Lighting Report
Attached to the e-mail Response to Council information request - MCU16/0066 & OPW16/ 0133 - email 1 of 3.
13 Omaru Street
Loganholme QLD 4129
+61 400 384 001 m
[email protected] e
www.rubidiumlight.com.au w
Cooroy Highway
Service Station
Lighting Plan
Environmental
rubidium
Mitigation
Prepared for
light
Hass Holdings
1
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
Large file: the download may take up to a minute.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 14 pages
Page 2
Prepared for
Safe Developments
Version Author/Reviewer Date Description of changes
V1 Trent Dutton 13/10/16 Draft for Comment
V2 Trent Dutton 13/10/16 Reviewed by client
Prepared by
Rubidium Light
13 Omaru Street
Loganholme Queensland
Australia 4129
ABN: 150 778 923 06
Phone: +61 400 384 001
[email protected]
www.rubidiumlight.com.au
© 2016 Rubidium Light
The information contained in this document produced by Rubidium Light is solely for the use of the client identified on the
cover sheet for the purpose for which it has been prepared and Rubidium light undertakes no duty to or accepts any
responsibility to any third party who may rely upon this document. All rights reserved. No section or element of this
document may be removed from this document, reproduced, electronically stored or transmitted in any form without the
written permission of Rubidium Light.
About Rubidium Light
Rubidium Light is a specialist lighting design consultancy that works with stakeholders across many areas of development
from concept to final construction.
Rubidium Light has been operating since 2011 and brings together an in depth knowledge of lighting and its application in
technically difficult lighting solutions.
Rubidium Light prides itself on its ability to react quickly and in a cost effective manner to provide outcomes both
responsible and cost effective to its clients and the environment.
rubidium
light
2
Page 3
Contents
Cover Page………………………………………………………………………………………………………………………….. 1
Document Information………………………………………………………………………………………………………………2
About Rubidium Light……………………………………………………………………………………………………….……. 2
Contents……………………………………………………………………………………………………………………………... 3
Executive Summary………………………………………………………………………………………………………………... 4
Introduction………………………………………………………………………………………………………………………….. 5
General Exterior Lighting………………………………………………………………………………………………………….. 5
• Post Tops 5
• Downlights 5
General Lighting Requirements..………………………………………………………………………………………………… 6
• AS1158 6
• AS4282 6
• Fuel Retailers 6
Illuminated Signs……………………………………………………………………………………………………………………. 7
Conclusion……………………………………………………………………………………..……………………………………...8
rubidium
light
3
Page 4
Executive Summary
Noosa Council outlined a number of concerns regarding lighting and illuminated signage at the proposed development site
referred to as Cooroy Highway Service Station in a RFI document MCU16/0066.
Rubidium Light has been commissioned to investigate and design an effective lighting plan taking into consideration the
RFI from Noosa Council, relevant Australian Standards and Fuel Retailer’s lighting requirements.
General Lighting
After careful design Rubidium has supplied a lighting plan able to satisfy all major fuel retailer’s requirements and AS1158
Lighting for Public Spaces (Cat 11a) while also showing compliance with AS4282 Control of the Obtrusive Effects of
Outdoor Lighting (Pre-curfew 11pm Commercial Boundary)
We have also been able to demonstrate compliance with Curfewed (after 11pm) Commercial Boundary with min offset of
10m with included dimming the 2 Northern post top luminaires only.
Signage
Illuminated signage should be designed to be not brighter than 300cd/m2 once installed. This will meet Noosa Council
requirements for illuminated signage.
Illuminated signage is critical to the successful night time operation of a fuel retailer and ensures the business appears to
be operating.
The appearance of “open for business” is part of the design of this project due to the site location on a major highway and
its capacity as a rest stop. Rest stops on major highways are critical to the ongoing safety of all road users.
rubidium
light
4
Page 5
Introduction
Rubidium Light has been engaged to supply environmental lighting plan ensuring compliance with the following standards
• AS1158 – Lighting for Public Spaces
• AS4282 – Control of the Obtrusive Effort of Outdoor Lighting
• Noosa Council 3000cd/m2 limit on illuminated signage
• Fuel Retailer’s Lighting Requirements
In conjunction with our supplied drawings, we will investigate each item above and demonstrate our proposed control
measures resulting in a compliant lighting plan. This plan not only meets the required standards but can ensure the
profitable running of this site and increased safety for road users.
