Council archive · source document
EGX_PROD_n7056534_28_Eenie_Creek_Road,_Noosaville_L3_SP246584 · OPW20/0145
2
3. Access to the easement and access along the easement must be available to
Energex personnel, including vegetation crews and regular routine line
inspection crews, and heavy equipment, such as Heavy Trucks, Machinery and
Cranes for construction, maintenance and emergency services, at all times.
4. Energex must be notified of construction on or near the easement, conductors
or structures prior to commencement of construction.
5. Stockpiling of spoil on the easement is prohibited.
6. The following clearance must be maintained from the top of any machinery
moving in the vicinity of energised conductors at all times:
132kV and 110kV conductors – 4.5m minimum clearance
All operators of machinery are to be made aware of the presence of high
voltage conductors. Should it be necessary to transport equipment or extend
any equipment, such that these clearances cannot be confidently maintained, a
Safety Advice request must be submitted to Energex via the following link:
https://www.energex.com.au/about-us/contact-us/forms/general-forms/safety-
advice-form
7. Lighting structures are not permitted in the easement without prior written
consent of Energex. Lighting designs for proposed developments (e.g. road,
carparks etc) on the easement are likely to require reduced height structures.
Please submit detailed design to Energex for approval. These drawings must
clearly show the following:
Proposed height of the lighting structures and the ground level at the
structure base;
Relative (to lighting structures) ground levels at Energex structures
(towers, pole etc) either side of the lighting structures; and
The location of the Energex structures in relation to the proposed
lighting.
8. Any future works in the vicinity of Energex assets are to be carried out in
accordance with the Electricity Entity Requirements: Working Near Overhead
and Underground Electric Lines. This guideline can be accessed via the
following link: https://www.energex.com.au/home/safety/safety-around-the-
network/safety-advice
Should you require further information regarding this matter, please contact the
undersigned on 0455 403 399 or [email protected] faithfully,
Benjamin Freese
Town Planner
Reference: HBD 7056534
Have you seen our fact sheets?
See the ‘considerations when developing around electricity infrastructure’ section of our website
www.energex.com.au/referralagency
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
EGX_PROD_n7056534_28_Eenie_Creek_Road,_Noosaville_L3_SP246584.pdfRelated documentApplication case desk ↗
About this file
- File size
- 207 KB (small file)
- File type
No other editions are linked here.