Attachment E - Unitywater Advice Note
Head Office:
Ground Floor, 33 King Street
Caboolture QLD 4510
Mailing Address:
PO Box 953, Caboolture QLD 4510
1300 0 UNITY (1300 086 489)
www.unitywater.com
ABN: 89 791 717 472
Services Advice Notice
South-East Queensland Water (Distribution and Retail Restructuring) Act 2009
Notice Details
Development Application No: 2023023661
Street Address: 58 Rene St, NOOSAVILLE, QLD 4566.
Property Description: Lot 58 RP228905
Proposal: Industry Warehouse Development
Local Government Area: Noosa Shire Council
Date of Issue: 5/12/2023
Assessment Officer: Bruck Gebreselassie
This notice is provided in accordance with Section 99BRAC of the South-East Queensland
Water (Distribution and Retail Restructuring) Act 2009.
Please note that the Service Advice Notice is advisory only and does not represent approval
of the connection or any associated works. The Service Advice Notice is valid for 6 months
from the date of this notice.
Application must be made to Unitywater for approval of the connection or associated works.
This development site is located within Unitywater’s current water supply and sewer
connections area. These services are available to the site.
Unitywater’s infrastructure in the area has sufficient capacity to cater the proposed
development demand.
Easements will be required in accordance with the South-East Queensland Water Supply
and Sewerage Design and Construction Code over water/sewerage mains located in private
property boundaries.
With regards to the driveway along the southern boundary, Unitywater cannot make a
decision without looking the proposal in detail. A Build Over application is required if the
proposed structure is within 3m of horizontal clearance, measuring from the centre of the
sewer main to the proposed structure. Please refer to the following link for more details.
Check before you build (unitywater.com)
Location of existing Unitywater infrastructure can be viewed at Unitywater’s website.
Precise details of infrastructure are available via Detailed Infrastructure Plan (DIP) on
Page 1 of 3
Unitywater is a statutory authority that provides water and sewerage services for the Unitywater has certification to
OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas. Environmental ISO 14001:2004 Reg No 4259
Quality Systems ISO 9001:2008 Reg No 4258
Revision No: 2 Effective Date: 19/02/2015 Next Review Date:19/02/2018
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 2 pages
Page 2
application. Further information on this process is available at Unitywater website
http://www.unitywater.com/reference library.
This proposal would require the applicant to apply to Unitywater for a ‘A&C Connection
Application’ which includes application/s for ‘network works’. For further information on this
process refer to Unitywater’s website at http://unitywater.com/Building-and-developing.
For current information in relation to all Unitywater’s fees applicable to connection
applications and development related works please refer to Unitywater website at
https://www.unitywater.com/Building-and-developing/pricing-fees-and-charges.
Fire Fighting Requirements
Direct connection of pressure boosting pumps to Unitywater network is not favoured by
Unitywater. Sometimes the requests may be considered depending on the capacity,
condition and sufficient connectivity of the reticulation system in the area. If there is any
such proposal, details of the pumps (pump curves and design calculations) needs to
be submitted to Unitywater’s Development Services for approval prior to installation.
This request shall include a certification by the hydraulic consultant that the maximum
flow rate of the installed pumps will be no greater than Unitywater’s standards of service,
relevant for the site.
Unitywater’s level of service towards firefighting capacity is guided by SEQ Design &
Construction Guidelines whereas the internal fire suppression systems of buildings shall
comply with the requirements of AS 2419.Therefore it is the responsibility of the developer
to design and install the necessary infrastructure such as pumps, break tanks etc, so that
the internal fire suppression system complies with the relevant standards.
The Usage of street hydrants as standalone firefighting facility to a building will be entirely
at the risk of the developer. Unitywater will not guarantee that the street hydrants will comply
with the requirements of AS 2419 or of QFES. This applies to dry hydrant systems too.
Unitywater, at its discretion, may change the operational regime of its water mains.
However, it won’t be changed below Unitywater’s minimum level of service towards street
hydrants. These values are shown in Table 1 below. For more details, please refer to the
latest version of SEQ Design & Construction Code.
It is the Applicant’s responsibility to ensure that it has all necessary consents and approvals
to carry out any connection related works in a publicly controlled place (e.g. Council, DTMR)
or property that is not owned or controlled by the Applicant prior to starting such works.
Page 2 of 3
Unitywater is a statutory authority that provides water and sewerage services for the Unitywater has certification to
OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas. Environmental ISO 14001:2004 Reg No 4259
Quality Systems ISO 9001:2008 Reg No 4258
Revision No: 2 Effective Date: 19/02/2015 Next Review Date: 19/02/2018
Page 3
Flow available Residual Head
from Unitywater in Water main
Type of Use Main (meters)
(Litres/second)
Residential dwellings of less than 3 storey 15 12
Commercial that is ancillary to residential use 15 12
Multi Storey residential greater than 3 storeys 30 12
Commercial and or Industrial 30 12
Should an approval for connection be provided by Unitywater, the developer will need to
apply to Unitywater for a Private Works Quote in relation to the cost for new metered water
supply service connections and live connections to existing water/sewer infrastructure by
Unitywater. A copy of the connection approval and associated approved plans detailing the
new connections must accompany the private works quotation application. Please refer
Unitywater’s website at http://www.unitywater.com/private-works. for further details.
An existing 150mm diameter sewer main travers the lot 5 site. Unitywater’s preference is
to relocate all sewers clear of any proposed building footprints. Any proposal to build over
and/or adjacent to a Unitywater asset must be assessed under the Queensland
Development Code (QDC) 1.4 – Building over or near relevant asset. (Refer
www.hpw.qld.gov.au). This assessment could be performed through Private Building
Certifier or Registered Professional Engineer of Queensland (RPEQ). Policy. Further
information on this process is available on Unitywater’s website at
http://www.unitywater.com/Building-and-development/renovating-or-extending
All water supply and sewerage works must be designed and constructed in accordance with
the South-East Queensland Water Supply and Sewerage Design and Construction Code,
Unitywater’s Connections Administration Manual and any other matter Unitywater considers
to be relevant to the connection or supply of its water services or wastewater services.
Any change to Unitywater’s existing infrastructure as required by this proposal must be
carried out at no cost to Unitywater.
Payment of Levied Charges will be required in accordance with Unitywater’s Infrastructure
Charges for water supply and sewerage.
If you have any queries about the advice, please contact Unitywater at
[email protected] or by phone on 1300 086 489.
Yours sincerely,
Development Services
Unitywater
Page 3 of 3
Unitywater is a statutory authority that provides water and sewerage services for the Unitywater has certification to
OH&S ISO 4801:2001 Reg No 4260
Moreton Bay, Sunshine Coast and Noosa Council areas. Environmental ISO 14001:2004 Reg No 4259
Quality Systems ISO 9001:2008 Reg No 4258
Revision No: 2 Effective Date: 19/02/2015 Next Review Date: 19/02/2018