RATIONAL METHOD SUMMARY CALCULATIONS - EXISTING
CASE
Cachment ID Existing Compiled By: MR
Catchment Area, A (ha) 0.077 Checked By: LO
Date: 2024/11/01.
Project Name: 51 Elanda Street, Sunshine Beach
Project No: SSC-2401
Time of Concentration, t (min) 5.000
Impervious Fraction, fi 0.450
Land and Soil Permeability Description (if fi < 0.2)
1 Hour 1:10 year rainfall intensity at locality, 1I10 75.200
10 year Discharge Coefficient, C10 0.800
Rainfall Intensities, Iy (mm/hr): Coefficient of Discharge, Cy: Rational Method, Qy (l/s) : Difference from Post Dev
I63.20 125.00 C63.20 0.64 Q63.20 17.11 -1.71
I50 142.00 C50 0.64 Q50 19.44 -1.94
I20 193.00 C20 0.76 Q20 31.37 -3.14
I10 227.00 C10 0.80 Q10 38.84 -3.88
I5 259.00 C5 0.84 Q5 46.53 -4.65
I2 301.00 C2 0.92 Q2 59.23 -5.92
I1 333.00 C1 0.96 Q1 68.38 -6.84