Plans and drawings

This document appears to be plans or drawings. Its page text below holds only the words printed on the drawings, without the drawings themselves, so it may be jumbled or hard to follow. To see the plans as drawn, choose Original above or download the file (both need you to log in).

Log in to see the plans as drawn
   - NOOSA COUNCIL
   APPROVED PLAN
OPW20/0051 23 SEP 2020


[OCR of page images]
 

 

 

 

 

 

    

SHEET 4 SHEET 3

 

 

 

 

 

 

   
    

KEN

Coro)

  

00 i

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

203 ASINZS 3000:2018 STREET LIGHTING CERTIFICATE LEGEND
3.11.5 Spacing from other underground services
ROAD AND PUBLIC SPACE LIGHTING IS CERTIFIED SYMBOK DESCRIPTION
‘All underground wiring systems shall be spacing not ass than 100 mm from ‘TOCOMPLY WITH THE NOMINATED CATEGORIES OF
other underground services, [ASINZS 1188.1.12005 AND ASINZS 1188.3.1 2005, ® STATIONNUMEER
NEW STREET 1-PRS PROPOSED OH CONDUCTOR
Wiring systems shall be suitably marked with waming tape in accordance NeW STREET 1 PRS @ Propose
with Clause 3.11.4.5 and maintain a separation from telecommunications UAE MACDONALD BRIVE.-V4 $ Re MER
gas and water services in accordance with Table 3.7 3 eR
“THE DESIGN AGSUMES MAINTENANCE FACTORS OF HY AIR BREAK OPEN
Further requirements forthe separation of telecommunications, gas and 0.7 FOR MINOR ROAD LIGHTING, 0.75 FOR MAJOR xc
ate ayers rors low’ vetoge witng evista are peeved Rr ROAD LIGHTING, 0,75 FOR LED LIGHTING, BASED ON x Ly Isc LINK OPEN
seme ‘THE FOLLOWING SCHEDULE x LV DISC LINK CLOSED
TABLE 3.7 4. LAMPS ARE TO BE REPLACED AT 36 MONTH > NON
: ” INTERVALS, AT WHICH TIME LUMINAIRES ARE TO Ld LV POLE TERMINATION
MINIMUM SEPARATION OF UNDERGROUND SERVICES BE INSPECTED, CLEANED AND MAINTAINED. - GROUND STAY
2, VEGETATION IS TO BE KEPT CLEAR OF STREET EXISTING UG CABLE
Minimum separation tolow —] Minimum separation lions. PROPOSED UG CABLE
age electrical service of conductive 2. INSPECTION PATROLS AND SPOT LAMP 7 EXISTING SUPPLY PILLAR
laentited In secordance wih | enclosures totow REPLACEMENT SHALL MAINTAIN SERVICE PROPOSED SUPPLY PILLAR
Typeotservice | causes14,sand mechanically | —‘voRage electrical AVAILABILITY AT NOT LESS THAN 95%, a tine PILLAR "
protected) carting electrode (1) 4, LUMINAIRES AND LAMPS SHALL BE REPLACED
“es we va Ger countess © PADMOUNTED TRANSFORMER
° EXISTING CABLE IN CONDUIT
Wier savant ® PROPOSED CABLE IN CONDUIT
100 500
restr than DNSS @) + MEN (EARTH GROUND STAKE)
‘Water service greater Gg ELECTRICAL CABLE MARKER
than ON6S @2) 300 00 RESIDENTIAL AND = ‘CUSTOMER SWITCHBOARD
“Sanitary drainage 100) 500 COMMERCIAL / INDUSTRIAL o PIT
Stormer dabepe 00 00 ‘SUBDIVISIONS 0 STOSTREETLIGHT
ocr azsrreetuoHr
cee 100 500 ONLY ENERGEX APPROVED MATERIALS, 3 TREE
Tanwar 00 INSTALLATION EQUIPMENT. AND 3
INSTALLATION TECHNIQUES SHAUL BE =
USED DURING CONSTRUCTION. of Ly swTc# Fuse UNIT

11 Authors, such as watar and as supplirs and elect distributors, may
require their series to be spaced ata gr
systems, Alzo soo Figur 3.10.

