                                                                                                                                                            RESIDENTIAL & LIGHT COMMERCIAL FOOTINGS - CONSTRUCTION NOTES                                                                      TIMBER NOTES:
   CLIENT DETAILS:                                                            MR ADAM LAW                                                                   1. All workmanship and materials shall be in accordance with the requirements of the relevant current Australian                  1. All timber design and construction shall be in accordance with AS1720 & AS1684 U.N.O.
                                                                                                                                                              Standard Codes (AS3600-2001 & AS2870-1996), Building By-Laws and the ordinances of the relevant Local Authority.                2. Softwood shall be min. Stress Grade F5 U.N.O. Hardwood shall be min. Stress Grade F14 U.N.O.
                                                                                                                                                            2. Concrete Footings and Slab (due to exposure)                                                                                   3. External timber shall be either hardwood - Durability Class I or II, or impregnated pine Grade 7,
   PROJECT DESCRIPTION: PROPOSED RENOVATIONS                                                                                                                    i) Concrete Class                  - Minimum 20 MPa at 28 days                                                                   pressure treated to AS1604 and re-dried prior to use. Supplementary treatment shall be applied to all
   PROJECT LOCATION:    91 UPPER HASTINGS STREET                                                                                                                        Slab on ground with
                                                                                                                                                                        damp-proof membrane
                                                                                                                                                                                                   - 20 nominal maximum aggregate size
                                                                                                                                                                                                   - 80 maximum slump +/-10mm
                                                                                                                                                                                                                                                                                                 cut surfaces. Details of preservative treatment shall be provided to the Engineer.
                                                                                                                                                                                                                                                                                              4. Timber Trusses shall supplied be pre-cambered an amount equal to the applied dead load deflection.
   LOCALITY             NOOSA HEADS                                                                                                                             ii) Concrete Class
                                                                                                                                                                        Footing non-aggressive
                                                                                                                                                                                                                - Minimum 25 MPa at 28 days
                                                                                                                                                                                                   - 20 nominal maximum aggregate size
                                                                                                                                                                                                                                                                                                 Thee (3) copies of the "shop" drawings are to be submitted to the Engineer for checking and for
                                                                                                                                                                                                                                                                                                 submission to the Local Gov. Authority. The design loads on roof, ceiling, truss node points and
  GENERAL                                                                                                                                                               soil                                                                                                                     amount of pre-camber provided are to be clearly showing on drawings.
                                                                                                                                                                                                   - 80 maximum slump +/-10mm                                                                 5. All bolts in timber construction shall be minimum M12 U.N.O and bolts, nuts and washers shall be
  1. These drawings shall be read in conjunction with all other Consultants Drawings and Specifications.                                                        iii) Concrete Class                             - Minimum 32 MPa at 28 days
  2. Before proceeding with the Works any discrepancies or anomolies in the Engineering Drawings or Project                                                                                                                                                                                      hot dip galvanised. Bolt holes drilled in timber shall be exact size for bolts. Washers under bolt head
                                                                                                                                                                        Footing-aggressive soil    - 20 nominal maximum aggregate size                                                           and nuts shall be at least 2.5 times bolt diameter.
     documentation identified by the Contractor/Builder shall queried directly with the Engineer for a decision.                                                        (1km - 50 km from coastline)
     NOTE: IF IN DOUBT ASK.                                                                                                                                                                        - 80 maximum slump +/-10mm                                                                 6. Timber dimensions on the finish width and thickness of timber to be:
  3. Setting out dimensions and sizes of Structural Members or Elements shall not be obtained by                                                               iv) Concrete Class                               - Minimum 40 MPa at 28 days                                                           a. Seasoned Softwood +5.0, -0 mm
     Scaling the Structural Drawings                                                                                                                                    Footing-aggressive soil    - 20 nominal maximum aggregate size                                                                b. Unseasoned Softwood >F7 +3.0, -3 mm, <F7 +2.0, -4.0 mm
  4. All setting out dimensions shown on the Engineering Drawings shall be checked by the Contractor                                                                    (Upto 1km from coastline)                                                                                                     c. Seasoned Hardwood +2.0, -0 mm
                                                                                                                                                                                                   - 80 maximum slump +/-10mm
     before construction works commences. Dimensions are in millimetres (mm), U.N.O.                                                                                                                                                                                                                  d. Unseasoned Hardwood +3.0, -3 mm
  5. During construction the structure shall be maintained in a stable condition. Construction loads                                                            v) Concrete Class                               - Minimum 32 MPa at 28 days for internal slabs
                                                                                                                                                                                                                - Minimum 40 MPa at 28 days for external slabs                                        (reference also Clause 1.6.2 in AS2082)
     must not exceed the capacity of the structure at the time of loading. If in doubt ask the Engineer.                                                                Suspended slab
                                                                                                                                                                                                                                                                                              7. All timber joints and notches shall be 100mm minimum away from loose knots, severe sloping grain
  6. All workmanship and materials shall be in accordance the requirements of the current                                                                                                          - 20 nominal maximum aggregate size
     editions including Amendments of the relevant SAA Codes of Practice, except as                                                                                                                                                                                                              gum veins or other minor defects.
                                                                                                                                                                                                   - 80 maximum slump +/-10mm
     varied by the Contract Documents and of the By-Laws of the Local Government Authority.                                                                 3. Concrete Slab (due to abrasion)                                                                                                8. All details not shown on the Engineering Drawings shall be in accordance with AS1684 - 1996
  7. Wind Loads for this Project have been determined in accordance with AS1170.1 - 2002                                                                        i) Footpaths & residential driveways              - Minimum 20 MPa at 28 days                                                    Residential Timber Framing Code and best practices.
  8. Permanent, imposed and other loads (Dead & Live) for this Project have been determined in                                                                 ii) Commercial/Industrial floors no vehicular traffic - Minimum 25 MPa at 28 days                                              9. Roof Trusses
     accordance with AS1170.2 - 2002.                                                                                                                                                                                                                                                            A design certificate is to be provided prior to truss manufacture and signed by Truss Engineer (RPEQ).
                                                                                                                                                               iii) Light pneumatic tyred traffic up to 3 t            - Minimum 25 MPa at 28 days                                               Once the trusses are installed the Truss Engineer shall provide a certificate indicating that the trusses
  9. A Site Classification for this Project was determined in accordance with AS2870 - 1996
                                                                                                                                                               iv) Other pneumatic tyred traffic over 3 t              - Minimum 32 MPa at 28 days                                               have been installed as required. The certificate shouls also indicate and cover all bracing and tie-down req'd.
    SITE CLASS                 FOUNDATIONS                                                                                        Surface Movement (Ys)
    CLASS - S      Slightly reactive clay sites, only slight ground movement from moisture changes.                                       0<ys<20
                                                                                                                                                               v) Non-pneumatic tyred traffic                          - Minimum 40 MPa at 28 days                                            STRUCTURAL STEELWORK
                                                                                                                                                            4. Minimum Cover                                           - 25 to upper face of internal slabs -0 +5mm                           1. All steelwork and materials shall be in accordance with AS4100 UNO.
    CLASS - M      Moderately reactive clay or silt sites which can experience moderate ground                                            20<ys<40
                   movement from moisture changes.                                                                                                             to Reinforcement                                        - 45 for external exposure                                             2. All welding to be in accordance with AS1554 except where varied by the Contract Documents, or project Drawings.
                   Highly reactive clay sites, which can experience high ground movement from                                                                                                                          - 30 to a membrane in contact with the ground                             All Welds shall be undertaken by a qualified and certified Welder in accordance with AS 1554.
    CLASS - P                                                                                                                             40<ys<60
                   moisture changes.                                                                                                                                                                                   - 40 to unprotected ground                                                All welding shall be 6mm continuous fillet welds U.N.O using E48XX Electrodes, Structural Purpose (S.P) welds.
                   Highly reactive clay sites, which can experience high ground movement from                                                               5. Minimum Laps and Splices for Reinforcement                                                                                        Butt welds shall be qualified, complete penetration full strength butt welds to AS 1554 Part 1.
    CLASS - H2                                                                                                                            60<ys<75                                                                                                                                            3. Unless noted otherwise, all Hot Roller steel sections shall be Grade 300 in accordance with AS 3678 & 3679.1.
                   moisture changes.                                                                                                                           (a) Slab Fabric                                        - 225 minimum overlap of transverse bars at all edges
    CLASS - E      Extremely reactive sites, which can experience extreme                                                                                      (b) Trench Mesh                                        - 500 splices in all footing beams                                         AS 1163 for RHS Sections - Grade 350 Minimum
                   ground movement from moisture changes.                                                                                 ys>75
                                                                                                                                                                                                                      - Laps at intersections as per the Design Drawings                         AS 1163 for CHS Sections - Grade 350 Minimum
    CLASS - A to P Filled sites.                                                                                                          Varies
                                                                                                                                                                 (c) Reinforcing Bars                                 - 500 splices in all footing beams                                      4. The Builder shall prepare fabrication drawings and shall submit three (3) copies of each drawing for
                   Sites which include soft soils, ie: soft clay or silt or loose sands; landslip, mine
    CLASS - P      subsidence; collapsing soils; soil subject to to erosion; reactive sites subject to                                                                                                                - Provide "L" bars at all beam intersections with 500 lap to each leg      approval. Fabrication shall not commence until Drawings have been submitted.
                   abnormal moisture conditions/sites which cannot be classified otherwise.                                                                 6. Fireplaces shall be supported on slab thickening extending 300 past the edges of the masonry, and                              5. All steelwork that will be exposed to view shall have weld splatter, flux, dags and burrs removed,
  EARTHWORKS NOTES:                                                                                                                                            reinforced with F72 mesh top and bottom. Slab thickening shall be 150 thick for single storey construction                        and all sealing and butt welds ground flush.
  Where any cut or filling is carried out on the site after the completion of the site investigation, the                                                      and 200 thick for two storey construction.                                                                                     6. The Builder shall provide all cleats and holes for fixing steel and timber to steel as required by the Drawings
  following recommendation shall be followed:-                                                                                                              Shrinkage Control                                                                                                                    whether or not shown.
  1. The areas allocated (marked) for clearing shall be stripped of all vegetation, roots & stumps removed to -300mm below                                  7. Reinforcing mesh may be reduced to F72 for slabs under 18m in length on "S" sites                                              7. Surface Treatment or Coatings
     natural surface level. Vegetation is to be stockpiled for mulching or removed from site.                                                               8. Where the floor slab is to be tiled, the following recommendations are made, in order to
  2. Vegetation clearing shall be undertaken in accordance with Local or State Government Laws/Regulations Planning                                             minimise the effect of shrinkage:-                                                                                                ELEMENT                      SURFACE PREPARATION TREATMENT OR COATING                                  FINISH