When integrated into the fabric of the project design, good light practise and lighting control can be inexpensive and the
result impressive to all stakeholder when compared to the outcome of lighting control post construction which is always a
compromise on architectural look and “bolt-on” lighting control measures.
Please read this report in conjunction with drawings and data sheet provided.
General Exterior Lighting
We have proposed that the general exterior lighting for this project be supplied by two methods
1. Post top luminaries for open areas.
2. High output downlights for covered areas.
Post tops
The lighting of large exterior areas are most economically supplied by large post
top luminaries impacting a large areas and reducing the quantity required to a
minimum. However this type of lighting can provide unwanted spill outside the
property. To avoid this we have used the following control measures:
• Mounting height of 7m which is the same total height of the proposed
building on-site.
• All post top luminaires are mounted on the perimeter of the site and
project their light toward the centre of the project.
• Selection of output and placement of fittings which allow for
compliance with relevant standards without over lighting.
• Selection of luminaires with strong cut-offs to the back of the fittings
rubidium
(towards property boundary).
Downlights
The lighting of covered areas have been provided by high output LED downlights.
Typically these areas are lit to a much higher level than the surrounding hardstand and
provides safety around fuel transfer equipment and a clear path from pumps to retail
counter. Generally lighting these areas will have little impact on spill light as they are
located well within the site and will also have good light control due to their recessed
construction.
light
5
Page 6
General Lighting Requirements
Australian Standard AS1158.3.1
This Australian Standard 1158 and part 3.1 deals direct with the hardstand areas surrounding the site buildings. It is
defined as “Parking spaces, aisles and circulation roads’’. This definition also requires further refinement based on the
level of night time activity and risk of crime. For the purpose of this site we have selected the highest level of night time
activity which results in a subcategory of P11a.
It is also worth mentioning that this level can be changed to a lower category if the expected amount of activity is reduced.
We have taken advantage of this to allow for the reduction in lighting levels to the overflow car park area only during
Curfewed hours of operation e.g. after 11pm. This area would generally not be in use during late night hours and the
ability to dim luminaires on the northern perimeter will allows us to comply with Curfewed hours spill lighting requirements.
Australia Standard AS4282
This standard is our guide to spill lighting requirements and sets out where and how spill light is to be measured and its
acceptable levels. These acceptable levels are found after investigation of site uses and surrounding properties. It also
lays out acceptable levels of spill based on time before or after 11pm. (pre and curfewed hours)
As this is a industrial site and is surround by industrial zoning we evaluate spill base on this subcategory. These
acceptable limits are further reduced after 11pm.
Spill measures before 11pm are evaluated at all neighbouring property boundaries and will ensure both lighting level and
intensity is compliant. After 11pm the acceptable level reduce considerably but the point of measurement also move inside
the neighbouring properties to their minimum building offsets set by local council (if the site is vacant), in this case 10m.
Apart from impact to neighbouring properties we must also insure no adverse effect to road users on the surrounding
transport systems. This is measured by a system called Threshold increment. This system evaluates the intensity of
lighting on this project to road users.
Fuel Retailers
Major fuel retailers also set out lighting levels required to ensure safety and effective retail management of their sites. We
have ensured no matter if this site is run by an independent or leased to a major retailer, lighting levels will be sufficient.
The highest levels requested by fuel retailers are 400 lux maintained under fuelling canopy with a vertical level on pump
face of 150 lux. The attached design demonstrates compliance with these requirements.
rubidium
light
6
Page 7
I
Illuminated Signage
Illuminated signage on this site preform some important functions, retail appeal and downstream of this return some real
benefits to the community in road safety. Service stations are preferred by night time travellers due to then good facilities
and perception of safety.
