Bushfire Hazard Assessment & Management Plan v2 - 30 Pottery St Pomona 2021

of 62

Page text read automatically using OCR, there may be inaccuracies

Bushfire Hazard Assessment & Management Plan v2                                 NCES REF: J000864
Lot 496 on MCH591 – 30 Pottery St, Pomona




3.3 Quantitative Modelling
Quantitative modelling of the potential bushfire conditions that may be experienced within the
VHC 9.1 Eucalypt forest to be retained within the west of the site, and present to the south-
west and north-west of the site has been undertaken to assist in determining the suitability of
the development and any asset setback requirements.
The models used comprise industry standard bushfire equations which have been built into
the FPAA endorsed FLAMESOL computer model. FLAMESOL allows numerous input
variables to be adjusted including fuel loads, fire danger index, site slope and distance to
vegetation. FLAMESOL uses the following algorithms:
    •    Rate of Spread – McArthur (1973) and Nobel et al. (1980)
    •    Flame Length – NSW Rural Fire Service (2001) and Nobel et al. (1980)
    •    Elevation of Receiver – Douglas and Tan (2005)
    •    Flame Angle – Douglas and Tan (2005)
    •    Radian Heat Flux – Drysdale (1999), Sullivan et al. (2003) and Douglas and Tan (2005)
The FLAMESOL Minimum Distance calculator has been used and comprises an AS
3959:2018 Method 2 (Appendix B) based calculator which will determine standard bushfire
behaviour variables as well as the minimum distances required to achieve a range of different
radiant heat levels (represented by BAL's).
Fuel load inputs have been drawn from Planning for Bushfire Resilient Communities (QFES
2019) based on the calculated potential fuel loads for VHC 9.1 (21 t/ha surface and near
surface fuels and 24.2 t/ha total fuels). 1º effective slope was adopted for the slope underlying
the VHC 9.1 Eucalypt Forest given across slope to upslope conditions to the west. 6.5º
effective slope was adopted for the slope underlying the VHC 9.1 Eucalypt Forest to the north-
west, and 8.3º effective slope was adopted for the slope underlying the VHC 9.1 Eucalypt
Forest to the south-west.
A Forest Fire Danger Index (FFDI) of 47 has been adopted for the site consistent with the
assignment by QFES (Catalyst 2020) (refer Plate 8).




                                                                                     SITE




                                   Plate 8 – FFDI (Source: QFES redi Map)

The Flamesol output results are shown in Plate 9 - 11.




© 2021                                               15

Log in to download the original (Bushfire Hazard Assessment & Management Plan v2 - 30 Pottery St Pomona 2021.pdf)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.