Bypass design The pressure relief pipe height and diameter can be
varied to accommodate the design peak flow rate and
The JellyFish® filter should be designed in an offline system driving head requirements. For these systems, the
configuration for most catchments. All stormwater filter driving head is calculated as the difference in elevation
systems will perform for a longer duration between between the top of the pressure relief pipe and the invert
required maintenance services when designed and of the outlet pipe.
applied in offline configurations. A standard offline
configuration has an external bypass that uses an When the internal bypass option is utilised, peak flow
upstream diversion structure. The elevation difference rates receive membrane filtration treatment up to the
between the top of the diversion structure and the filtration design flow rate, with the balance of the peak
JellyFish® filter outlet pipe invert should be a minimum flow receiving primary treatment only. In these cases,
of 455 mm. Excess flow that overflows the diversion, increased sump depth may be required to increase
bypasses the JellyFish® filter. sediment storage capacity and to minimise re-suspension
of previously captured sediment at peak flow rates.
For smaller sites an online configuration might be more
suitable. In these cases, an optional internal bypass It is also possible to configure this arrangement using
pressure relief pipe(s) can be placed in one or multiple a single diversion structure. Contact Humes for design
cartridge receptacles within the JellyFish® filter. assistance.
Figure 5 – JellyFish® filter offline arrangement without diversion weir
JellyFish® unit outlet I.L.
Diversion chamber inlet is 455 mm lower than
I.L. of high flow bypass
inlet
w Low flo
flo w
w
Lo
High flow bypass
Bypass inlet I.L. is 455 mm
higher than JellyFish®
unit outlet
Diversion chamber JellyFish® unit Collection chamber
Figure 6 – JellyFish® filter offline arrangement with diversion weir
JellyFish® unit outlet I.L.
is 455 mm lower than
Diversion chamber inlet top of weir wall
w Low flo
flo w
w
Lo
High flow bypass
Top of weir is 455 mm
higher than I.L. of
JellyFish® unit outlet
Diversion chamber JellyFish® unit Collection chamber
10 JellyFish® filter
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Jellyfish Compliance with SEQ MUSIC Modelling Guidelines.pdfRelated documentApplication case desk ↗
About this file
- File size
- 5.0 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.