
1 ~ | TO METER SUPPORT ¢ (ONES SHOWN) SPRINKLER! DIRECTION (MIN SIZE DN100 FOR FIRE HYDRANT SERVICE)
| MISTER (POTABLE). SERVICE , , «| 2 | oR FIRE BUTTERFLY NALYE. LUGGED TAPPED TYPE, GEAR OPERATED, LOCKABLE (CHECK DEVELOPER
“} ELEVATION (eB 5 [1] Seven” [SPRINKLER SERVICE SINGLE CHECK VAI VE TESTABLE (SCVT |__DEVELOPER
. THAN OOM, DOMESTIC SERVICE \ AA | SCALENT.S. am FIRE HYDRANT SERVICE SINGLE CHECK VALVE, TESTABLE (SCVTI (HN SIZE 01001 | DEVELOPER =
Lo" WATER SUPPLY PIPE MATERIAL BELOW GROUND IS ” Lywpusrievock ett pre | BALL VALVE THREADED, LOCKABLE (WATER METER ISOLATION) = ON |
MAIN E100, INCLUDING BEND FITTINGS. ' 9 | 2 | HYDRANT | BALL VALVE, THREADED, LEASE CHECK VALUE IGEN DEVELOPER
10 [1] SERVICE | SINGLE CHECK VALVE, TESTABLE (SCV) (MIN SIZE DN25) (FIRE SERVICE BYPASS) DEVELOPER
LIMIT OF UNITYWATER APPROVAL | > T_|1_| BYPASS [DI TAPPING BAND UPSTREAM IFIRF SERVICE BYPASS) RFFER SEQ-WAT-1108-5 IAITYWATER
i {4 DI TAPPING BAND DOWNSTREAM (FIRE SERVICE BYPASS) REFER SEQ-WAT-1108-5
THRUST BLOCK LIMIT OF ASSET INSTALLATION, & | 4 LIMIT OF ASSET INSTALLATION, OWNERSHIP BUTTERFLY VALVE, LUGGED, LEVER OR GEAR OPERATED (WATER METER ISOLATION) | wrywaTeR
OWNERSHIP & MAINTENANCE BY! & MAINTENANCE BY DEVELOPER/ B| 2 | FoR 296s OR BALL VALVE, THREADED, LOCKABLE FOR 50MM SIZE METER
UNITYWATER PROPERTY OWNER/BODY CORPORATE % [4 BASKET TYPE STRAINER (DIRT BOX’) |_UNITYWATER
WATER METER TO UNITYWATER SPECIFICATION (WATERIPOTABLE) SERVICE)
| 15 | 1__| WATER | INCLUDING ACCESSIBLE BASKET TYPE INLINE STRAINER ("DIRT BOX") |_UNITYWATER
(POTABLE) | BALL VALVE, THREADED OR BUTTERFLY VALVE, WAFER, LEVER OR GEAR
16| 2 | SERVICE | ACTUATED [CHECK VALVE ISOLATION) | DEVELOPER
ai 4 WATERIPOTABLE) SERVICE DOUBLE CHECK VALVE, TESTABLE (DCV) INCLUDING DEVELOPER
Y-TYPE STRAINER
APPROVED SCALE JOB DESCRIPTION DRAWING TITLE
NEIL McKENZIE & ASSOCIATES PTY. LTD. DRAWN A NOOSA YOUNGCARE WATER SERVICE CONNECTION DETAILS
CONSULTING ENGINEERS CHECKED NWN 32 VIEWLAND DRIVE
WIENS RPEO 2097, NEER 3 14/699a SANDGATE ROAD DESIGNED NM NOOSA HEADS
aan TE JE AIST, RPEO. 2087, NPER CLAYFIELD, , QLD 4011 APPROVED a ata TAG aun
THIS DRAWING REMAINS THE PROPERTY OF PHONE: (07) 3862 1886
No. REVISION DATE DWN | NEIL McKENZIE & ASSOCIATES (C) Copyright FAX: (07) 3862 1397 DATE SEP. 1 DELUCA DEVELOPMENT & CONSTRUCTION NUMBER Q20- 004- C09 NUMBER

 

 

 

 

 

 

 

 

 

 

 

 
Log in to download the original file

C09-WATER-SERVICE-CONNECTION-DETAILS-Rev.1.pdf · 4.9 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.