J&P Richardson Industries Pty Ltd -9-
4.2.3 Geometry
The magnetic field calculations will be based on the intermediate pole top construction
shown in Appendix 2 for F790/F7298. A simplified ‘stick figure’ representation of the
structure geometries is reproduced in Figure 4 below for convenience.
Figure 4 F790 / 7298 Intermediate construction geometry ( IS(C)E
0.09m
2.00m
AФ CФ
1.90
BФ BФ
2.30m
1.90
m
CФ AФ
4.3 Magnetic and electric field calculations
4.3.1 Scenario1 average feeder load
The results of electric and magnetic field calculations relevant to scenario1 are summarised
in Table 7 below and Figure 6 and figure 7 overleaf.
Table 7 EMF levels scenario1 average 132kV feeder load
Calculated value at edge of
4mG offset
PARAMETER easement Maximum
Northern Southern Northern Southern
Magnetic Field strength 0.54mG 0.71mG N/A N/A 1.83mG
Electric Field strength 0.139kV/m 0.113kV/m ------ ------ 0.329kV/m
Hollett Road EMF Study V1.0