The site requirements must also be balanced with the impact to neighbouring properties with consideration to their night
time uses. In this case all directly surrounding properties are zoned industrial and it can be reasonably expected that
these properties will not be inhabited during night time hours and if are illuminated sign on this site would not affect their
amenity.
rubidium
The illuminated signage has been reduced to only impact oncoming traffic on the Bruce Highway specifically, which further
restricts illuminated sign to the south and east faces of the site. This placement will ensure impact of illuminated sign is
only experienced toward the Bruce Highway and away from any residential properties to the west. Any impact on
properties to the east would be minimal due to the long distances and relative low intensity when compared to light levels
emitted from the Bruce Highway.
Noosa Council requires an illuminate sign to emit no more than 300cd/m2. This can be achieved in the design of the
signage and tested to ensure we meet this requirement. It is assumed that all signage on this project will be supplied
below this limit.
light
.
7
Page 8
Conclusion
This report should be read in conjunction with the following drawings and data sheets:
HAS0001-E01 Lighting Plan
Luminaire Data Sheets D1, D2, D2A, P1, P1A and W1
The above designs and data sheets can be used as examples for generic specification for selection of luminaires and
lighting layouts. They can be substituted for other fittings and layouts given all the above mitigation measures are included
and performance of luminaires are simular. This should be evaluated on a case by case basis upon tender offer.
We have supplied lighting plans and luminaire selection to meet all requirements laid out above. All general exterior
lighting requirements have been met while minimising spill light below AS4282 requirements for both pre and post
curfewed hours.
A limit has been set for the total brightness emitted from illuminated signage in compliance with Noosa Council
requirements. A clear understanding of the benefits of illuminated signage has been laid out and a demonstration on
adverse effect have shown that none exist due to surrounding zoning and distance to residential properties.
We are happy that all potential adverse effects on rural amenity have been mitigated while still achieving required lighting
levels to compliment this development.
This report has been produced for inclusion in a wider RFI response.
Trent Dutton
Principal Lighting Engineer MIES
rubidium
light
8
Page 9
NOTES:
1
LANDSCAPING THIS DRAWING IS INTENDED TO DEMONSTRATE THE DESIGN CONCEPT ONLY. IT IS EXPECTED THAT THE SCHEME WILL BE FURTHER DEVELOPED
Oe ~ ‘Upt
THE PROPOSED LIGHTING SCHEME COMPLIES WITH AS1158.3.1:2005 CAT P11(a) & P12 (DISABLED).
‘ 5 one wy” oe ee en IRE 7 >
we an aR Jer sit zea ze) 32.0 36.3 35a 300 483 BN
THE LIGHT LOSS FACTOR APPLIED TO THESE CALCULATIONS IS IN ACCORDANCE WITH AS1158.3.1:2005 AND IS BASED UPON THE FOLLOWING:
« — IP5X OR IP6X LUMINAIRE
* CLEANING CYCLE OF 4 YEARS IN NORMAL POLLUTION CATEGORY AREA
BULK LAMP CHANGE AT 50,000 HOURS OR 70% LED OUTPUT
e SPOT REPLACEMENT OF FAILED LAMPS
COMPLIANCE WITH AS4282 IS DEMONSTRATED FOR A COMMERCIAL AREA AT THE BOUNDARY OF NEIGHBOURING PROPERTIES FOR PRE-CURFEW
OPERATION AND CURFEWED OPERATION WITH TYPE P1A DIMMED TO 50%.
a
FOR CLARITY, ONLY HORIZONTAL ILLUMINANCE PLANES ARE SHOWN
/AITING.BAY
— eo so po ag ts peas a me bo ae PHOTOMETRIC DATA WAS PROVIDED BY MANUFACTURER. SOFTWARE USED FOR CALCULATIONS IS AGI32
lors] { 14
G9 Met a4 20n 29 se ia a2 0) Ge br or [teigvogyiple M62 86 8S 9.0 nz set a ae azar mf asa ma Obtrusive Light - Compliance Report Obtrusive Light - Compliance Report
|
PARKING a AS 4282-1997, Pre-Curlew, Commercial AS 4282-1997, Post-Curtow, Commercial
ee oe __ on Filename: DESIGN Filename: DESIGN RES SETBACK
Be M8 285 55 227 183 18s ae ae] me te PP) ws ree feo nse se UTDOOR, aan er eae 13/10/2016 75545 AM 13/90/2016 9:06:58 AM
| foe oO) oiniNe AREA, .
