Lighting Report
Attached to the e-mail Response to Information Request MCU16/0079 (email 1 of 3).
Obtrusive Light – Compliance Report
At
Tewantin Noosa RSL
1 Memorial Avenue, Tewantin QLD 4565
We have undertaken the calculations of light spillage for the development at 1 Memorial
Avenue, Tewantin QLD 4565. The results have shown to comply with AS4282-1997
“Control of the obtrusive effects of outdoor lighting” and will not cause interference or an
environmental nuisance with the night time amenity of the residential areas.
1) CONDITION 1 – PRE-CURFEW IN COMMERCIAL AREAS:
2) CONDITION 2 – CURFEW IN COMMERCIAL AREAS:
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original (Lighting Report.pdf)
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 1 page
Page 2
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Residents East
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0
0.1 0.0
0.1 0.0
0.1
0.2 0.0
0.1
0.2 0.0
0.1
0.2 0.0
0.1
0.2 0.0
0.1
0.2 0.0
0.1
0.2 0.0
0.2
0.1 0.0
0.2
0.1 0.0
0.1
0.2 0.0
0.2
0.1 0.0
0.1
1 2
PELICAN 3
STREET 4 5 6 7 8 9
1.3 2.7
MH: 6 MH: 6
RWD
RWD
MH: 6 RWD RWD
4.8 9.3 18.6 17.6 13.5 14.2 22.8 13.9 13.8 20.2 15.0
17
9.4 5.7 5.0 4.3 2.9 3.6 5.0 3.6 3.5 5.0 4.2 1
AVENUE
Carpark East
10.6 2.6 1.3 0.9 1.1 1.4 1.9 3.1 4.4 2.8
5 5
MH: 6
DP DP
2
STREET
BINS
FSR
FHR 2.4 6.5 11.0 19.1 10.0
PROPOSED MIXED MH: 6
USE DEVELOPMENT RWD
RWD
DP DP DP
POINCIANA
FWG
DOONELLA
E
3
4
DD
5
D
C
EXISTING BUILDING
FHR
B
4
A
Calculation Summary
1 2 3 4 5 6 7 8 9 10 Area Description Units Avg Max Min Max/Avg UG Height
Carpark East Lux 7.67 22.8 0.9 2.97 N.A. 0
Obtrusive Light - Resident East_ N.A. 22.24 60 1 2.70 N.A. N.A
Obtrusive Light - Resident East_ Lux 0.06 0.2 0.0 3.33 N.A. N.A
Residents East Lux 0.01 0.1 0.0 10.00 N.A. 0
DESIGN NOTES:
THIS CALCULATION IS FOR INFORMATION ONLY AND NOT FOR CONSTRUCTION.
THE MAINTENANCE FACTOR APPLIED TO THIS CALCULATION IS 0.8 FOR LED AND 0.7 FOR FLUORESCENT
FITTINGS.
Luminaire Schedule
THIS DESIGN CALCULATION IS BASED UPON THE DRAWINGS SUPPLIED BY THE ARCHITECT, AND OTHER
DESIGN INPUTS ASSUMED BY US, AS DETAILED IN THIS DOCUMENT. Symbol Qty Label Description LLF Lum. Lumens Total Watts
IN PRACTICE, THE ACCURACY OF THE VALUES WILL DIFFER DUE TO ENVIRONMENTAL VARIATIONS SUCH
1 GNS070H 2 1xHSI-MP 70W CO_NDL Pierlite Genesis I 70W MH E27 Wide Wall Mounted at 6.0m 0.700 3344 85
AS ACTUAL LUMINAIRE POSITIONING, ROOM SURFACE REFLECTANCE, SUPPLY VOLTAGE, LOCAL 4 GNS070H 2 1xHSI-MP 70W CO_NDL_1Pierlite Genesis I 70W MH E27 Wide Poll Mounted at 6.0m 0.700 3344 340
LUMINAIRE AMBIENT TEMPERATURE, OBSTACLES/FURNITURE, ETC. THESE RESULTS ARE ALSO SUBJECT
TO NORMALLY ACCEPTED PHOTOMETRIC TOLERANCES, AND CALCULATION/PROGRAM UNCERTAINTIES.
rev date drawn reason for issue consulting engineer project
1
2
16.09.16 DN.L. LIGHTING CALCULATIONS
21.09.16 DN.L. REVISED CALCULATION SURFACE
Cushway Blackford & Associates Pty Ltd
ABN 23 010 522 988
TEWANTIN NOOSA RSL
ELECTRICAL SERVICES
P 07 3896 1100 scale designed
E [email protected]
5 Trafalgar Street, Woolloongabba QLD 4102
drawing title N.T.S. @A3 DN.L.
PO Box 1517, Coorparoo DC QLD 4151 EXTERNAL CARPARK LIGHTING CALCULATIONS project number drawing number revision
DO NOT SCALE ANY PART OF THIS DRAWING
ALL DIMENSIONS ARE TO BE TAKEN FROM THE ARCHITECTS DRAWINGS & ON SITE
138-11-2 001 2