4.1 Limitations.

Our site and soil evaluation noted the following limitations which may have an
adverse effect on the performance, serviceability, and sustainability of
environmentally acceptable on-site domestic wastewater management

e allotment size, configuration and topographic idiosyncrasies,

e — separation distance requirements,

e areas previously used or required for construction or landscaping,

e poor permeability of sub soil profile.

In formulating our recommendations we have noted, considered and made allowance
for the effect these limitations will have on the performance, serviceability, and
sustainability of on-site domestic wastewater management. We consider that in line
with the recommendations set out within this report, and with appropriate control
measures in position, sustainable on-site domestic wastewater treatment and disposal
will be achieved.

In consideration of these limitations and with reference to the Queensland Plumbing
and Wastewater Code and AS/NZS1547-2012 On-site Domestic Wastewater
Management, we recommend advanced secondary treatment of all domestic
wastewater flows for the efficient, sustainable and environmentally acceptable
disposal of treated effluent on this allotment. The use of such approved advanced
secondary treatment systems consequentially enables the 30m horizontal separation
distance from the intermittent watercourses/dams to be reduced to 10m, and the
vertical separation distance to be reduced to 300mm.

Although we recorded no existing evidence of eutrification, we believe there is the
potential for eutrification of any associated dam or watercourse if there is nutrient
leakage from any disposal site. However, with our recommended, and appropriate
vegetation planting, with the incorporation of a wastewater treatment system with
nutrient stripping capabilities and with the encouraged use of phosphate free cleaning
products, we believe the reduced potential will be contained.

 

Unearthed Geotechnical P/L. 5 Design Report 022-003
Log in to download the original file

wastewater design.pdf · 13.0 MB (very large file)

Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.