     Conditions, or Developer Specifications and requirements.                                                                                                   - F92 slab mesh (or equivalent) should be provided                                                                                                            (AS 1627 - PART)
  3. Prior to any topsoil/earthworks commencing; all erosion and sedimentation works are to be installed and completed, in                                  Construction Joints & Penetrations                                                                                                    ALL INTERNAL ELEMENTS Abrasive Blast, Hand Clean Alkyd Zinc Phosphate Primer-Type 1 See Architects Specs.
     accordance with project Erosion & Sedimentation Plan & Drawings, or in accordance with Local and State Gov't Reg's.                                    9. Constructions Joints or pour breaks where not shown on the Approved Plans or Details shall be located and formed to the
  4. Prior to any excavation works commencing the Contractor/Builder shall undertake a D.B.Y.D - Dial Before You Dig                                                                                                                                                                              EXCEPT GALV. PURLINS and Power Wire brush to     (AS 4089) Thickness 0.075mm
                                                                                                                                                                approval of the Engineer.
     and physically locate/mark all buried/above ground services so that they are visible, including any necessary terminations.                            10. No penetrations, recesses or chases other than those shown on the structural drawings shall be made in concrete                   (INTERNAL)            CLASS 1 AS1627
  5. Topsoil is to be removed (100 - 200mm depth) and placed in stockpiles, stockpile surface track rolled to seal, for later use.                              members without the approval of the Engineer.                                                                                     EXPOSED STEELWORK Abrasive Blast, Hand Clean Alkyd Zinc Phosphate Primer-Type 1 See Architects Specs.
  6. Any topsoil stripped surface (sub-grade) beneath a fill embankment or to be filled area is to be compacted using a                                     11. At penetrations in slabs unless otherwise detailed reinforcement must not be cut but shall be gathered equally                    (INTERNAL)            and Power Wire brush to    (AS 4089) Thickness 0.075mm
     12 Tonne (minimum) vibrating pad foot roller. Where the soil sub-surface profile is not at optimum moisture content the                                    to each side of the penetrations and extra reinforcement provided between the penetrations as directed by the Engineer.                                                            Two Coats Full Gloss (AS4025.1)
                                                                                                                                                                                                                                                                                                                        CLASS 1 AS1627
     area to be filled shall be shallow tyned by Grader, moisture conditioned, blade mixed and compacted (min 4 passes).                                    Reinforcement Placement                                                                                                                                                                Thickness 0.050mm each Coat
     The compacted sub-grade is to be proof rolled using a 20kLitre (full) water truck and witnessed by Geotechnical Engineer.                              12. Reinforcement is presented diagrammatically. It is not necessarily shown in true projection.
     Any soft areas which are areas that show displacement beneath truck tires are to be re-tyned and compacted, before                                     13. Provide the Engineer with 24 hours notice of reinforcement being ready for inspection.                                            EXPOSED STEELWORK            Chemical Degrease & Acid Hot Dipped Galvanized                            See Architects Specs.
     being re-proof rolled.                                                                                                                                     No concrete is to be poured without the approval of the Engineer.                                                                 (EXTERNAL)                   Descale                  Thickness - 350gms/m2
  7. Cut batters are to be maximum; 1 (vertical) : 2 (horizontal)-(1 : 2), U.N.O on the Drawings. Fill batters (compacted)                                  14. Splices in reinforcement shall be made only in the positions shown where lap length is not shown it shall be sufficient
                                                                                                                                                                to develop the full strength of the reinforcement.                                                                             8. Cold Formed Sections shall comply with AS/NZS 4600, AS1594 & AS1595.
     are to be maximum of 1 (vertical) : 4 (horizontal) (1 : 4) U.N.O on the Drawings.
                                                                                                                                                            15. Welding of reinforcement will only be permitted with the prior approval of the Engineer.                                       9. Minimum Steel Yield Stress - Purlins & Girts shall be 450 MPa.
  8. Cut or Fill batters shall be protected from surface erosion by rainfall or wind by Contractor as soon as practical achievable.
                                                                                                                                                            16. Reinforcement must not be continuous through construction joints.                                                             10. All Purlins & Girts Sections shall have a minimum Galvanized Steel Coating - 350gms/m2
     Batter protection methods/systems may be; hydromulching, wood-chip mulch/mulch, erosion protection matting, or other                                   17. Spacement of sufficient "stools" under main bottom reinforcement bar and top cross bar in slabs to allow adequate
     similar proprietary products, or 100mm topsoil spread with grass seed, or U.N.O on the Drawings.                                                                                                                                                                                         11. All Laps & Bridging shall be in accordance with the Manufacture's Instructions.
                                                                                                                                                                support in correct position during concreting (not greater than 900mm spacing's).
     FILL MATERIAL TYPES & QUALITY                                                                                                                          17. Supply and lay steel fabric in flat sheets at splices. Fabric shall be lapped as specified of in accordance with AS3600.      12.Unless Noted, all Welds shall be 6mm continuous Fillet (Noted CFW) Category GP using E41XX or E48XX Electrodes.
     General Fill - Silty sand clay (CL) with gravel, Plasticity Index (PI)>12 &<18, Testing in accordance with AS1289.3.3.1                                Reinforcement                                                                                                                     13.Unless Noted, all gusset plates shall be 10mm.
     Select Fill - Clayey silty sand with gravel (SC) to silty sand clay (CL) with gravel, Plasticity Index (PI)>7 &<12,                                                                                                                                                                      14.All Holding Down bolts shall be either commercial bolts or be made from mild steel bar Grade 250 MPa U.N.O.
                                                                                                                                                            19. Reinforcement Symbols:
     Testing in accordance with AS1289.3.3.1                                                                                                                                                                                                                                                  15.BOLT DESIGNATION - TYPICAL U.N.O
                                                                                                                                                                N Grade 500 MPa Deformed Bar
     Granular Fill (Road Base Pavements) - Silty sand gravel (GM) to clayey silty sandy gravel (GC), Plasticity Index (PI)<7                                                                                                                                                                                             Bolt Type                Comments
                                                                                                                                                                SL Grade 500 MPa Deformed Slab Mesh
     Testing in accordance with AS1289.3.3.1 & MRTS05 - 2015 Unbound Pavement Specification.                                                                    Y Grade 410 MPa Deformed Bar                                                                                                                             4.6/S                    Commercial Bolts Grade 4.6 to AS1111 - Snug Tightened
      Compaction of Fill Materials                                                                                                                              A Grade 250 MPa Deformed Bar - Pools Construction                                                                                                        8.8/S                    High Strength Structural Bolts Grade 8.8 to AS1252 - Snug Tightened
                                                                                                                                                                R Grade 250 MPa Plain Bar                                                                                                                                8.8/TB                   High Strength Structural Bolts Grade 8.8 to AS1252 - Fully Tensioned
      (a) Sand fill (Non-cohesive) up to 800 deep, placed in maximum 300 thick layers and compacted with a vibrating
                                                                                                                                                            Curing & Placement of Concrete                                                                                                                                                        to AS1511 & Bearing Joint.
          roller to achieve a minimum Dynamic Cone Penetrometer reading of 16 blows per 300 penetration
          (refer AS 1289.F3.3). Sand fill may be flooded if necessary to achieve this compaction standard,                                                                                                                                                                                                               8.8/TF                   High Strength Structural Bolts Grade 8.8 to AS1252 - Fully Tensioned
                                                                                                                                                            20. Slabs to be cured and kept moist for 7 days (min.)
          provided the water can subsequently be drained from the site.                                                                                     21. No concrete to be poured when site temperature exceeds 35° C or falls below 5° C.                                                                                                 to AS1511 as a Friction Joint with Facing Surface Left Uncoated
      (b) Cohesive fill (General & Select Fill) up to 400 deep, placed in max. 200mm thick layers and compacted using a 12T                                 Grouting                                                                                                                          16.Concrete encased steelwork shall be unpainted, free from all loose rust, loose mill scale, dirt, oil, grease, etc. and the
          Vibratory roller. Fill shall be moisture conditioned (+/- 2% of O.M.C) & compaction, testing according to AS1289-5.4.1                                                                                                                                                                 encasement concrete strength shall be minimum 25 MPa and cover of 165mm. Concrete Encasing shall be centrally
                                                                                                                                                            21. Grouting under base plates shall be the responsibility of the Steelwork Erection Contractor,
      (c) Controlled filling shall continue for at least 1 metre past the edge of the foundation/works and shall be battered back to                                                                                                                                                             reinforced with 5 mm wire to AS1303 or 6 mm Structural Grade Bars to AS1302 at 150mm pitch.
          the original surface with a slope of no less than 1:2 (Vert : Hor).                                                                                    Grouting thickness shall be nominally 40mm U.N.O
                                                                                                                                                                                                                                                                                              17.All Steelwork shall be secured using temporary bracing to stabilise the structure during erection.
      (d) Granular Fill placed in max. 200mm thick layers & compacted to 98% MMDD (STD Comp), according to AS1289-5.4.1.                                    22. Grout for base plates shall be minimum 50MPa compressive strength, and be a proprietary
      (e) Where the depth of filling material exceeds that specified above, the filling material shall be                                                        produce such as Fosroc, Conbextra HF or Embercon Masterflow, or equivalent and approved.
          compacted as follows:-                                                                                                                            23. Base plates shall be supported before grouting by galvanised steel packers covering not less
          Non-cohesive fill to 65% Density Index in accordance with AS1289.E6.1                                                                                  than 10% of the bearing area. Access for grouting must not be blocked by packers. The steel
          Cohesive fill to 97% Maximum Dry Density (MMDD) (Standard Compaction) in accordance with AS1289 - 5.4.1                                                                                                                                                                                                       Copyright: The drawing and engineering content shown in this drawing remains the property of Blackall
                                                                                                                                                                 erection Contractor shall provide all fasteners, site cleats, packers, shims, wedges and landing                                                       Range Consulting Engineer and may not be copied, altered, sections omitted or erased and changes
          Compaction tests shall be carried out on each layer as fill material is placed. If the compaction standard
                                                                                                                                                                 stools, and the like necessary for the efficient and safe erection of the steel works.                                                                 made without the prior written approval of Blackall Range Consulting Engineer. Acceptance of Blackall
          specified is not achieved, additional compaction is required. For foundations; a "Pier and Slab" and "Pier and Beam" footing
          design may be required where all piers are founded on the underlying natural material, or as applicable.                                                                                                                                                                                                      Range Consulting Engineer fee proposal or estimate is deemed sufficient to effectuate an agreement.
                                                                                                                                                                                                                                                                                                                        Non-payment of said fee proposal or estimate and subsequent use of Blackall Range Consulting
                                                                                                                                                                                                                                                                                                                        Engineer drawings or material is a breach of said agreement and subject to litigation. ABN 94950162458
Rev. No. Drawn Amendment Details
   A     Drawings -
                                                                                           Drawn
                                                                                           CJF
                                                                                                   Checked Date
                                                                                                   CJF     24/04
                                                                                                                   Site Classification:       P           BLACKALL RANGE CONSULTING ENGINEER                                                                     CLIENT:                                                 PROJECT DETAILS:                                                    Sheet No.               1 of 8
                                                                                                                                                            Consulting Civil, Structural and Geotechnical Engineer                         ABN 94950162458
                                                                                                                                                                                                                                                                                                                                                                                             Date Issued:     DEC 2019
                                                                                                                   Soil Classification:       CH                                                                                                                 MR ADAM LAW                                             PROPOSED RENOVATIONS
                                                                                                                                                                      Campbell J Foster                                                Po Box 342                                                                                                                                            CAD File:

