PERFORMANCE OUTCOMES                           ACCEPTABLE OUTCOMES                                        PROPOSED SOLUTION

Impact on Ecologically Important Areas

PO2                                            No acceptable outcome provided                             No vegetation clearing or other ecological impacts are
Bushfire mitigation measures do not                                                                       required to facilitate the bushfire mitigation measures
adversely impact on:                                                                                      detailed in this report.
a) biodiversity values, connectivity and
ecosystem functioning; and
b) the long term physical integrity of
waterways, wetland and areas of native
vegetation.

Water Supply for Fire Fighting Purposes

PO3                                            AO3.1                                                      The development complies with AO3.2.
Development provides an adequate               Premises are connected to the reticulated water supply.
                                                                                                          The site will not be connected to a reticulated water
water supply for firefighting purpose
                                                                                                          supply. A permanent dam with volume far in excess of
which is reliable, safely located and freely   Editor's note—For reconfiguring a lot, water supply
                                                                                                          5,000 litres is located approximately 60m to the east of
accessible.                                    needs to provide for a minimum flow and pressure of
                                                                                                          the proposed Lot 2 building envelope. The existing
                                               10 litres a second at 200kPa at all times for firefighting
                                                                                                          formed access track traverses immediately adjacent to
                                               purposes.
                                                                                                          the dam and a concrete culvert crossing provides a solid
                                                                                                          access point for water extraction for fire-fighting
                                               OR
                                                                                                          purposes.
                                               AO3.2
                                               Where there is no available reticulated water supply,
                                               the premises has:

                                               a) an accessible dam, swimming pool or water tank
                                               available for firefighting purposes with an onsite water
                                               volume of not less than 5,000 litres; and


        DECEMBER 2021                                 BUSHFIRE HAZARD ASSESSMENT & MANAGEMENT PLAN                                               Page: 24
                                                                21 JIRRIMA CRESCENT, COOROIBAH
Log in to download the original file

Appendix D - Bushfire Hazard Assessment and Management Plan .pdf · 5.5 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.