aia BP re hon aes Piss a ad i
sea ns ra ans me ne ass aa xf we for |.) ae Mluminance Ituminance
sigs so 22 ase iss asa na slo ea as aa Maximum Allowable Value: 25 Lux Maximum Allowable Value: 4 Lux
2 OVERFLC W fe ne ae) 0Q FAST FOOD ne ana 3 Calculations Tested (14) Calculations Tested (13):
PARKING z —_ Oh 97 5,°4 Test Max Test Max
se ak os as ass nes nt a 0 So 38-1 40.9 48.9 39.6 341 | | ot om 1 Calculation Label Results illum. Calculation Label = Results Mum.
owe 423 means In Be ua 8a] 1 . aus sas a2 ar ae os | [SERVICE STATION’ ObtrusiveLignt WEST_Ill_Seg! PASS 22.2 ObtrusiveLight RES WEST _II_Segt PASS 32
* | 20 Beers One ObtrusiveLignt SOUTH _|f_Seg1 PASS 0.9 ObtrusiveLignt RES W! {_Seg2 PASS 12
aaa ae akg as ask ie tata na DINING AREA [02 a0 et 9 ser en ( ai ObtrusiveLight SOUTH_If_Seq2 PASS 14 ObtrusivoLignt RES SOUTH_ ill Sogt PASS 0.4
ObtrusiveLight SOUTH_I_Seqg3 PASS 1.4 ObtrusiveLight RES SOUTH_Ill_Seg2 PASS O07
ObtrusiveLight SOUTH_IE_Seg¢ PASS O4 ObtrusiveLight RES SOUTH Ill Sea3 PASS 0.9
ObirusiveLight SOUTH _I_ Seo PASS 0.3 ObtrusiveLight RES SOUTH _Ill_Seg4 PASS 60.8
ObtrusiveLight SOUTH_If_ Seo6 PASS 03 ObtrusiveLight RES SOUTH Ill Sea5 PASS O4
ObtrusiveLight NOATH_Ill_ Segt PASS 21.8 ObtrusiveLight RES SOUTH fil Seg6 PASS 0.2
ObtrusiveLight EAST_Ill_ Seg! PASS = 0.2 ObtrusiveLight RES SOUTH Ill Seg7 PASS) = 0.2
“ ObtrusiveLignt EAST Ill Sea? PASS 04 ObtrusiveLight RES EAST il Seg! PASS 02
3s 36.56 949 776 22.2 181 143 at — — Bly osc oe ObtrusiveLight EAST Ill Seg? PASS 0.4 ObtrusiveLight RES EAST_Il_ Seg2 PASS 04
sf — ObtrusiveLight EAST _ill_ Seg4 PASS 1.3 ObtrusiveLight RES EAST_ tl Seg3 PASS 0.5
pos os 2 . wpa fe SERVICE : wae Obtrusivalight EAST_IlSegs PASS) (1.1 ObtrusiveLight RES EAST til Seg¢ PASS) 1.1
a oe sa ue np we fa |. | sk was ee Obtrusivelight EAST lit Seq PASS = 0.8
“ Bb}
\ 2.9 25.0 26.5 283 2.7 188 1s9 12h 10.3 for | Sopp STATION [tee BB sss 3.9 28.2 33.58 S18 aL 263 Luminous Intensity (Cd) At Vertical Planes
2a 20 23.9 266 21 233 2 tes up ne te ag SALES AREA les Luminous Intensity (Cd) Per Luminaire Maximum Allowable Value: 2500 Cd
2 nee 23 ca a3 Sef ns fue si v % Maximum Allewable Value: 7500 Cd eee *
\ina 222 one ane ae ars ca ter ef tse fas aN] — sine Control Anale: 83 Degracs Calculations Tested (13)
\ SERVICE Cailcutas