Copyright: The design and engineering content shown on this drawing remains the property
                                                                                                                   Wind Category:             N3                  BEng(Civil), MIEAust. (609713), CPEng, RPEQ (7228)
                                                                                                                                                                                                                                       Mapleton, QLD, 4560
                                                                                                                                                                                                                                       (07) 5445 7354 (Office)
                                                                                                                                                                                                                                                                                                                         91 UPPER HASTINGS STREET                                            DRAWING NUMBER                  REV.
of Blackall Range Consulting Engineer and may not be copied, altered, sections omitted
or erased and changed in any way without the prior written approval from Blackall
Range Consulting Engineer. ABN 94950162458                                                                         Terrain Category:          2.5                    Signature
                                                                                                                                                                                                                                       (07) 5445 7332 (Fax)
                                                                                                                                                                                                                                       0419 140465 (Mobile)
                                                                                                                                                                                                                                                                                                                         NOOSA HEADS                                                         2019-1027-01                        3
Full text of pages 2 to 7 (of 8)

Page 2

                                                                                                                         New Concrete Pool (Ref: Drawing 08)                               DEB1

                                                                                                                                                                                                                                                                                                                           75x4.0 SHS Post P1                                                                                                    400 min.
                                                                                                                                                                                                                                                                                                                                                                                                           100 min.                                        SL82 Fabric                         100                                                                                      1200mm Min.
                                                                                                                                                                                                                                                                                                                                                                   SL                                                                                                                                               R12 Dowel Chemset                                                                                                         100
                                                                                                                                                                                                                                                                                                                                                                                                      1 on 20 fall                                                                                                  into Existing Footing                                               SL82 Fabric
                                                                                                                                                                                                                                                                                                                                                                                        FSL




                                                                                                                                                                                                                        DEB1




                                                                                                                                                                                                                                                                                                                                     1200 mm Max




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        250 Min.
                                                                                                                                                                                                                                                                                 Fill                                                              NSL




                                                                                                                                                                                    CONCRETE SLAB DECK
                                                                                                                                                                                                                                                                                                                                                                                                                                                                           Sand Fill                                                                                                                                                         125




                                                                                                                                                                                                                                                                                                                                                                            400 Min.
                                                                                                                                                                                                                                                                                                                                                                                                                                                        200 Micron Plastic




                                                                                                                                                                                                                                                                   300 mm Min.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          200 Micron Plastic
                                                                                                                                                                                                                                                                                                                                                                                                                                                        Membrane (DPM). Typ.                         Existing Footing Beam                                                                                                Membrane (DPM). Typ.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              R12 - 400mm Long Dowel




                                                                                                                                                                                                                                                                                                                                                                                                                       300
                                                                                                                                                                                                                                                                                                                                                                                                                                                       2 N12 Bar Top                                                                                                                                                    Controlled Fill (Ref: Notes)
                                                                                                                                                                                                                                                                                                                                                                                                                                                       R10 "Z" Bar at 400 C/C or                                                                                 450          Bar @ 400 C/C. Bar wrapped in
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Denso Tap or approved or Equiv.




                                                                                                                                                                                                                                                                                                                              150
                                                                                                                                                                                                                                                                                                                                                                                            R10 ligs at 400 C/C or                                     N12 "Z" Bar at 900 C/C.
                                                                                                                                                                                                                                                                                                                                                                                            N12 ligs at 600 C/C.                                       L11TM300
                                                                                                                                                                                                                                                            150 SQ x 8mm
                                                                                                                                                                                                                                                            Base plate                                         Ø350                                                                                                                 350                                                                                   TYP. DOWELLED EXTERNAL EDGE BEAM - TEB1




                                                                                                                                                                      DEB1
                                                                                                                                                                                                                                                                TYP. SHS POST FOOTING DETAIL - PF1                                                                                                        TYP. EXTERNAL EDGE BEAM - EB1                                                                                                                  Not to scale
                                ST1




                                                                                1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Not to scale




                                                                                                                                                                                                                        DEB1
                                                                                                                                                                                                                                                                                                          Not to scale                                                                                                         Not to scale                                                                                                                                         1000 mm max.
                                                                                            ST1                                                    ST1                                                                                                                                                                                                                                                                                                                                                                                                 SL82 Mesh Top            Internal load - bearing wall
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          100
                                                                                                                                                                                                                                                                                                                       100x100 H3 Post                                                                                                       140 SQR HWD H3 Post
                                                                     ST1




                                                                                                                                                                                                                                                                                                                         2/M12 bolts through                                                                                                   2/M12 bolts through
                                                                                                                                                                                                                                                                                      75mm Min
                                                                                                                                                                                                                                                                                                                         galv. Cast-in stirrup                                                                   75mm Min
                                                                                                                                                                                                                                                                                                                                                                                                                                               galv. Cast-in stirrup
                                                                                       DEB1                                                           DEB1                                                                                                                                                                                                                                                                                      Weathered top
                                                                                                                                                                                                                                                                                                                         Weathered top




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       400 Min.
                                          ST1                                                                                                                                                                  ST1/DEB1                                                                                                                                                                                                                                                                                                                      200 Micron Plastic                     2 N12 Bar Top         200 Micron Plastic
                                                                                                                                                                                                                                                                Ground to fall                                                                                                                      Ground to fall
                                                                                                                                                                                                               R12 Bar (Galv.) Dowels @ 400 Ctrs                away from piers                                                                                                                     away from piers                                                                                                                          Membrane (DPM). Typ.                                         Membrane (DPM). Typ.
                                                    DEB1




                                                                                1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       R10 "Z" Bar at 400 C/C or
                                                                                                                           IB1




                                                                                                                                                                                    DEB1
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        N12 "Z" Bar at 900 C/C.
                                                                                                                                                                                                                                                                      FILL                                                                                                                                FILL                                          FILL                                                                          R10 ligs at 400 C/C or                            If Slab not Cast with Footing
                                                                                                                                                                                                                                                                                                                                FILL                                                                                                                                                                                                  N12 ligs at 600 C/C.
                                                                                                                                                                                                                                                N12 Bar Looped                                                                                                                         N12 Bar Looped




                                                                                                                                                                                                                                                                                                                                                                                                                                                                      1200 mm Min.
                                                                                                                                                                                                                                                                                                                               NSL                                                                                                                     NSL




                                                                                                                                                                                                                                                                                                                                                     900 mm Min.
                                                                                                                                                                                                                                                over stirrup                                                                                                                           over stirrup
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        350        L11TM300
                                                                                                                                                                                                                                                                                                                                                                                                                                                 M12 Loop Bar
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       TYP. INTERNAL BEAM - IB1




                                                                                                                                                                                                                                                                                                                                                                                       300mm Min.
                                                                                                                                                                                                                                                   300mm Min.
                                                                    R12 Bar (Galv.) Dowels @ 400 Ctrs                    TEB1                                                                                                                                                                                              Concrete Pier                                                                                                          Concrete Pier                                                                                                     Not to scale
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             200 Min.              DEB1 Edge Beam and Slab                            Water Proof & Flexible
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      Exterior Epoxy Sealant
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  Conc. Steps
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   SL72 Fabric
                                                                                                                                                                                                                                                                                                         Ø350mm                                                                                                               Ø450mm

                                                                                     R12 Bar (Galv.) Dowels @ 400 Ctrs                                                                                                                         TYP. TIMBER POST FOOTING DETAIL - PF1                                                                                                    TYP. TIMBER POST FOOTING DETAIL - PF2
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Block
                                                                                                                                                                                                                                                    NOT SUPPORTING ROOF LOAD                                                                                                                   SUPPORTING ROOF LOAD
                                                                                                                                                                                                                                                                                                        Not to scale                                                                                                        Not to scale
                                                                            TEB1
                                                                                            TEB1
                                                                   TEB1




                                                                                                                                                                                                                                                                                                                                                                                                                                           400 min.                                                                                                                                                       DEB1 Edge beam &
                                                                                                                                                                                                                                                                                                                       Compacted Clayey Fill                                                                200 Min.                                          SL72 Fabric                       100                                                                 SECTION 1                             Stair Slab - N12 Tie Bars

                                                                                                                                                                                                                                                                                                                         SL                                                                                                                                                                                                                                         Not to scale
                                                                                                                                                                                                                                        N12 Bar @ 400 Ctrs Vertical
                                                                                                                                                                                                                                                                                                                                    300 Approx




                                                                                                                                                                                                                                                                                            <1200mm
                                                                                                                                  R12 Bar (Galv.) Dowels @ 400 Ctrs                                                                                                                                                                                                                                                                                                                                                                                                                "Z" Bar as per RWT1 Base Slab
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            N12 Bar @ 400 Ctrs
                                                                              IB1                                                                                                                                                                                                                                                                                       200 Seried Core Filled Block
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     50mm Comp. sand fill




                                                                                                                                                                                                                                                                                                                                                                                                                                           1200 Max.
                                                                                                                                                                                                                                                                                                                           Granular Material




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           400
                                                       EB1




                                                                                                                                                                                                                                                                                                                                                                          N12 Bar @ 400 Ctrs Vertical




                                                                                                                                                                                                                                                                                                                                                                                                                                             Varies
                                                                                                                                                                                                                                                                                                                                                                                                                                                           200 Micron Plastic                                                                                                                                              Depth as Per RTW1 Detail
                                                                                                                           TEB1




                                                                                                                                                                                                                                          200 Seried Core Filled Block                                                                                                                                                                                     Membrane (DPM). Typ.
                                                                                                                                                                                                                                                                                                                           Geotextile Material




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          400
                                                                                                                                                                                                                                           N12 Bar @ 400 Ctrs Horiz.                                                                                                                                      1 on 20 fall
                                                                                                                                                                                                                                                                                                                        Ø100mm AG Drainage Pipe                                                                                                                                 Controlled Fill Ref. Notes
                                                                                                                                                                                                                                                         1 on 20 fall                                                   Geotextile wrapped                                                          FSL
                                                                                           EB1                                                                                                                                                                                                                                                                                                                                                         Alt. Cast Concrete Deepened
                                                                   50mm Min Step                                            50mm Min Step                                                                                                             FSL                                                                                                                                                                                              Edge Beam rather than Block                                              N12 "L" Bar @ 400 Ctrs                    300            "Z" Bar as per RWT1 Base Slab
                                                                                                                                                                                                                                                                                                                                                                                                                                                       2 N12 Bar Top                                                                                TYP. RETAINING WALL/STRIP FOOTING STEP DETAIL
                                                                                                                                                                                                                                                                                 400 Min.