2 DN= intemal diameter of pipe

 

* distance from underground wring

 

 

 

 

 

 

 

 

 

 

 

PLAN REGISTER
DWGNe, __OWGTITLE
‘ACDOS'-001. COVER SHEET & SURVEY PLAN
‘ACO6S'.002. ELECTRICAL DESIGN PLAN 1 OF 6
‘ACOGS'-002 ELECTRICAL DESIGN PLAN 2 OF 6
‘ACOGSI-004 ELECTRICAL DESIGN PLAN OF 6
‘ACO65'-005 ELECTRICAL DESIGN PLAN 4 OF 6
ACOES'-006 ELECTRICAL DESIGN PLANS OF 6
‘ACOGS!-007 ELECTRICAL DESIGN PLAN 6 OF 6
‘AC065'-008. LV GEOGRAPHIC SCHEMATIC 1 OF 2
‘ACOES'-009 LV GEOGRAPHIC SCHEMATIC 2 OF 2
ACOGS'-010 HV GEOGRAPHIC SCHEMATIC
ACOSSI-ENG! ISOLUX PLOT 1 OF 2
ACOSSI-ENG? _ISOLUXPLOT2OF 2

 

 

 

 

HORIZONTAL DIRECTIONAL DRILLING

CONTRACTOR TO INSTALL DRAW ROPES IN ALL CONDUITS
[AND PLUG, ENSURE THAT CONOUITS ARE INSTALLED AT THE
CORRECT DEPTH AT THE BEGINNING & END OF CONDUIT RUN.
SUPPLY ADAPTORS.

CONSTRUCTION NOTES

4. CONTRACTOR TO INCLUDED PROVISIONAL SUM FOR
VACUUM EXCAVATION AS U.G. SERVICES HAVE BEEN

IDENTIFIED IN THE VICINITY.

CONTRACTOR INCLUDE PROVISIONAL SUM FOR 'CUT AND

REINSTATE CONCRETE FOOTPATH, FULL PANEL AND FILL,

woe,
STATIONS 23.23: VEGETATION CLEARING REQUIRED,
STEEP INCLINES AND DECLINES PRESENT. CIVIL
‘CONTRACTOR TO PROVIDE CLEAR TRENCH AND LEVEL
GROUND FOR PILLAR POSITIONS,

STATIONS 25-26; SHALLOW CONDUIT INSTALLATION
REQUIRED, DIRECTIONAL ORILL NOT APPROPRIATE; OPEN
CUT ROAD TRENCH, SEE SHEET 6 FOR ENERGEX
CROSS-SECTION OETAL,

5. TRAFFIC CONTROL REQUIRED.

CONSTRUCTION NOTES - PRIVATE
PROPERTY
‘THE CONTRACTOR WLL BE RESPONSIBLE FOR THE FOLLOWING:

1 SUPERVISE INSTALLATION OF CONDUITS THE FULL LENGTH OF
THE DRIVEWAY,

 

 

GENERAL NOTES

1, ALLCABLES TO BE INSTALLED IN CONDUIT WITHIN THE
‘STANDARD ELECTRICITY ALIGNMENT OF 250-900mm FROM

PROPERTY BOUNDARY.

‘CONSTRUCTION PERSONNEL SHALL MEASURE ACTUAL

GABLE LENGTHS REQUIRED ON SITE AFTER INSTALLATION

(OF CONDUITS THEN NOTIFY SUPPLIER WHEN CONFIRMING

(CABLE ORDER,

[ALL BENDS INSTALLED ON 125mm RETICULATION

‘CONDUITS MUST BE 1830mm RADIUS UNLESS OTHERWISE,

‘SPECIFIED,

4. CONTRACTOR TO SUPPLY ALL LABELS AND SITE ID
NUMBERS TO ENERGEX SPECIFICATI

'5, ELECTRICAL CONTRACTOR TO SUPPLY AND INSTALL.
‘CONDUITS AS SHOWN IN CIVIL WORK SCHEDULE,

INSTALL ELECTRICAL CONDUIT AND

TELECOMMUNICATIONS PIT AND PIPE IN JOINT USE

TRENCH REFER PROJECT NUMBER ACTON«T

STANDARDS AND SPECIFICATIONS

THIS WORKS PLAN IS TO BE READ IN CONJUNCTION AND
COMPLY WITH THE FOLLOWING ENERGEX MANUALS AND
SPECIFICATIONS:

