Services and infrastructure works (such as stormwater, Underground services are not located within 20 metres of a tower,
sewerage, water and the like) do not impact on the safety and pole, stay or substation boundary.
reliability of substations or major electricity infrastructure.
AO9.2
No valve pits occur within:
(a) for transmission infrastructure, 60 metres of a tower, pole
or stay; or
(b) for distribution infrastructure, 20 metres of a tower, pole or
stay.
AO9.3
Underground services traversing an easement cross at right
angles to the overhead or underground lines.
**FINAL DRAFT Post Consultation 2019**