                                                                                                                                                                                                                                                                                                                                                                                                                      400
                                                                    100mm STRIP DRAIN - S/STEEL                           PF1                                                                                                                                                                                          2 N12 Bar Top                                                                                                                   R10 "Z" Bar at 400 C/C or                                                                                         Not to scale
                                  ST1




                                                                                                                                                                        PIT                                                                                                                                                                                                                R10 ligs at 400 C/C or                                      N12 "Z" Bar at 900 C/C.
                                                                                                                                                                                                                                                                                                                       R10 "Z" Bar at 400 C/C or                                           N12 ligs at 600 C/C.                                        3 N12 Bar or
                                                                                                                                                                                                                                         R10 ligs at 400 C/C or
                                                                                                                                                                                                                                         N12 ligs at 600 C/C.                                                          N12 "Z" Bar at 900 C/C.                                                                                                         L11TM300                                                     NOTE:
                                                                                                                           PF2                         PF2                                                                                                                                                                                                                                                                                                                                                          The information provided on these drawings has been derived solely from the
                                                                                                                                                                                                                                                                                                         350         L11TM300                                                                                                      350
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Architectural Drawings provided to Blackall Range Consulting Engineer (The Engineer).
                                                                                                                                    ST1                        DEB1                                                                            TYP. WALL STRIP FOOTING - ST1 DETAIL                                                                                                                        DEEPENED EDGE BEAM - DEB1                                                                                No allowance has been made, other than the site soil conditions shown on the Drawings.
                                               ST1                                                                                                                                                                                                                                                                                                                                                                            Not to scale
                                                                                                                                                                                                         ST1




                                                                                                                                                                                                                                                                                                      Not to scale
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Where site soil conditions, at the building site differs from that shown on the Structural
                                                                                                                                                                                                                                                                                                                                                                                           PF1 - Ø350mm BORED PIER - 100 SHS POST P1                                                                                drawings the Builder shall contact The Engineer for clarification prior to work continuing.
                                                                                                                                                                                                                                                                                                                                                                                           FOOTING MIN. 900MM DEEP U.N.O
                                                                                                                                                                 1% Fall                                                                                                                                                                                                                                                                                                                                            Where discrepancies or anomalies between architectural and structural drawings and
                                                                                                                                                                                                                                                                                                                FOUNDATION PLAN                                                            PF1 - Ø450mm BORED PIER - 140 HWD POST P2                                                                                averse site conditions are found such as; member sizes, span and connections, post
                                                                                                                                                                                                                                                                                                                                                                                           FOOTING MIN. 1200MM DEEP U.N.O
                                                                                                                          ST1




                                                                                                                                                                                                                                                                                                                                N.T.S                                                                                                                                                                               footing and foundation, post size, fill areas, tree roots and stumps within foundation
                                                                                                                                                                                                                                                                                                                                                                SLAB MESH                                                                                                                                           areas, rock or rock floaters, backfilled trenches within the foundation area, layers of
                                                                                                                                                                                                                  SITE CLASS              TYPE OF                                                     FOOTING DEPTH      FOOTING    MAX. FOOTING                                                                                                                                                                    unconsolidated soil material below the level where Site Investigation boreholes
                                                                                                                                                                                                                                        CONSTRUCTION                                                    (D) mm (Min) REINFORCEMENT SPACING C/C (m) SLAB LENGTH SLAB LENGTH SLAB LENGTH                                                                                                                              termination has not been allowed for. It is the responsibility of the builder to contact The
                                                                                                                                                                                                                                                                                                                                                   >18m        >18m & <25m >25m & <30m
                                                                                                                                                                                                                  CLASS - P                                                                                                                                                                                                                                                                                         Engineer where any of the above arise, such that the design can be verified and
                                                                                                                                                                                                                                      POST FOOTING                                                        1200 min.                                L11TM300                 5000                                      SL72                         SL82                               SL92                          amended where required.
                                                                                                                                                                                                                  (Assumed)



                                                                                                                                                                                                                                                                                                                                                    REINFORCED CONCRETE DRIVEWAY
                                                                                                                                                                                                                                                                                                                                                    100mm THK - SL72 MESH TOP.

                                                                                                                                                                                                                                                                                                                                                    REINFORCED CONCRETE SLAB ON                                                                                                                                                Copyright: The drawing and engineering content shown in this drawing remains the property of Blackall
                                                                                                                                                                                                                                                                                                                                                    GROUND - 100mm THK - SL82 MESH TOP.                                                                                                                                        Range Consulting Engineer and may not be copied, altered, sections omitted or erased and changes
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               made without the prior written approval of Blackall Range Consulting Engineer. Acceptance of Blackall
                                                                                                                                                                                                                                                                                                                                                    REINFORCED CONCRETE STAIR SLAB ON                                                                                                                                          Range Consulting Engineer fee proposal or estimate is deemed sufficient to effectuate an agreement.
                                                                                                                                                                                                                                                                                                                                                    FILL - 100mm THK - SL82 MESH TOP.                                                                                                                                          Non-payment of said fee proposal or estimate and subsequent use of Blackall Range Consulting
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               Engineer drawings or material is a breach of said agreement and subject to litigation. ABN 94950162458
Rev. No. Drawn Amendment Details
   A     Drawings -
                                                                                                   Drawn
                                                                                                   CJF
                                                                                                           Checked Date
                                                                                                           CJF     24/04
                                                                                                                                       Site Classification:                   P                                 BLACKALL RANGE CONSULTING  ENGINEER
                                                                                                                                                                                                                                      LANDSCAPED AREA                                                                                                                                                                       CLIENT:                                                                                            PROJECT DETAILS:                                                                                   Sheet No.                  2 of 8
                                                                                                                                                                                                                           Consulting Civil, Structural and Geotechnical Engineer                                                                                           ABN 94950162458
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  Date Issued:         DEC 2019
                                                                                                                                       Soil Classification:                   CH                                                                                                                                                                                                                                            MR ADAM LAW                                                                                        PROPOSED RENOVATIONS
                                                                                                                                                                                                                                          Campbell J Foster                                                                                                             Po Box 342                                                                                                                                                                                                                                                CAD File:

Copyright: The design and engineering content shown on this drawing remains the property
                                                                                                                                       Wind Category:                         N3                                                    BEng(Civil), MIEAust. (609713), CPEng, RPEQ (7228)
                                                                                                                                                                                                                                                                                                                                                                        Mapleton, QLD, 4560
                                                                                                                                                                                                                                                                                                                                                                        (07) 5445 7354 (Office)
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               91 UPPER HASTINGS STREET                                                                           DRAWING NUMBER                  REV.
of Blackall Range Consulting Engineer and may not be copied, altered, sections omitted
or erased and changed in any way without the prior written approval from Blackall
Range Consulting Engineer. ABN 94950162458                                                                                             Terrain Category:                      2.5                                                       Signature
                                                                                                                                                                                                                                                                                                                                                                        (07) 5445 7332 (Fax)
                                                                                                                                                                                                                                                                                                                                                                        0419 140465 (Mobile)
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               NOOSA HEADS                                                                                         2019-1027-02                   3

Page 3

                                                                       Step          200                                                              Step    200                                                                                                            < 50


                                                                                                                                            D                                                                                                                                                                                                                                                1/N12
                                                  D                                                                                                                                                                                                                                         100                                                                                              Corner
                                                                                                                                                                                         1.5D                                                                                      Slab mesh                                                                                                 lap bar
                                                                                                          SLOPE 1 in 10                                                                                                                            TYPICAL SLAB RECESS DETAIL
                                                                           ALTERNATIVE STEP DETAIL A                                                         ALTERNATIVE STEP DETAIL B                                                    (SUITABLE FOR RECESSES LESS THAN 50mm DEEP)                                               External Edge Beam
                                                                                                Not to Scale                                                                 Not to Scale                                                                                     Not to Scale
                                                                                                                                                                    100                                                                                                          Slab mesh                                      OUTSIDE CORNER LAP BAR DETAIL
                                                                                      Step 200                                                                                                                                                                                                                                                         Not to Scale

                                                                                                                                                                                                                   50 to 200                                                                                                                                          Slab mesh

                                                                                                                                                                                                                                                                                                                                      350
                                                                D                                                                                                                                                                                                                                                                     MAX.

                                                                                                                     1.5D                                                              400                                                                             400
                                                                                                                                                                                                                                      125                                                                            100                                500
                                                                                                                                                                                                                                 2 Layers slab mesh
                                                          ALTERNATIVE STEP DETAIL C TYPICAL FOORTING BEAM STEP                  TYPICAL SLAB RECESS DETAIL                                                                                                                                                                   TYPICAL SLAB STEP DETAIL
                                                       (STEPS LESS THAN 200 mm)                         (SUITABLE FOR RECESSES GREATER THAN 50 mm BUT LESS THAN 200 mm DEEP)                                                                                                                                         (SUITABLE FOR STEP LESS THAN 350 mm DEEP)
                                                   Not to Scale                                40 cover                   300                                                                                                  Not to Scale                                                                                                 Not to Scale
                                                                                                                          Lap
                                                                                                                                                                                                                                                                                                                                              Construction joint
                                                                                                                                                                                                                                          3 N12 bars or extend                                                                                 3 N12 bars top
                                                    Footing step :                                                                                                                                                                        B2 mesh to far side                                                                                  where internal beam top steel
                                                                       3-N12 Z Bars                                                                                                D                                                      of external footing beam mesh                                                                        is provided
                                                    MAX. height -
                                                    2xD                each face                                                                                                                    '1'                                                          '1'                                                                               Slab mesh
                                                    Trench mesh or reinforcing
                                                    bars as specified                                                                                                                                                                                                                                  1 : 20 fall
                                                                                                                                                                                                                                                                                                                                              Internal Footing Beam
                                                                                                                                                                                                                                                Internal footing beam
                                                                                                                                                                                                                               External Footing Beam                                                                                                        1
                                                   D                                                                                                    Trench mesh or reinforcing                                                                                                           External Footing beam                                                        Trench mesh (refer
                                                                                                                                                        bars as specified                                                                                                                                                                              5                  internal footing beam)
                                                                                                                                                                                                                                                                                                                                   100
                                                                                                                                                                                                                                                                                                                                   max.         3 N12 bars Bottom
                                                                                                                                                                                            TYPICAL FOOTING BEAM INTERSECTION DETAIL                                                                    40 Cover
                                                                                                                                                                                                                                Not to Scale                                                                                                500 LAP
                                                                                                                  1.5 x D - 450 min
                                                                                                                                                                                                                                                                                                                                SECTION 1 - 1
                                                                                TYPICAL FOOTING BEAM STEP (STEP GREATER THAN 200 mm)                                                                                                    Trench/bottom mesh (refer
                                                                                                                                                                                                                                                                                       Corner Bars shall be provided                 Not to Scale                     Trench/Bottom mesh (refer
                                                                                                                                                                                                                                        edge beam detail)
                                                                                                                       Not to Scale                                                                                                                                                    at all corners as per corner                                                   edge beam detail)
                                                                                                  2D (eg. 1200)                                    Trench mesh (refer                                                                                                                  bar lap detail.
                                                                                                                                                   edge beam detail)


