MCU16/0079 Appendix F - Environmental Noise Imact Assessment
RS L MECHCANICAL PLANT NOIS E EMIS S IONS AT:
R1: Dwellings Due South R2: Dwelling Due East across Pelican Street
Commercial A/C units 60 dB(A) 3m Commercial A/C units 60 dB(A) 3m
Number of units 2 units Number of units 2 units
Total of units 63 dB(A) 3m Total of units 63 dB(A) 3m
Distance to dwelling 49 m Distance to dwelling 75 m
Distance attenuation (-6 dB per doubling of distance) -24 dB(A) Distance attenuation (-6 dB per doubling of distance) -28 dB(A)
Roof directivity at plant deck -6 dB(A) Roof directivity at plant deck -6 dB(A)
Component impact (includes façade reflection) 35 dB(A) Component impact (includes façade reflection) 32 dB(A)
Impact inside with windows open 28 dB(A) Impact inside with windows open 24 dB(A)
Basement exhaust fan 66 dB(A) 3m Basement exhaust fan 66 dB(A) 3m
Number of units 1 units Number of units 1 units
Total of units 66 dB(A) 3m Total of units 66 dB(A) 3m
Distance to dwelling 84 m Distance to dwelling 48 m
Distance attenuation (-6 dB per doubling of distance) -29 dB(A) Distance attenuation (-6 dB per doubling of distance) -24 dB(A)
90 degree bend at exhaust side of fan and risers acoustically lined -14 dB(A) 90 degree bend at exhaust side of fan and risers acoustically lined -14 dB(A)
Component impact (includes façade reflection) 26 dB(A) Component impact (includes façade reflection) 30 dB(A)
Impact inside with windows open 18 dB(A) Impact inside with windows open 23 dB(A)
Combined mechanical plant at façade 36 dB(A) Combined mechanical plant at façade 34 dB(A)
Combined mechanical plant inside windows open 28 dB(A) Combined mechanical plant inside windows open 27 dB(A)
R3: Dwelling Due East across River
Commercial A/C units 60 dB(A) 3m
Number of units 2 units
Total of units 63 dB(A) 3m
Distance to dwelling 330 m
Distance attenuation (-6 dB per doubling to river, river 0 dB) -34 dB(A)
Roof directivity at plant deck -6 dB(A)
Component impact (includes façade reflection) 26 dB(A)
Impact inside with windows open 18 dB(A)
Basement exhaust fan 66 dB(A) 3m
Number of units 1 units
Total of units 66 dB(A) 3m
Distance to dwelling 330 m
Distance attenuation (-6 dB per doubling to river, river 0 dB) -31 dB(A)
90 degree bend at exhaust side of fan and risers acoustically lined -14 dB(A)
Component impact (includes façade reflection) 23 dB(A)
Impact inside with windows open 16 dB(A)
Combined mechanical plant at façade 28 dB(A)
Combined mechanical plant inside windows open 20 dB(A)