\ . ° 5 or res) I << ISERVICEBAY??:= 23 29 Luminaire Locations Tested (48) Calculation Label
\ LUIS Tent Homie: PASS Obtrusivel ight RES WEST Gd Sagi PASS
69 aa my a9 3a ObtrusiveLight RES WEST Cd Seg2 PASS
(seo ta a9 29 tna ane ake ana ObtrusiveLight RES SOUTH Cd Segi PASS
UNDERGROUND | ObttusiveLight RES SOUTH Cd_Seg2 PASS
«46.2 2.8 39,2 RETENTION TANK; | | Timashosd Inceoment (7) CdtrusivoLignt RES SOUTH Cd Seg? PASS
i vr ObtrusiveLight RES SOUTH_Cd_Seg4 PASS
cae . = r 5): CotrusiveLignt RES SOUTH Cd Seg5 PASS
Calculations Tested (6
/ — . Adepiation Test ObtrusiveLight RES SOUTH _Cd_Segs PASS
BIO RETENTION 2 Calculation Label Lumience Flomuits ObtrusiveLight RES SOUTH Cd_Seg7 PASS
BASIN ObirusiveLignt_ Ti EASEMENT EAST 10 PASS Cotrusivel ight RES EAST Ca Segt PASS
ObtrusiveLight_T) EASEMENT WEST 10 PASS ObtrusiveLight oo east cA Soa a
ObtrusivaLight_Ti TAYLOR SOUTH 10 PASS Cotrusivel igtt RES €d_Sog
Obtusivelight 1) TAYLOR NORTH 10 PASS ObtrusiveLight RES EAST_Cd_Seg4 PASS
. ObtrusiveLight_T! HOLTS WEST 10 PASS
BOOSTER t_T!| HOLTS EAST 10 PASS
an caSEMENT yom)
SITE LIGHTING PLAN . AS4282 REPORT BEFORE 11PM AS4282 REPORT AFTER 11PM TYPE
Luminaie Schedule FULL LIGHTING LEVEL P1A 50% DIMMED
Symbol Qty Label TotalLampLumens LLF Description
cE] 23 D1 18349 0.660 | VERSALUX HELIX 144W 4000K LED RECESSED EXTERIOR DOWNLIGHT
Oo 12 D2 3793 0.660 | VERSALUX ARES LEILA 43W 4000K LED WIDE BEAM RECESSED EXTERIOR DOWNLIGHT
Oo 1 D2A | 3793 0.660 | VERSALUX ARES LEILA 43W 4000K LED WIDE BEAM ASYMMETRIC OPTIC RECESSED EXTERIOR DOWNLIGHT
=| 8 Pt NA. 0.660 | LAD BEACON VIPER LARGE 223W 4000K LED POST TOP AREA LIGHT MOUNTED @ 7M
[J |2 PIA | NA. | 0.660 | LAD BEACON VIPER LARGE 223W 4000K LED POST TOP AREA LIGHT MOUNTED @ 7M C/W 50% DIMMING
LJ [2 Wi NA. | 0.660 | LAD BEACON VIPER LARGE 223W 4000K LED WALL MOUNTED AREA LIGHT MOUNTED @ 7M
Calculation Summary
Label CalcType Units Avg Max Min Min/Avg | Max/Avg
CAR PARK Ev 1 Mluminance Lux (23.20 (888 | 3.3 0.14 NA.
CAR PARK Ev 2 Mluminance Lux (2150 729 3.4 0.14 NA.
DRIVE THROUGH tlluminance Lux A 58.3 0.29 NA.
HARD STAND AREA tlluminance Lux 131.15 | 276 3.8 0.12 8.85
OUTDOOR DINING {luminance Lux (197.86 | 514 106 0.54 NA.
OVERFLOW Ev 1 Illuminance Lux 18.29 (584 4.0 0.22 NA.
OVERFLOW Ev 2 {luminance Lux 13.41 (51.5 32 0.24 NA.