                                                                      D                                                                                                                                               Corner Bars shall be provided
                                                                                                                                                                                                                      at all corners as per corner
                                                          (eg. 600)
                                                                                                                                                                                                                      bar lap detail.
                                                                                                                                   Corner Bars shall be provided
                                                                                                                                   at all corners as per corner                                                                                                                                                                                                                                          Extra "N12" Min. bar in
                                                                                                                                   bar lap detail.                                                                                                                                                                                                                         500 Min Lap                   widened penetration rib.
                                                                                                                                                                                                                                                                                                       TYPICAL BAY WINDOW DETAIL
                                                                                                   TYPICAL OFFSET FOOTING DETAIL                                                                          TYPICAL EDGE REBATE DETAIL                                                                                         Not to scale                                                                                                     Rib
                                                                                                                     Not to scale                                                                                              Not to scale
                                                                                                               Provide Polystyrene Lagging                                                                 Provide Polystyrene Lagging
                                                                                                               around pipe of thickness to                                                                 around pipe of thickness to
                                                                                                                                                             1.5 x Pipe Dia. (100mm Min.)
                                                                                           D                   Local Authority Requirements                                                                Local Authority Requirements

                                                                                                                                                                                                                                                                                                       100mm Clear                                                                                         Pipe
                                                                                                                                                      D




                                                                                                                                                                                                                                                    D




                                                                                                                                                                                                                                                                                                                                                            TYP. PIPE PENETRATION THROUGH RIBS
                                                                                                                                                                                                                                                                                                                                                                                          Not to scale
                                                                                                                                                                                                                                                                                                                50mm Clear
                                                                                                                                                                                                                                                                                                                                             Copyright: The drawing and engineering content shown in this drawing remains the property of Blackall
                                                                                       2xD                             2xD                                                          2xD                             2xD                                                             300                            300                       Range Consulting Engineer and may not be copied, altered, sections omitted or erased and changes
                                                 TYP. PIPE PENETRATION - TOP OF FOOTING                                                                   TYP. PIPE PENETRATION - BOTTOM OF FOOTING                                                             TYP. UNDER FOOTING                                                           made without the prior written approval of Blackall Range Consulting Engineer. Acceptance of Blackall
                                                                                                                                                                                                                                                                                                                                             Range Consulting Engineer fee proposal or estimate is deemed sufficient to effectuate an agreement.
                                                                                               Not to scale                                                                            Not to scale                                                                                 Not to scale                                             Non-payment of said fee proposal or estimate and subsequent use of Blackall Range Consulting
                                                                                                                                                                                                                                                                                                                                             Engineer drawings or material is a breach of said agreement and subject to litigation. ABN 94950162458
Rev. No. Drawn Amendment Details
   A     Drawings -
                                                                                               Drawn
                                                                                               CJF
                                                                                                       Checked Date
                                                                                                       CJF     24/04
                                                                                                                            Site Classification:      P             BLACKALL RANGE CONSULTING ENGINEER                                                                              CLIENT:                                                   PROJECT DETAILS:                                                    Sheet No.                3 of 8
                                                                                                                                                                            Consulting Civil, Structural and Geotechnical Engineer                          ABN 94950162458
                                                                                                                                                                                                                                                                                                                                                                                                                  Date Issued:     DEC 2019
                                                                                                                            Soil Classification:      CH                                                                                                                            MR ADAM LAW                                               PROPOSED RENOVATIONS
                                                                                                                                                                                         Campbell J Foster                                              Po Box 342                                                                                                                                                CAD File:

Copyright: The design and engineering content shown on this drawing remains the property
                                                                                                                            Wind Category:            N3                           BEng(Civil), MIEAust. (609713), CPEng, RPEQ (7228)
                                                                                                                                                                                                                                                        Mapleton, QLD, 4560
                                                                                                                                                                                                                                                        (07) 5445 7354 (Office)
                                                                                                                                                                                                                                                                                                                                              91 UPPER HASTINGS STREET                                            DRAWING NUMBER                    REV.
of Blackall Range Consulting Engineer and may not be copied, altered, sections omitted
or erased and changed in any way without the prior written approval from Blackall
Range Consulting Engineer. ABN 94950162458                                                                                  Terrain Category:         2.5                               Signature
                                                                                                                                                                                                                                                        (07) 5445 7332 (Fax)
                                                                                                                                                                                                                                                        0419 140465 (Mobile)
                                                                                                                                                                                                                                                                                                                                              NOOSA HEADS                                                         2019-1027-03                        3

Page 4

                                                                                                                                                                                                                                                                                                                                                                           Existing Timber Beam                 PB1 Beam
                                                                                                                                                                                                                                                                 14 Guage 14 x 32mm Hex-head                                                      2 Bolt dia. min
                                                                                                                                                                                                                     M12 Chemical Anchors PL1                    Screws, Min. 6 per Side, or
                                                                                                                                                                                                                                                                                                                                                  5 Bolt dia. min
                                                                                                                                                                                                                     Galv.@ 900 Ctrs Max.                        2 M12 Galv. Gr8.8 Bolts                      M12 Bolts                                                                                       M16 Gr8.8 Bolts
                                                                                                                                                                                                                                                                                                          Galvanised or S/S                                                                                   @900 Ctrs & either
                                                                                                                                                                                                                                                                                                                                                  4 Bolt dia. min                                             side of beam joint
                                                                                                                                                                                                                                                                                                            P2 HWD Post
                                                                                                                                                                                                                                                                                                                                             PB1 Beam
                                                                                                                                                                                                                                                                      Rafter
                                                                                                                                                                                                                                                                                                          TIMBER POST P2 to PB1 CONNECTION
                                                                                                                                                                                                                                                                                                                               Not to Scale
                                                                                                                                                                                                                                                              4mm (Min.) Thick "L" Bracket                                                                                                                   Timber Beam Securely
                                                                                                                                                                                                                                                              100mm Wide x 200mm High                                                                                                                          Bolted to SHS Posts
                                                                                                                                                                                                                                                              Both sides of VB1/2
                                                                                                                                                                                                                                                                                                                                                                                      TYP. PLATE DETAIL 1
                                                                                                                                                                                                                                         TYP. RAFTER TO PL1 CONNECTION                                                                                                                        Not to Scale
                                                                                                                                                                                                                                                               Not to Scale


                                                                                                                                                                                                                                                                                                                    Rafter/Joist

                                                                                                                                                                                                                                                                                                             Framing Anchor                  Timber Beam/Bearer


                                                                                                                                                                                                                                                              Lintel L3
                                                                                                                                                                                                                                                                                                                              TYP. DETAIL
                                                                                                                                                                                                                             150mm long, 6mm
                                                                                                                                                                                                                                                                                                                                    N.T.S
                                                                                                                                                                                                                             Fabricated Angle
                                                                                                                                                                                                                                                                      2 Bolt dia. min
                                                                                                                                                                                                                                    M12 Bolts                         5 Bolt dia. min
                                                                                                                                                                                                                                                                                                                                             140 SQR HWD H3 Post
                                                                                                                                                                                                                                                                      4 Bolt dia. min                                                         2/M12 bolts through
                                                                                           REF: DETAIL                                                                                                                                                                                                                                        galv. Cast-in stirrup
                                                                                                                                                                190 Core Filled Block                                                   P1 Post
                                                                                                                                                                                                                                                                                                                          75
                                                                                                                 L4                                                                                                                                                                                                                          M12 Chem-set Bolts
                                                                                                                                                                                                                                                                                                                                             Min. 125mm Embedment
                                                                                                                                                               L1/L5
                                                                                                                                                                                         L1
                                                                                                                                                                                                                             TYP. P1 POST/BEAM CONNECTION DETAIL
                                                                                                                                                                                                                                                                                                                                                   190 Core Filled Block
                                                                                                                                                                                                                                                      N.T.S




                                                                                                                                                       REF: DETAIL                       L1
                                                                                                                                                                 L2
                                                                                                                                                                                                                                M12 Cyclone Rod                   PFC or Timber
                                                                                                                                                                                                                                                                  Lami-Beam



                                                                                                                                                                                                                                                                                                          TYP. P2 POST-BLOCK CONNECTION DETAIL
                                                                                                                                                                                                                                                                                                                                   N.T.S
                                                                                                                                                                                                                                                                    M12 Rod Chemset
                                                                                                                                                                                         L1                                                                         into Block - 125mm Min                             FLOOR MEMBER SIZES
                                                                                                                                                                                                                                                                     Core filled Block                                 MEMBER               SIZE              ALT. SIZE           GRADE            SPAN
                                                                                                                                                    L1/L5                                                                        LINTEL & BLOCK CONNECTION                                                                DJ1         150x50 F14            140x35 MGP12               H3             Single Span
                                                                                                                                                                                                                                                    N.T.S                                                                 DB1         200x50 F14            190x45 MGP12               H3             Cont. - 2 Spans
                                                                                                                                                                                                                                                                                                                          PL1         150x50 F14            140x35 MGP12               H3             Single Span
                                                                                                                                                                                                                           BRACING SCHEDULE WIND DIRECTION "A" - (Wind Load = 3.6kN)
                                                                                                                                                                                                                            BRACING TYPE            BRACING UNITS BRACING QTY            TOTAL BRACING
                                                                                                                                                                                                                                                                                                                        LINTEL MEMBER SIZES
                                                                                                                                                                                                                                                       (kN/m)         (m)                  FORCE (kN)
                                                                                                                                      REF: DETAIL                                                                                                                                                                     MEMBER               SIZE             ALT. SIZE         GRADE MEMBER SPAN
                                                                                                              Ref: Deatil 1                                                                                                 PLYWOOD - 4.5mm             6.4kN/m               6.0        46.0x6.4=38.4
                                                                               L3 - Plate Existing Beam                                                                                                                     Steel SHS Posts             4.0kN/Each             0                 0                       L1        100x6mm "L"                   -             G300          Galvi-lintel
                                                                                                                                                                                                                            190 Core Filled Block       12kN/m                 >1             >12.0                                220x35 KD F17 200x58 LVL 15                  T2
                                                                                                                                P1        PL1                        PL1                                                                                                                                                 L2                                                                  Single
                                                                                                                                                                                                                                                                                               >3.6 kN
                                                                            Existing Post                                                                                                                                  NOTE:
                                                                                                                                                                                                                                                                                                                         L3           200PFC              280x65 GL18C          T2           Single
                                                                                                                                                                                                                           * The bracing capacity values used applies to a 2.7 m high wall
                                                                                                                                      Pergola Rafters RF1@600 Ctrs                                                         BRACING SCHEDULE WIND DIRECTION "B" - (Wind Load = 3.6kN)                                     L4        395x65 GL17C 390x65 GL18C                    T2           Single
                                                                                                                                                                                                                            BRACING TYPE            BRACING UNITS BRACING QTY            TOTAL BRACING
                                                                                                                                                                                                                                                                                                                         L5           100PFC              75x50x5 RHS           G300         Single
                                                                                                                                 P2       PB1           P2           PB1 P2
                                                                                                                                                                                                                                                       (kN/m)         (m)                  FORCE (kN)
                                                                                                                                                                                                                            PLYWOOD - 4.5mm             6.4kN/m               4.5      4.5x6.4=28.8                      RF1       140x35 KD F27 140x35 KD F17                  H2           Single
                                                                                                                                                                                                                            Steel SHS Posts            4.0kN/Each              0               0                         PB1       240x45 KD F27 240x45 KD F17                  H2           Single
                                                                                                                                                                                                                            190 Core Filled Block      12kN/m                  >1           >12.0
                                                                                                                                                              REF: DETAIL                                                  NOTE:                                                             >3.6 kN                     P1        75x4.0mm SHS 90x3.2mm SHS G300/450                        Single
                                                                                                                                                                                                                           * The bracing capacity values used applies to a 2.7 m high wall
                                                                                                                                                                                                             A                                                                                                           P2         140 SQR F27 125 SQR F27    H3                            Single
                                                                                                                                                                                                                                             BRACING LEGEND
                                                                                                                                                                                                                                             INDICATES M12 TIE DOWN @ 1200 CTS FASTENED TO FOUNDATIONS OR LOWER STORY BEARERS.
                                                                                                                                                                                                                                             INDICATES M16 TIE DOWN THAT IS FASTENED TO FOUNDATIONS OR LOWER STORY BEARERS.