= UNDERGROUND OISTRISUTION CONSTRUCTION MANUAL,
2 OVERHEAD CONSTRUCTION MANUAL

1 PUBLIC LIGHTING MANUAL

[NETWORK LABELLING AND SIGNAGE MANUAL

FOR DETAILS OF ADDITIONAL TRENCH CROSS-SECTIONS,
REFER TO ENERGEX UNDERGROUND DISTRIBUTION
‘CONSTRUCTION MANUAL,

UG SERVICES INFORMATION

UNDERGROUND SERVICES SHOWN ON THIS WORKS PLAN
INTHE VICINITY OF PROPOSED EXCAVATION WORKS ARE
INDICATIVE ONLY.

‘CONSTRUCTION PERSONNEL SHALL REQUEST ON-SITE
IDENTIFICATION AND LOCATION OF EXISTING BURIED
SERVICES FROM THE QUEENSLAND DIAL BEFORE YOU DIG
SERVICE. PH'1100 FAX:1200 652 077 (A MINIMUM OF TWO DAYS
NOTICE IS REQUIRED)

REFER JOS No; 19158836,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUIT CROSS SECTION - FOOTPATH & ROADWAY
600 FOOTPATH
SO MINOR ROAD
1200 MAVOR ROAD - - -- --
° ° oo oo
DETALO “ETAL =—«(DETALP.=—(OETALE
SURVEY PLAN 00 FOOTPATH
SURVEY PLAN 750 MINOR ROAD
1200 MAVOR ROAD
q v 0 ° 4 =~ 20S 180200 METRES
— SCALE 1.2000 At Se DETAILS DETALY
SCALE 110000 NOTE: Snm PROTECTION COVER STRIP REQUIRED WHEN NOT
\ TN ALLOGATED ENERGEX UG ALIGNMENT
TSSUE [ DESCRIPTION DATE DEVELOPER DETALS AGREE WORKS COORDNATOR [= Approved RUSPOWER CONNECT
"RUSPOWER CONNECTS THE FIRST POINT OF -
A [ORIGINAL 081052020_| CONTACT FOR CONSTRUCTION ENQUIRIES Auspower Connect Pty Ltd [teatnee property erviTo ENERGEX OF [38m PARENT PROJECTNO. [= Curtis Consuting Group SUBDIVISION 5 LOTS INTO 16LOTS PROJECT NO ACtO11
ec porss: [MARK SAIN- DIRECTOR ENERGEXUG_[0- 03m LOTS iat ‘Alex Curtis - RPEQ No, 7917 SET
suddng creer OD SMTA STREETLIGHTS | 0.7m BOK | CANCELLING LOTS Lot 140 MCHETS, Lot? RPEEZODS, ets ELECTRICAL RETIOULATION ENERGEX PROECTNO.
Pudcna LD 4875 Tr NaN REFER DBYD Lot RPIOTI7S, Lot 8 RPtEOTOS, Ke INSTALL 1O0KVA POLE TRANSFORMER,
38° [pROJECT MANAGER DETAILS AS Lot 101 sP142407 AEPROVED DATE” GBS 7070 42m 240mm ALAC UG, 1 PILLARS $4400175
pmeci@banendcom Top CONSULTING PIYLTD HP GAS = Da RALTSO0TS CHECKED MeKennn AANO Tix RATE 2 LED STREETLIGHTS
se doangste wont cthpnennanee® [ous REYNOLOS WATER REFER DBYO_| LOCAL AUTHORITY Noosa Gounel DESIGNER” 5 Whitaker 725 Lake MacDonald Drive,
mintafbewad wateecpchwbesttenpurnisen — [225289 9800 STORMWATER | REFER DBYD_| UBD REF Map 5 O16 PHONE: 0419 707156 A Toi0] at
i: oe er [email protected] REFER DBYD | PEGGED, (On Request ISSUE DATE: Lake MacDonald 4563 ISSUE NO. SHEET 1 OF

 

 

 

 

 

 

 

 

 

 

 

 

 

 
Log in to download the original file

Approved Plans OPW20-0051 1 of 3.pdf · 54.4 MB (very large file)

Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.