Request for Amended Advice Agency Response_Energex_Council CDA_01-04-2020

Attached to the e-mail Request for Energex to provide an Amended Advice Agency Response - 152006.1999.4.

of 32

Page text shows just the words. Original shows the document exactly as it was published.

Very large file: it may take a few minutes

The original of this document is very large (12.4 MB). Opening the original or downloading it may take a few minutes. Please be patient and don't click again. The page text is quick to read. If you are on mobile data, it is best to wait until you are on Wi-Fi.

        J&P Richardson Industries Pty Ltd           -9-


4.2.3   Geometry
        The magnetic field calculations will be based on the intermediate pole top construction
        shown in Appendix 2 for F790/F7298. A simplified ‘stick figure’ representation of the
        structure geometries is reproduced in Figure 4 below for convenience.

        Figure 4           F790 / 7298 Intermediate construction geometry ( IS(C)E

                   0.09m


                                                            2.00m

                   AФ                               CФ

                                                            1.90

                   BФ                               BФ
                             2.30m
                                                            1.90
                                                            m
                   CФ                               AФ




4.3     Magnetic and electric field calculations

4.3.1   Scenario1 average feeder load
        The results of electric and magnetic field calculations relevant to scenario1 are summarised
        in Table 7 below and Figure 6 and figure 7 overleaf.

        Table 7            EMF levels scenario1 average 132kV feeder load

                                        Calculated value at edge of
                                                                            4mG offset
               PARAMETER                        easement                                             Maximum
                                         Northern         Southern    Northern    Southern

         Magnetic Field strength         0.54mG            0.71mG       N/A          N/A              1.83mG

         Electric Field strength        0.139kV/m         0.113kV/m    ------        ------          0.329kV/m




        Hollett Road EMF Study                                                                V1.0
Log in to download the original file

Request for Amended Advice Agency Response_Energex_Council CDA_01-04-2020.pdf · 12.4 MB (very large file)

Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.