                                                                                                                                                                                                                   B             0.9m
                                                                                                                                                                                                                                             INDICATES M16 BOLT
                                                                                                                                                                                                                                             INDICATES 900mm LENGTH
                                                                                                                                                                                                     WIND DIRECTION                          TO ONE SIDE OF STUD WALL, STUDS TO BE AT 600mm CENTERS MAXIMUM. VERTICALLY INSTALLED SHEETING TO BE
                                                                                                                                                                                                                                             NAILED TO TIMBER FRAME WITH 30mm x Ø2.8-3.15mm
                                                                                                                                                                                                                                             AROUND ALL EDGES AND BUTT JOINTS AND AT 300mm CENTERS ALONG INTERMEDIATE STUDS. PROVIDE M12

                                                                                                                                            GROUND FLOOR LEVEL TIMBER FRAMING,                                                               CYCLONE ROD WITHIN 50mm OF EACH END OF THE BRACING WALL CONTINUOUS FROM TOP PLATE TO SLAB/FLOOR
                                                                                                                                                                                                                                             FRAMING AND M12 BOLTS FROM BOTTOM PLATE TO SLAB/FLOOR FRAMING AT 1200mm CENTERS MAXIMUM IN BETWEEN
                                                                                                                                                                                                                                                                                                                                                                                   Copyright: The drawing and engineering content shown in this drawing remains the property of Blackall
                                                                                                                                                                                                                                                                                                                                                                                   Range Consulting Engineer and may not be copied, altered, sections omitted or erased and changes
                                                                                                                                                                                                                                                                                                                                                                                   made without the prior written approval of Blackall Range Consulting Engineer. Acceptance of Blackall
                                                                                                                                              LINTEL, BRACING & TIE-DOWN PLAN                                                                Note: All external walls are Load Bearing Walls (LBW) U.N.O                                                                           Range Consulting Engineer fee proposal or estimate is deemed sufficient to effectuate an agreement.
                                                                                                                                                                                                                                                                                                                                                                                   Non-payment of said fee proposal or estimate and subsequent use of Blackall Range Consulting
                                                                                                                                                                                 N.T.S
                                                                                                                                                                                                                                                                                                                                                                                   Engineer drawings or material is a breach of said agreement and subject to litigation. ABN 94950162458
Rev. No. Drawn Amendment Details
   A     Drawings -
                                                                                              Drawn
                                                                                              CJF
                                                                                                         Checked Date
                                                                                                         CJF     24/04
                                                                                                                              Site Classification:          P                BLACKALL RANGE CONSULTING ENGINEER                                                                                          CLIENT:                                                                     PROJECT DETAILS:                                                   Sheet No.                4 of 8
                                                                                                                                                                                         Consulting Civil, Structural and Geotechnical Engineer                                 ABN 94950162458
                                                                                                                                                                                                                                                                                                                                                                                                                                                        Date Issued:     DEC 2019
                                                                                                                              Soil Classification:          CH                                                                                                                                           MR ADAM LAW                                                                 PROPOSED RENOVATIONS
                                                                                                                                                                                                  Campbell J Foster                                                        Po Box 342                                                                                                                                                                   CAD File:

Copyright: The design and engineering content shown on this drawing remains the property
                                                                                                                              Wind Category:                N3                                BEng(Civil), MIEAust. (609713), CPEng, RPEQ (7228)
                                                                                                                                                                                                                                                                           Mapleton, QLD, 4560
                                                                                                                                                                                                                                                                           (07) 5445 7354 (Office)
                                                                                                                                                                                                                                                                                                                                                                                     91 UPPER HASTINGS STREET                                           DRAWING NUMBER                  REV.
of Blackall Range Consulting Engineer and may not be copied, altered, sections omitted
or erased and changed in any way without the prior written approval from Blackall
Range Consulting Engineer. ABN 94950162458                                                                                    Terrain Category:             2.5                                  Signature
                                                                                                                                                                                                                                                                           (07) 5445 7332 (Fax)
                                                                                                                                                                                                                                                                           0419 140465 (Mobile)
                                                                                                                                                                                                                                                                                                                                                                                     NOOSA HEADS                                                        2019-1027-04                        3

Page 5

                                                                                                                                                                                                                                                                                                                                                                                 Existing Timber Beam                 PB1 Beam
                                                                                                                                                                                                                                                                       14 Guage 14 x 32mm Hex-head                                                      2 Bolt dia. min
                                                                                                                                                                                                                           M12 Chemical Anchors PL1                    Screws, Min. 6 per Side, or
                                                                                                                                                                                                                                                                                                                                                        5 Bolt dia. min
                                                                                                                                                                                                                           Galv.@ 900 Ctrs Max.                        2 M12 Galv. Gr8.8 Bolts                      M12 Bolts                                                                                       M16 Gr8.8 Bolts
                                                                                                                                                                                                                                                                                                                Galvanised or S/S                                                                                   @900 Ctrs & either
                                                                                                                                                                                                                                                                                                                                                        4 Bolt dia. min                                             side of beam joint
                                                                                                                                                                                                                                                                                                                  P2 HWD Post
                                                                                                                                                                                                                                                                                                                                                   PB1 Beam
                                                                                                                                                                                                                                                                            Rafter
                                                                                                                                                                                                                                                                                                               TIMBER POST P2 to PB1 CONNECTION
                                                                                                                                                                                                                                                                                                                                     Not to Scale
                                                                                                                                                                                                                                                                    4mm (Min.) Thick "L" Bracket                                                                                                                   Timber Beam Securely
                                                                                                                                                                                                                                                                    100mm Wide x 200mm High                                                                                                                          Bolted to SHS Posts
                                                                                                                                                                                                                                                                    Both sides of VB1/2
                                                                                                                                                                                                                                                                                                                                                                                            TYP. PLATE DETAIL 1
                                                                                                                                                                                                                                               TYP. RAFTER TO PL1 CONNECTION                                                                                                                        Not to Scale
                                                                                                                                                                                                                                                                     Not to Scale


                                                                                                                                                                                                                                                                                                                          Rafter/Joist

                                                                                                                                                                                                                                                                                                                   Framing Anchor                  Timber Beam/Bearer


                                                                                                                                                                                                                                                                    Lintel L3
                                                                                                                                                                                                                                                                                                                                 TYP. DETAIL
                                                                                                                                                                                                                                   150mm long, 6mm                                                                                        N.T.S
                                                                                                                                                                                                                                   Fabricated Angle
                                                                                                                                                                                                                                                                            2 Bolt dia. min
                                                                                                                                                                                                                                          M12 Bolts                         5 Bolt dia. min
                                                                                                                                                                                                                                                                                                                                                   140 SQR HWD H3 Post
                                                                                                                                                                                                                                                                            4 Bolt dia. min                                                         2/M12 bolts through
                                                                                                REF: DETAIL                                                                                                                                                                                                                                         galv. Cast-in stirrup
                                                                                                                                                                     190 Core Filled Block                                                    P1 Post
                                                                                                                                                                                                                                                                                                                                75
                                                                                                                     L4                                                                                                                                                                                                                            M12 Chem-set Bolts
                                                                                                                                                                                                                                                                                                                                                   Min. 125mm Embedment
                                                                                                                                                                  L1/L5
                                                                                                                                                                                              L1
                                                                                                                                                                                                                                   TYP. P1 POST/BEAM CONNECTION DETAIL
                                                                                                                                                                                                                                                                                                                                                         190 Core Filled Block
                                                                                                                                                                                                                                                            N.T.S




                                                                                                                                                          REF: DETAIL                         L1
                                                                                                                                                                      L2
                                                                                                                                                                                                                                      M12 Cyclone Rod                   PFC or Timber
                                                                                                                                                                                                                                                                        Lami-Beam



