3.5.1.2 Corrosion protection and compatibility
requirements for roofing
(a)Metal sheet roofing must be protected from
corrosion in accordance with Table 3.5.1.1.
(b)Where different metals are used in a roofing
system, including flashings, fasteners, guttering,
downpipes, etc., they must be compatible with each
other as described in Tables 3.5.1.2a to 3.5.1.2d and
(i)no lead materials can be used upstream from
aluminium/zinc coated materials; and
(ii)no lead materials can be used on roofs that form
part of a potable (drinking) water catchment area; and
(iii)no copper materials can be used upstream from
galvanised coated materials.
3.5.3.2 Materials
Gutters, downpipes and flashings must—
(a)be manufactured in accordance with AS/NZS 2179.1
for metal; and
(b)be manufactured in accordance with AS 1273 for
UPVC components; and
(c)be compatible with all upstream roofing materials in
accordance with 3.5.1.2(b); and
(d)not contain any lead if used on a roof forming part
of a potable water catchment area.
3.5.3.4 Installation of gutters
(a)Gutters must be installed with a fall of not less than
—
(i)1:500 for eaves gutters, unless fixed to metal fascias;
and
(ii)1:100 for box gutters.
(b)Eaves gutters must be—
(i)supported by brackets securely fixed at stop ends
and at not more than 1.2 m centres; and
(ii)be capable of removing the overflow volume
specified in Table 3.5.3.3a and Table 3.5.3.3b.
(c)Overflow measures in accordance with Table
3.5.3.4a
3.5.3.5 Downpipes — size and installation
20° FALL Downpipes must—
(a)not serve more than 12 m of gutter length for each
20° FALL down pipe; and
(b)be located as close as possible to valley gutters;
and
(c)be selected in accordance with the appropriate
eaves gutter section as shown in Table 3.5.3.2a to
Table 3.5.3.2c.
3.5.1.3 Minimum pitches for metal sheet roofing
profiles
2° FALL
metal roofing 5○ or more will be corrugated custom
orb uno
metal roofing between 2○ - 5○ will be trapezoidal
profile or similar
metal roofing at 1○ will be a concealed fastened
profile or similar
b
a
0 1m 5m
Revision Proposed Residence Address Client Scale
This plan shall remain the sole property of Suncoast Building Design and must not be 1/10 Sunseeker Cl Noakes 1:100
given, lent, hired out or otherwise disposed of or copied without the written permission of Noosaville
Suncoast Building Design. Drawn Page No.
Note: all dimensions/engineer details and relevant information to be checked and
confirmed by builder /client. Suncoast Building Design does not take any responsibility MM/SB 8
after drawings have been checked and confirmed by builder/client or construction has Suite 7 / 10 Grebe St, Peregian Beach mob: 0401565629
commenced. [email protected] Job No. Date Stage Drawing
www.suncoastbuildingdesign.com.au mob: 0491289102
20.141 01.05.23 DA Approval Roof Plan
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Design plans.pdfRelated documentApplication case desk ↗
About this file
- File size
- 577 KB (small file)
- File type
No other editions are linked here.