Attachment 1 - Site Inspection Report
Introduction As per your request, David Wild from EC Engineers completed an inspection of 2/16 Grant St, Noosa Heads on Tuesday 25 October 2025. The inspection was undertaken at the request of the building owner – Maan Investments P/L. The following report outlines the results of our inspection in relation to the structural and future performance of the right side elevation planter boxes. Background The property comprises of a residential duplex building which was completed approximately 18 months ago. Its construction includes split floor levels across supported by a concrete slab on ground. The first level features a suspended concrete floor slab. The walls of the building comprise of a rendered and painted finish along with a low-pitched roof. Aerial view of property The building is constructed on an elevated and sloping lot which falls from the rear towards the street front. The dwelling has been designed to follow the profile of the land. As we understand, towards the end of construction council approved for the installation of a timber planter box to be installed along the right-side elevation of the building. The planter boxes extend from the entry area to the rear of the building extending past the ground floor rooms. Page 2 of 10 ENGINEERING REPORT Address: 2/16 Grant St, Noosa Heads Reference: 112351