                                                                                                                                                                                                                                                                                                                TYP. P2 POST-BLOCK CONNECTION DETAIL
                                                                                                                                                                                                                                                                                                                                         N.T.S
                                                                                                                                                                                                                                                                          M12 Rod Chemset
                                                                                                                                                                                              L1                                                                          into Block - 125mm Min                             FLOOR MEMBER SIZES
                                                                                                                                                                                                                                                                           Core filled Block                                 MEMBER               SIZE              ALT. SIZE           GRADE            SPAN
                                                                                                                                                       L1/L5                                                                           LINTEL & BLOCK CONNECTION                                                                DJ1         150x50 F14            140x35 MGP12               H3             Single Span
                                                                                                                                                                                                                                                          N.T.S                                                                 DB1         200x50 F14            190x45 MGP12               H3             Cont. - 2 Spans
                                                                                                                                                                                                                                                                                                                                PL1         150x50 F14            140x35 MGP12               H3             Single Span
                                                                                                                                                                                                                                 BRACING SCHEDULE WIND DIRECTION "A" - (Wind Load = 3.6kN)
                                                                                                                                                                                                                                  BRACING TYPE            BRACING UNITS BRACING QTY            TOTAL BRACING
                                                                                                                                                                                                                                                                                                                              LINTEL MEMBER SIZES
                                                                                                                                                                                                                                                             (kN/m)         (m)                  FORCE (kN)
                                                                                                                                         REF: DETAIL                                                                                                                                                                        MEMBER               SIZE             ALT. SIZE         GRADE MEMBER SPAN
                                                                                                                  Ref: Deatil 1                                                                                                   PLYWOOD - 4.5mm             6.4kN/m               6.0        46.0x6.4=38.4
                                                                                       L3 - Plate Existing Beam                                                                                                                   Steel SHS Posts             4.0kN/Each             0                 0                       L1        100x6mm "L"                   -             G300          Galvi-lintel
                                                                                                                                                                                                                                  190 Core Filled Block       12kN/m                 >1             >12.0                                220x35 KD F17 200x58 LVL 15                  T2
                                                                                                                                   P1        PL1                        PL1                                                                                                                                                    L2                                                                  Single
                                                                                                                                                                                                                                                                                                     >3.6 kN
                                                                                    Existing Post                                                                                                                                NOTE:
                                                                                                                                                                                                                                                                                                                               L3           200PFC              280x65 GL18C          T2           Single
                                                                                                                                                                                                                                 * The bracing capacity values used applies to a 2.7 m high wall
                                                                                                                                         Pergola Rafters RF1@600 Ctrs                                                            BRACING SCHEDULE WIND DIRECTION "B" - (Wind Load = 3.6kN)                                     L4        395x65 GL17C 390x65 GL18C                    T2           Single
                                                                                                                                                                                                                                  BRACING TYPE            BRACING UNITS BRACING QTY            TOTAL BRACING
                                                                                                                                                                                                                                                                                                                               L5           100PFC              75x50x5 RHS           G300         Single
                                                                                                                                    P2       PB1           P2           PB1 P2
                                                                                                                                                                                                                                                             (kN/m)         (m)                  FORCE (kN)
                                                                                                                                                                                                                                  PLYWOOD - 4.5mm             6.4kN/m               4.5      4.5x6.4=28.8                      RF1       140x35 KD F27 140x35 KD F17                  H2           Single
                                                                                                                                                                                                                                  Steel SHS Posts            4.0kN/Each              0               0                         PB1       240x45 KD F27 240x45 KD F17                  H2           Single
                                                                                                                                                                                                                                  190 Core Filled Block      12kN/m                  >1           >12.0
                                                                                                                                                                 REF: DETAIL                                                     NOTE:                                                             >3.6 kN                     P1        75x4.0mm SHS 90x3.2mm SHS G300/450                        Single
                                                                                                                                                                                                                                 * The bracing capacity values used applies to a 2.7 m high wall
                                                                                                                                                                                                                  A                                                                                                            P2         140 SQR F27 125 SQR F27    H3                            Single
                                                                                                                                                                                                                                                   BRACING LEGEND
                                                                                                                                                                                                                                                   INDICATES M12 TIE DOWN @ 1200 CTS FASTENED TO FOUNDATIONS OR LOWER STORY BEARERS.
                                                                                                                                                                                                                                                   INDICATES M16 TIE DOWN THAT IS FASTENED TO FOUNDATIONS OR LOWER STORY BEARERS.

                                                                                                                                                                                                                         B             0.9m
                                                                                                                                                                                                                                                   INDICATES M16 BOLT
                                                                                                                                                                                                                                                   INDICATES 900mm LENGTH
                                                                                                                                                                                                            WIND DIRECTION                         TO ONE SIDE OF STUD WALL, STUDS TO BE AT 600mm CENTERS MAXIMUM. VERTICALLY INSTALLED SHEETING TO BE
                                                                                                                                                                                                                                                   NAILED TO TIMBER FRAME WITH 30mm x Ø2.8-3.15mm
                                                                                                                                                                                                                                                   AROUND ALL EDGES AND BUTT JOINTS AND AT 300mm CENTERS ALONG INTERMEDIATE STUDS. PROVIDE M12

                                                                                                                                                GROUND FLOOR LEVEL TIMBER FRAMING,                                                                 CYCLONE ROD WITHIN 50mm OF EACH END OF THE BRACING WALL CONTINUOUS FROM TOP PLATE TO SLAB/FLOOR
                                                                                                                                                                                                                                                   FRAMING AND M12 BOLTS FROM BOTTOM PLATE TO SLAB/FLOOR FRAMING AT 1200mm CENTERS MAXIMUM IN BETWEEN


                                                                                                                                                  LINTEL, BRACING & TIE-DOWN PLAN                                                                  Note: All external walls are Load Bearing Walls (LBW) U.N.O                                                                               Copyright: The drawing and engineering content shown in this drawing remains the property of Blackall
                                                                                                                                                                                                                                                                                                                                                                                             Range Consulting Engineer and may not be copied, altered, sections omitted or erased and changes
                                                                                                                                                                                      N.T.S                                                                                                                                                                                                  made without the prior written approval of Blackall Range Consulting Engineer. Acceptance of Blackall
                                                                                                                                                                                                                                                                                                                                                                                             Range Consulting Engineer fee proposal or estimate is deemed sufficient to effectuate an agreement.
                                                                                                                                                                                                                                                                                                                                                                                             Non-payment of said fee proposal or estimate and subsequent use of Blackall Range Consulting
                                                                                                                                                                                                                                                                                                                                                                                             Engineer drawings or material is a breach of said agreement and subject to litigation. ABN 94950162458
Rev. No. Drawn Amendment Details
   A     Drawings -
                                                                                               Drawn
                                                                                               CJF
                                                                                                        Checked Date
                                                                                                        CJF     24/04
                                                                                                                              Site Classification:             P               BLACKALL RANGE CONSULTING ENGINEER                                                                                              CLIENT:                                                                       PROJECT DETAILS:                                                     Sheet No.                5 of 8
                                                                                               CJF      CJF     1/02                                                                         Consulting Civil, Structural and Geotechnical Engineer                                     ABN 94950162458
                                                                                                                                                                                                                                                                                                                                                                                                                                                                  Date Issued:     DEC 2019
                                                                                                                              Soil Classification:             CH                                                                                                                                              MR ADAM LAW                                                                   PROPOSED RENOVATIONS
                                                                                                                                                                                                       Campbell J Foster                                                            Po Box 342                                                                                                                                                                    CAD File:

Copyright: The design and engineering content shown on this drawing remains the property
                                                                                                                              Wind Category:                   N3                                  BEng(Civil), MIEAust. (609713), CPEng, RPEQ (7228)
                                                                                                                                                                                                                                                                                    Mapleton, QLD, 4560
                                                                                                                                                                                                                                                                                    (07) 5445 7354 (Office)
                                                                                                                                                                                                                                                                                                                                                                                             91 UPPER HASTINGS STREET                                             DRAWING NUMBER                  REV.
of Blackall Range Consulting Engineer and may not be copied, altered, sections omitted
or erased and changed in any way without the prior written approval from Blackall
Range Consulting Engineer. ABN 94950162458                                                                                    Terrain Category:                2.5                                    Signature
                                                                                                                                                                                                                                                                                    (07) 5445 7332 (Fax)
                                                                                                                                                                                                                                                                                    0419 140465 (Mobile)
                                                                                                                                                                                                                                                                                                                                                                                             NOOSA HEADS                                                            2019-1027-05                      3

Page 6

                                                                                                                                                  N32 CONCRETE SL72
                                                                                                                                                  MESH, 50 TOP COVER                     N12 TRIMMERS BARS




                                                                                                                                                              100 125




                                                                                                                                                                                                                            200
                                                                                                                                                100mm COMPACTED BASE
                                                                                                                                                COURSE GRAVEL UNDER SLAB                           450         150
                                                                                                                                                (IF ORDERED).
                                                                                                                                                                           DRIVEWAY SLAB EDGE TREATMENT
                                                                                                                                                                                              NOT TO SCALE




                                                                                                                                                                                                                                                             Copyright: The drawing and engineering content shown in this drawing remains the property of Blackall

                                                                                                                                                                                TYPICAL DRIVEWAY DETAIL                                                      Range Consulting Engineer and may not be copied, altered, sections omitted or erased and changes
                                                                                                                                                                                                                                                             made without the prior written approval of Blackall Range Consulting Engineer. Acceptance of Blackall
                                                                                                                                                                                                                                                             Range Consulting Engineer fee proposal or estimate is deemed sufficient to effectuate an agreement.
                                                                                                                                                                                                                                                             Non-payment of said fee proposal or estimate and subsequent use of Blackall Range Consulting
                                                                                                                                                                                                                                                             Engineer drawings or material is a breach of said agreement and subject to litigation. ABN 94950162458

Rev. No. Drawn Amendment Details
   A     Drawings - 1076-06
                                                                                           Drawn
                                                                                           CJF
                                                                                                   Checked Date
                                                                                                   CJF     24/04
                                                                                                                   Site Classification:   P     BLACKALL RANGE CONSULTING ENGINEER                                                             CLIENT:       PROJECT DETAILS:                                                     Sheet No.                6 of 8
                                                                                                                                                     Consulting Civil, Structural and Geotechnical Engineer              ABN 94950162458
                                                                                                                                                                                                                                                                                                                                  Date Issued:     DEC 2019
                                                                                                                   Soil Classification:   CH                                                                                                   MR ADAM LAW   PROPOSED RENOVATIONS
                                                                                                                                                              Campbell J Foster                                      Po Box 342                                                                                                   CAD File:

Copyright: The design and engineering content shown on this drawing remains the property
                                                                                                                   Wind Category:         N3              BEng(Civil), MIEAust. (609713), CPEng, RPEQ (7228)
                                                                                                                                                                                                                     Mapleton, QLD, 4560
                                                                                                                                                                                                                     (07) 5445 7354 (Office)
                                                                                                                                                                                                                                                             91 UPPER HASTINGS STREET                                             DRAWING NUMBER                  REV.
of Blackall Range Consulting Engineer and may not be copied, altered, sections omitted
or erased and changed in any way without the prior written approval from Blackall
Range Consulting Engineer. ABN 94950162458                                                                         Terrain Category:      2.5                Signature
                                                                                                                                                                                                                     (07) 5445 7332 (Fax)
                                                                                                                                                                                                                     0419 140465 (Mobile)
                                                                                                                                                                                                                                                             NOOSA HEADS                                                            2019-1027-06                      3

Page 7

                                                                                                                                                                          2.0 x 1.0m x 1.0m
                                                                                                                                                                          Deep Rubble Pit
                                                                                                                                                                          Geotextile Wrapped




                                                                                                                                                                                                                                                                                                                                                                  100mm WIDE S/STEEL
                                                               POOL DESIGN REF: DRAWING 08                                                                                                                                                                                                                                       SEE NOTE 2
                                                                                                                                                                                                                                                                                                                                                                  STRIP DRAIN

                                                                                                                                                                                                                                                                                                                                                                  40 Min.
                                                                                                                                                                                                                                                                                                               CONCRETE ENCASEMENT
                                                                                                                                                                                                                                                                                                                                                                        EXPANSION JOINT TO ENGINEER'S
                                                                                                                                                                                                                                                                                                               (SEE NOTE 1)
                                                                                                                                                                                                                                                                                                                                                    100                 DETAIL (SEE NOTE 3)
                                                                                                                                                                                                                                                                                             100 Driveway Slab

                                                                                                                                                                                                                                                                                                                                                                                                                          Existing Garage Slab
                                                                                                                                                                                                                                                                                                                                                                                                                                                             20x15 THIOFLEX 600 TWO PART
                                                                                                                                                                                                                                                                                                                                                                                                                                                             POLYSULPHIDEJOINT SEALANT BY