STORE ENTRY Mluminance Lux 456.78 780 242 0.53 NA.
UNDER CANOPY Mluminance Lux 469.53 | 907 237 0.50 NA.
PWD CAR SPACE Mluminance Lux 50.98 |664 40.6 0.80 1.30 REN DER
Rev. Date Dm. _ Description Chika Project Tite Drawn: Chk M Date 43 1046
COOROY HIGHWAY ELECTRICAL SERVICES Soak: 5p
: Rubidium Light
SERVICE STATION LIGHTING LAYOUT Drawing No Rev Size M +51 4030400)
QUEENSLAND EXTERIOR LIGHTING
Loganholme QLD 4129
This drawing is protected by copyright and is not to be reproduced in part or whole without the written permission of Rubidium Light HAS 0001-E01 0 A3 E trent_dutton@notmailcom rubidium light
Page 10
Project Cooroy Service Station
Area Exterior Lighting
Type D1
Description Versalux Helix
Mounting Type Recessed
System Current 144W
Lamp Type LED 4000K
Lumen Output 18349 Lumens
Colour Rendering Index >80CRI
Optic Wide
IP Rating IP66
Impact Rating IK08
Finish White
Supplier Part Number HELIX18000MBRFW (NON-DIMMABLE)
Rubidium Light A 13 Omaru Street Loganholme Q 4129 M +61 400 384 001 E [email protected]
Page 11
Project Cooroy Service Station
Area Exterior Lighting
Type D2
Description Versalux Ares Leila225
Mounting Type Recessed
System Current 38W
Lamp Type LED 4000K
Lumen Output 3793 Lumens
Colour Rendering Index >80CRI
Optic Wide 40 degree
IP Rating IP66
Impact Rating IK06
Finish White
Supplier Part Number 536055
Rubidium Light A 13 Omaru Street Loganholme Q 4129 M +61 400 384 001 E [email protected]
Page 12
Project Cooroy Service Station
Area Exterior Lighting
Type D2A
Description Versalux Ares Leila225 Asymmetric
Mounting Type Recessed
System Current 38W
Lamp Type LED 4000K
Lumen Output 3793 Lumens
Colour Rendering Index >80CRI
Optic Wide 40 degree
IP Rating IP66
Impact Rating IK06
Finish White
Supplier Part Number 536059
Rubidium Light A 13 Omaru Street Loganholme Q 4129 M +61 400 384 001 E [email protected]
Page 13
Project Cooroy Service Station
Area Exterior Lighting
Type P1
Description LAD Beacon Viper Large
Mounting Type Post Top
System Current 223W
Lamp Type LED 4000K
Lumen Output 24685 Lumens
Colour Rendering Index >70CRI
Optic Type 4
IP Rating IP66
Impact Rating IK06
Finish TBC
Supplier Part Number VPL96NB-2204KT4UNVSF2
Rubidium Light A 13 Omaru Street Loganholme Q 4129 M +61 400 384 001 E [email protected]
Page 14
Project Cooroy Service Station
Area Exterior Lighting
Type P1A
Description LAD Beacon Viper Large
Mounting Type Post Top
System Current 223W
Lamp Type LED 4000K
Lumen Output 24685 Lumens
Colour Rendering Index >70CRI
Optic Type 4
IP Rating IP66
Impact Rating IK06
Finish TBC
Supplier Part Number VPL96NB-2204KT4UNV2PFSF2 (50% DIMMABLE)
Rubidium Light A 13 Omaru Street Loganholme Q 4129 M +61 400 384 001 E [email protected]
Page 15
Project Cooroy Service Station
Area Exterior Lighting
Type W1
Description LAD Beacon Viper Large
Mounting Type Wall Mounted
System Current 223W
Lamp Type LED 4000K
Lumen Output 24685 Lumens
Colour Rendering Index >70CRI
Optic Type 4
IP Rating IP66
Impact Rating IK06
Finish TBC
Supplier Part Number VPL96NB-2204KT4UNVWB
Rubidium Light A 13 Omaru Street Loganholme Q 4129 M +61 400 384 001 E [email protected]