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  0.20 T
                                                                                                                                                                                                                                                                                                                                                                                                                                                             PARCHEM OR APPROVED EQUIVALENT, IN
                                                                                                                                                                                                                                                                                                                                                                                                                                                             ACCORDANCE WITH MANUFACTURERS                                                             SILICON SEALANT
                                                                                                                                                                                                                                                                                                                                                                                          BEDDING LAYER
                                                                                                                                                                                                                                                                                                                                                                                                                                                             RECOMMENDATIONS
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           3mm WIDE FILL




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          REINFORCEMENT
                                                                                                                                                                                                                                                                                            100                                                                                                                                                                                                                                                                         TOC
                                                                                                                                                                                                                                                                                                                                                                                        SOIL
                                                                                                                                                                                                                                                                                    DRIVEWAY SLAB & ENCASEMENT
                                                                                                                                                                                                                                                                                    POURED TOGETHER

                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             T = 125
                                                                                                                                                                                                                                                                                                                                           100                100
                                                                                                                                                                                                                                                                                              NOTES:
                                                                                                                                                                                                                                                                                              1. Specific site conditions may require an increase in concrete encasement dimensions and/or
                                                                                                                                                                                                                                                                                              reinforcement. It is the customer's responsibility to ensure the concrete encasement is designed for
                                                                                                                                                                                                                                                                                              the application. A minimum concrete strength of 25MPa is recommended. The concrete should be
                                                                                                                                                                                                                                                                                              vibrated to eliminate air pockets. Engineering advice may be required.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        SHRINKAGE                          CUT EVERY
                                                                                                                                                                                                                                                                                              2. The finished level of the concrete encasement must be approximately 3mm above the top of the
                                                                                                                                                                                                                                                                                              channel edge.                                                                                                                                                                                                             CRACK               DPM            SECOND BAR
                                                                                                                                                                                                                                                                                              3. Expansion and crack control joints are recommended to protect the channel and the concrete
                                                                                                                                                                                                                                                                                              encasement. Engineering advice may be required.                                                                                                                                                                       JOINT TO BE MASONRY SAW CUT WITHIN 8 HOURS OF CONCRETE SETTING
                                                                                                                                                                                                                                                                                              4. For further details, refer to ACO's design & site installation files at
                                                                                                                                                                                                                                                                                              www.acodrain.com.au/resources

                                                                                                                                                                                                                                                                                                                            STRIP DRAIN SECTION DETAIL                                                                                                                                                              CONSTRUCTION JOINT - TYPE KJ
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                NOT TO SCALE
                                                                                                                                                                                                                                                                                                                                           NOT TO SCALE
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               Grated Pit Cover




                                                                                                                                                                                                                       Ø90mm uPVC Storm water Pipe (Min. 1 in 60 grade)
                                                                                                                                                                                                                                                                                                                            <30                                      <30
                                                                                                                                                                                                                                                                                                                                                 300

                                                                                                                                                                                                                                                                                                                                      25                   25
                                                                                                                                                                                                                                                                                             SIDE PLATES
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       NSL




                                                                                                                                                                                                                                                                                                                                                                                                  <30
                                                                                                                                                                                                                                                                                                                                                                                                                                                 SQ Everhard Polymer Pit
                                                                                                                                                                                                                                                                                                                                                                                                                                                 Size as Spec. on Drawings




                                                                                                                                                                                                                                                                                                                                                                                  25
                                                                                                                                                                                                                                                                                                                                                                                                                                                      Pit Boss Pipe/Pit Adapter
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    Compacted Granular Material




                                                                                                                                                                                                                                                                                                                                                                                                300
                                                                                                                                                                                                                                                                                                                                                                                  25
                                                                                                                                                                                                                                                                                                                                                                                                                                         Ø90mm uPVC S/W Pipe
                                                                                                                                                                                                                                                                                                                                                                                                                                         or as Specifiec on Drawings




                                                                                                                                                                                                                                                                                                                                                                                                 <30
                                                                                                                                                                                                                                                                                                                                                                                                                                                   50mm Bedding Sand

                                                                                                                                                                                                                                                                                                        Steel Grate 300 SQR (Galv.)                    SQUARE GRATE TO SUIT PIT
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     TYP. GRATED POLYMER PIT SECTION
                                                                                                                                                                                                                                                                                                                                                       HOT DIP GALVANISED.                                                                                                                                             NOT TO SCALE
                                                                                                                                                                                                                                                                                                                                    5O*6 BARS
                                                                                                                                                                                                                                                                                                                                    AT 5O CRS




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Property Boundary
                                                                                                   7                                                                                                                                                                                                                           300 SQR GRATED PIT PLAN DETAIL.
                                                                                                                                                 300 SQR Grated Pit
                                                                                                                                                                                                                                                                                                                                                  NOT TO SCALE
                                                                100mm STRIP DRAIN - S/STEEL
                                                                                                  6                                                                                                                                                                                      EASTERN DRIVEWAY LEVELS




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             Garage
                                                                                                                                                                                                                                                                                                                                                                            Road Level
                                                                                                                                                                                                                                                                                                                                                                                                             A R M




                                                                                                                                                                                                                                                                                                                                                                                                                O
                                                                                                                                                                                                                                                                                                                                                                                                         F
                                                                                                                                                                                                                                                                                                                                                                                                        AL



                                                                                                                                                                                                                                                                                                                                                                                                                    EO
                                                                                                                                                                                                                                                                                                                                                                                                                                                                          O




                                                                                                                                                                                                                                                                                                                                                                                                                                                                     AR
                                                                                                                                                                                                                                                                                                                                                                                                                                                                   LF


                                                                                                                                                                                                                                                                                                                                                                                                                                                                          M
                                                                                                                                                                                                                                                                                                                                                                                                                                                                           EO
                                                                                                                                                                                                                                                                                                                                                                                                                                                                 A
                                                                                                                                                                                                                                                                                           NO.      CHAINAGE           DIST (m)        LEVEL          SLOPE
                                                                                             KJ                                                                           4                                    I.O                                                                         1          0.00              0.00           54.56          0
                                                                                                   5                                                                                                                                                                                        2         1.50              1.50           54.485        -1 in 20               M1 Kerb Profile
                                                                                                                   Ø90mm uPVC Storm water Pipe




                                                                                                                                                                                 Ø90mm uPVC Storm water Pipe




                                                                                                                                                                                                                                                                                            3         3.225             1.725          54.225        -1 in 6.25                                                                                                                                                                                                              F
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 A RO




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        ME
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         L
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         A




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          O
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                A RO




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       ME
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       Garage Floor 52.80




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            F
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          AL



                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         O
                                                                                                                                                                                                                                                                                            4         8.725             5.50           54.23          Level
                                                                         CONCRETE DRIVEWAY




                                                                                                                                                                                                                                                                                          WESTERN DRIVEWAY LEVELS
                                                                                                                                                                                                                                                                                           NO.      CHAINAGE           DIST (m)        LEVEL           SLOPE                                                                         1 in 28              1 in 6                            1 in 4                              1 in 4                                 1 in 8                              1 in 19
                                                                                                                                                                                                                                                                                           1          0.00              0.00           54.76
                                                                                                                                                                                                                                                                                            2         1.00              1.00           54.73         -1 in 28
                                                                                                                                                                                                                                                                                            3         2.50              1.50           54.48         -1 in 6




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Ch - 10.07


                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             Ch - 10.60
                                                                                                                                                                                                                                                                                                                                                                                                                         Ch - 0.00


                                                                                                                                                                                                                                                                                                                                                                                                                                          Ch - 1.00



                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Ch - 2.50


                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Ch - 3.53




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           Ch - 9.07
                                                                                                                                                                                                                                                                                            4         3.50              1.00           54.23         -1 in 4
                                                                                                                                                                                                                                                                                            5         8.57              5.07           52.93         -1 in 4
                                                                                                  KJ                                                             KJ                                                                                                                         6         10.07             1.00           52.747        -1 in 8
                                                                                                       4                                                              3                                                                                                                     7         10.60             1.03           52.80         +1 in 19                                                                                                                                        WESTERN DRIVEWAY LONG SECTION
                                                                 100mm STRIP DRAIN - S/STEEL                                                         100mm STRIP DRAIN - S/STEEL

                                                                                                       3
                                                                                                                                                                                                                DRAIN AGE PLAN
                                                                                                                                                                                                                                                                          N.T.S

                                                                                                                                                                      2
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           Copyright: The drawing and engineering content shown in this drawing remains the property of Blackall
                                                                                                   2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       Range Consulting Engineer and may not be copied, altered, sections omitted or erased and changes
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           made without the prior written approval of Blackall Range Consulting Engineer. Acceptance of Blackall
                                                                                                                                                                      1                                                                                                                                                                                                                                                                                                                                                                                                                                                    Range Consulting Engineer fee proposal or estimate is deemed sufficient to effectuate an agreement.
                                                                                                  1                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        Non-payment of said fee proposal or estimate and subsequent use of Blackall Range Consulting
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           Engineer drawings or material is a breach of said agreement and subject to litigation. ABN 94950162458
Rev. No. Drawn Amendment Details
   A     Drawings - 1076-08
                                                                                                           Drawn
                                                                                                           CJF
                                                                                                                     Checked Date
                                                                                                                     CJF     15/09
                                                                                                                                                   Site Classification:                                              M                                                            BLACKALL RANGE CONSULTING ENGINEER                                                                                                                                            CLIENT:                                                                                                                                                    PROJECT DETAILS:                                                     Sheet No.               7 of 8
                                                                                                                                                                                                                                                                                    Consulting Civil, Structural and Geotechnical Engineer                                                            ABN 94950162458
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                Date Issued:     DEC 2019
                                                                                                                                                   Soil Classification:                                              CH                                                                                                                                                                                                                                         MR ADAM LAW                                                                                                                                                PROPOSED RENOVATIONS
                                                                                                                                                                                                                                                                                                  Campbell J Foster                                                                            Po Box 342                                                                                                                                                                                                                                                                                       CAD File:

Copyright: The design and engineering content shown on this drawing remains the property
                                                                                                                                                   Wind Category:                                                    N3                                                                    BEng(Civil), MIEAust. (609713), CPEng, RPEQ (7228)
                                                                                                                                                                                                                                                                                                                                                                                               Mapleton, QLD, 4560
                                                                                                                                                                                                                                                                                                                                                                                               (07) 5445 7354 (Office)
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           91 UPPER HASTINGS STREET                                             DRAWING NUMBER                      REV.
of Blackall Range Consulting Engineer and may not be copied, altered, sections omitted
or erased and changed in any way without the prior written approval from Blackall
Range Consulting Engineer. ABN 94950162458                                                                                                         Terrain Category:                                                 2.5                                                                       Signature
                                                                                                                                                                                                                                                                                                                                                                                               (07) 5445 7332 (Fax)
                                                                                                                                                                                                                                                                                                                                                                                               0419 140465 (Mobile)
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           NOOSA HEADS                                                            2019-1027-07                      3

The text continues on page 8.

Used in these records

About this file

File size
1.3 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

BA190515 - 91 Upper Hastings Street Noosa Heads - 2019-1027 - 91 Upper Hastings Street - Rev 3.pdf · 1.3 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.